{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"EZC100H4080","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"EZC100H4080","canonicalUrl":"https://aoctrl.com/schneider/EZC100H4080","factsUrl":"https://aoctrl.com/api/mcp/products/EZC100H4080","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact EZC100H, EZC100H4080, 4-pole fixed MCCB, 80 A thermal-magnetic TM-D trip, 100 kA Icu at 240 V AC.","salesMarkdown":"## Breaking capacity — the number that decides the fit The EZC100H4080 carries a 100 kA Icu at 110–130 V AC and 50 kA at 220–240 V AC — meaning it can safely interrupt a fault current up to that level without welding or bursting the contacts. At 380–400 V it still holds 30 kA, and at 550 V AC it holds 10 kA. On DC sides, it is rated 10 kA at 125 V DC (1-pole) and 250 V DC (2-pole). That covers most industrial distribution panels fed by a transformer or a generator step-down. The TM-D trip unit is thermal-magnetic — thermal for overload (inverse-time, responding to RMS heating), magnetic for short-circuit (instantaneous pick-up). The breaker is Category A (no intentional short-time delay), meaning it trips fast on a hard fault — standard for a distribution feeder or branch panel where selectivity is handled upstream with a time-delay breaker or fuse. Fixed-mount on a backplate, front-connected both line and load. The 4-pole body is 100 mm wide, 130 mm tall, 60 mm deep — a compact footprint for a 100 kA-rated 4-pole. Connection pitch is 25 mm, which matches standard busbar spacing. IP20 finger-safe terminals are standard; the enclosure must provide the rest of the ingress protection. IK07 impact rating means it survives a 2 J hammer blow — enough for panel-door mounting if the door is not exposed to heavy tools. The EZC100H4080 is listed as current production (active lifecycle). It is certified to EN/IEC 60947-1 and -2, JIS C8201-2-2, and GB/T 14048.2 — so it is accepted in European, Japanese, and Chinese markets.","metaTitle":"Easypact EZC100H4080 MCCB, 80 A, 100 kA Icu at 240 V","metaDescription":"Schneider EasyPact EZC100H4080 4-pole MCCB, 80 A thermal-magnetic TM-D trip, 100 kA breaking capacity at 240 V AC. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"60 mm","Width":"100 mm","Height":"130 mm","Voltage":"550 V AC 50/60 Hz conforming to IEC 60947-2 250 V DC conforming to IEC 60947-2","IP Rating":"IP20","Application":"Distribution","Control Type":"Toggle","Product Status":"Active","Terminal Pitch":"25 mm","Trip Unit Type":"Thermal-magnetic","Pollution Degree":"3 conforming to IEC 60947","Temp Storage Max":"85 °C","Temp Storage Min":"-35 °C","Breaking Capacity":"10 kA Icu at 125 V DC 1P conforming to IEC 60947-2 10 kA Icu at 250 V DC 2P conforming to IEC 60947-2 10 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 110...130 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 380...400 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 415 V AC 50/60 Hz conforming to IEC 60947-2","Insulation Voltage Ui":"690 V AC 50/60 Hz conforming to IEC 60947-2","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-35...85 °C","Connection Surface Top":"Front","Mechanical Life Cycles":"13000 cycles","Connection Surface Bottom":"Front","Main Product Or Component Type":"Circuit breaker","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/766c1549da7e239f65cabefc7b16e51f.pdf","sourceUrl":"https://www.se.com/ae/en/product/EZC100H4080/circuit-breaker-easypact-ezc100h-tmd-80a-4-poles-3d/","alternativesUrl":"https://aoctrl.com/api/mcp/products/EZC100H4080/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/EZC100H4080","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/EZC100H4080 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}