{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"EZC100H4100","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"EZC100H4100","canonicalUrl":"https://aoctrl.com/schneider/EZC100H4100","factsUrl":"https://aoctrl.com/api/mcp/products/EZC100H4100","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact EZC100H series, EZC100H4100, 4-pole MCCB, 100 A thermal-magnetic TM-D trip unit, 10–100 kA Icu breaking capacity, IEC 60947-2.","salesMarkdown":"The EZC100H4100 is a 4-pole moulded-case circuit breaker from the Schneider Electric EasyPact EZC100H series, rated 100 A at 40 °C with a TM-D thermal-magnetic trip unit. The H breaking capacity code tells you the interrupting rating at the highest-voltage test point: 100 kA Icu at 110–130 V AC, 30 kA at 380–400 V AC, and 10 kA at 550 V AC. The 4-pole configuration with 3t protected poles and no neutral protection means the breaker protects three phases and switches the neutral without a trip element on it — standard for a 3-phase + N distribution board where the neutral is not expected to carry fault current. The 690 V AC rated insulation voltage and 550 V AC maximum operational voltage cover 400/480 V systems with headroom, and the 250 V DC rating makes it usable in DC distribution panels up to that voltage. ## Deployment context The breaker mounts fixed to a backplate with a 25 mm connection pitch — standard for panelboard or switchboard integration. The IP20 degree of protection means it is suitable for installation inside a closed electrical enclosure where no water ingress is expected; the IK07 impact rating provides basic mechanical robustness against accidental tool strikes during panel wiring. It also carries JIS C8201-2-2 and GB/T 14048.2 approvals, covering Japanese and Chinese markets respectively. Pollution degree 3 allows installation in environments with conductive pollution (condensation, light dust), typical of industrial control panels not in a climate-controlled room.","metaTitle":"Schneider Electric EZC100H4100 EasyPact EZC100H 100A 4P MCCB","metaDescription":"Schneider Electric EZC100H4100 EasyPact EZC100H MCCB, 100A thermal-magnetic trip, 4 poles, 10-100kA Icu breaking capacity. Active production, sourced to order. Quoted on request.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"60 mm","Width":"100 mm","Height":"130 mm","Voltage":"550 V AC 50/60 Hz conforming to IEC 60947-2 250 V DC conforming to IEC 60947-2","IP Rating":"IP20","Application":"Distribution","Control Type":"Toggle","Network Type":"DC AC","Product Status":"Active","Terminal Pitch":"25 mm","Trip Unit Type":"Thermal-magnetic","Pollution Degree":"3 conforming to IEC 60947","Temp Storage Max":"85 °C","Temp Storage Min":"-35 °C","Insulation Voltage Ui":"690 V AC 50/60 Hz conforming to IEC 60947-2","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-35...85 °C","Connection Surface Top":"Front","Mechanical Life Cycles":"13000 cycles","Connection Surface Bottom":"Front","Main Product Or Component Type":"Circuit breaker","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$76.41","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/1d86a06b65af136cdb427023eec73361.pdf","sourceUrl":"https://www.se.com/vn/en/product/EZC100H4100/circuit-breaker-easypact-ezc100h-tmd-100a-4-poles-3d/","alternativesUrl":"https://aoctrl.com/api/mcp/products/EZC100H4100/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/EZC100H4100","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/EZC100H4100 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}