{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"EZC100H4100","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"EZC100H4100","canonicalUrl":"https://aoctrl.com/schneider/EZC100H4100","factsUrl":"https://aoctrl.com/api/mcp/products/EZC100H4100","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact EZC100H series, EZC100H4100, 4-pole MCCB, 100 A thermal-magnetic TM-D trip unit, 10–100 kA Icu breaking capacity, IEC 60947-2.","salesMarkdown":"The EZC100H4100 is a 4-pole moulded-case circuit breaker from the Schneider Electric EasyPact EZC100H series, rated 100 A at 40 °C with a TM-D thermal-magnetic trip unit. The H breaking capacity code tells you the interrupting rating at the highest-voltage test point: 100 kA Icu at 110–130 V AC, 30 kA at 380–400 V AC, and 10 kA at 550 V AC. The 4-pole configuration with 3t protected poles and no neutral protection means the breaker protects three phases and switches the neutral without a trip element on it — standard for a 3-phase + N distribution board where the neutral is not expected to carry fault current. The 690 V AC rated insulation voltage and 550 V AC maximum operational voltage cover 400/480 V systems with headroom, and the 250 V DC rating makes it usable in DC distribution panels up to that voltage. ## Deployment context The breaker mounts fixed to a backplate with a 25 mm connection pitch — standard for panelboard or switchboard integration. The IP20 degree of protection means it is suitable for installation inside a closed electrical enclosure where no water ingress is expected; the IK07 impact rating provides basic mechanical robustness against accidental tool strikes during panel wiring. It also carries JIS C8201-2-2 and GB/T 14048.2 approvals, covering Japanese and Chinese markets respectively. Pollution degree 3 allows installation in environments with conductive pollution (condensation, light dust), typical of industrial control panels not in a climate-controlled room.","metaTitle":"Schneider Electric EZC100H4100 EasyPact EZC100H 100A 4P MCCB","metaDescription":"Schneider Electric EZC100H4100 EasyPact EZC100H MCCB, 100A thermal-magnetic trip, 4 poles, 10-100kA Icu breaking capacity. Active production, sourced to order. Quoted on request.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Circuit Breaker Accessories"],"specifications":{"Depth":"60 mm","Width":"100 mm","title":"EZC100H4100","Height":"130 mm","Standards":"EN/IEC 60947-1 EN/IEC 60947-2 JIS C8201-2-2 GB/T 14048.2","description":"circuit breaker, EasyPact EZC100H, TMD, 100A, 4 poles 3d","Control type":"Toggle","Network type":"DC AC","Mounting mode":"Fixed","Trip unit name":"TM-D","Protection type":"Overload protection Short-circuit protection","lifecycle_stage":"current","Connection pitch":"25 mm","Local signalling":"Positive contact indication","Mounting support":"Backplate","Pollution degree":"3 conforming to IEC 60947","Range of product":"EasyPact","Trip unit rating":"100 A at 50 °C","Breaking capacity":"10 kA Icu at 125 V DC 1P conforming to IEC 60947-2 10 kA Icu at 250 V DC 2P conforming to IEC 60947-2 10 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 110...130 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 380...400 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 415 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"Easypact EZC100H","Network frequency":"50/60 Hz","Poles description":"4P","Upside connection":"Front","Device application":"Distribution","[In] rated current":"100 A at 40 °C","Downside connection":"Front","Circuit breaker name":"Easypact EZC100H","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A","Mechanical durability":"13000 cycles","Breaking capacity code":"H","IK degree of protection":"IK07 conforming to EN 50102","IP degree of protection":"IP20 conforming to IEC 60529","Earth-leakage protection":"Without","Product or component type":"Circuit breaker","Suitability for isolation":"Yes conforming to IEC 60947-2","Neutral protection setting":"Without protection","Protected poles description":"3t","[Ui] rated insulation voltage":"690 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"550 V AC 50/60 Hz conforming to IEC 60947-2 250 V DC conforming to IEC 60947-2","Ambient air temperature for storage":"-35...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"5 kA at 125 V DC conforming to IEC 60947-2 5 kA at 250 V DC conforming to IEC 60947-2 5 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 2.5 kA at 550 V AC 50/60 Hz conforming to IEC 60947-2 15 kA at 380...400 V AC 50/60 Hz conforming to IEC 60947-2 25 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 110...130 V AC 50/60 Hz conforming to IEC 60947-2 7.5 kA at 415 V AC 50/60 Hz conforming to IEC 60947-2","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$76.41","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/1d86a06b65af136cdb427023eec73361.pdf","sourceUrl":"https://www.se.com/vn/en/product/EZC100H4100/circuit-breaker-easypact-ezc100h-tmd-100a-4-poles-3d/"},"ai":{"faq":[{"question":"Where can I buy EZC100H4100 and get a price?","answer":"The EZC100H4100 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead-time estimate."},{"question":"What is the breaking capacity of EZC100H4100 at 400 V?","answer":"At 380–400 V AC 50/60 Hz, the EZC100H4100 delivers 30 kA Icu per IEC 60947-2. This is the maximum fault current the breaker can safely interrupt at that voltage level."},{"question":"What compliance documentation does EZC100H4100 carry?","answer":"The breaker is certified to EN/IEC 60947-1, EN/IEC 60947-2, JIS C8201-2-2, and GB/T 14048.2. It is suitable for isolation per IEC 60947-2 and carries IP20 and IK07 protection ratings."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/EZC100H4100","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/EZC100H4100 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-07-22T19:47:38.189Z","lastPublished":"2026-07-22T19:47:38.189Z","indexable":true}}