{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"EZC100N1015","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"EZC100N1015","canonicalUrl":"https://aoctrl.com/schneider/EZC100N1015","factsUrl":"https://aoctrl.com/api/mcp/products/EZC100N1015","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact EZC100N, EZC100N1015, 1-pole thermal-magnetic circuit breaker, 15 A rated current, 25 kA breaking capacity at 110-130 V AC, IP20, backplate mount.","salesMarkdown":"The Schneider Electric EZC100N1015 is a 1-pole thermal-magnetic circuit breaker from the EasyPact EZC100N series, rated 15 A at 40 °C (15 A at 50 °C with the TM-D trip unit). It's built for distribution duty in fixed-mount panels — backplate mounted, front-connected, and toggled manually. The 25 mm width per pole keeps the rail density tight; a 13000-cycle mechanical durability means it'll outlast most panel refreshes. The EZC100N1015 carries a 25 kA Icu at 110-130 V AC and 18 kA at 220-240 V AC per IEC 60947-2. That's the N breaking capacity code — enough for most secondary distribution panels behind a larger main breaker. At 400-415 V AC it drops to 2.5 kA, so if your line side is 400 V with high fault current, this needs upstream coordination. The 5 kA at 125 V DC (1-pole) covers DC bus or battery circuits. Fixed backplate mount, 25 mm pitch per pole, front connections top and bottom. IP20 finger-safe terminals, pollution degree 3 rated — fine for a clean panel environment. The toggle actuator gives positive contact indication; the thermal-magnetic trip handles both overload and short-circuit without an external relay.","metaTitle":"Schneider Electric EZC100N1015 EasyPact EZC100N Circuit Brea","metaDescription":"Schneider Electric EZC100N1015 EasyPact EZC100N miniature circuit breaker, 15 A thermal-magnetic, 1-pole, 25 kA breaking capacity at 110-130 V AC. Sourced to order against an RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":[],"specifications":{"Depth":"60 mm","Width":"25 mm","Height":"130 mm","Voltage":"125 V DC conforming to IEC 60947-2 415 V AC 50/60 Hz conforming to IEC 60947-2","IP Rating":"IP20","Application":"Distribution","Control Type":"Toggle","Network Type":"DC AC","Product Status":"Active","Terminal Pitch":"25 mm","Trip Unit Type":"Thermal-magnetic","Pollution Degree":"3 conforming to IEC 60664-1 3 conforming to IEC 947-1","Temp Storage Max":"85 °C","Temp Storage Min":"-35 °C","Breaking Capacity":"25 kA Icu at 110...130 V AC 50/60 Hz conforming to IEC 60947-2 5 kA Icu at 125 V DC 1P conforming to IEC 60947-2 18 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 2.5 kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2 2.5 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2","Insulation Voltage Ui":"690 V AC 50/60 Hz conforming to IEC 60947-2","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-35...85 °C","Connection Surface Top":"Front","Mechanical Life Cycles":"13000 cycles","Connection Surface Bottom":"Front","Main Product Or Component Type":"Circuit breaker","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/a6195588d470c5887ad170123fd20012.pdf","sourceUrl":"https://www.se.com/ae/en/product/EZC100N1015/circuit-breaker-easypact-ezc100n-tmd-15-a-1-pole-1d/","alternativesUrl":"https://aoctrl.com/api/mcp/products/EZC100N1015/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/EZC100N1015","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/EZC100N1015 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}