{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"EZC100N1080","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"EZC100N1080","canonicalUrl":"https://aoctrl.com/schneider/EZC100N1080","factsUrl":"https://aoctrl.com/api/mcp/products/EZC100N1080","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact EZC100N, circuit breaker, EZC100N1080, 80 A, 1P, 25 kA Icu at 110-130 V AC, thermal-magnetic TM-D trip unit.","salesMarkdown":"## Panel fit and protection profile The Schneider Electric EZC100N1080 is an EasyPact EZC100N circuit breaker — a 1-pole, 80 A thermal-magnetic unit with a TM-D trip curve, sized for distribution panels where a single-phase or DC branch needs short-circuit and overload protection. The 25 mm width per pole keeps the DIN-rail fill factor tight; at 80 A rated current (40 °C ambient, derated to 80 A at 50 °C), it covers feeder and subfeeder duty in a 415 V AC or 125 V DC system. Breaking capacity hits 25 kA Icu at 110-130 V AC, dropping to 18 kA at 220-240 V AC and 2.5 kA at 400-415 V AC — so the upstream fault current available at the panelboard determines which voltage tap you can land it on.","metaTitle":"Schneider Electric EZC100N1080 EasyPact EZC100N, 80 A, 1P, 2","metaDescription":"Schneider Electric EZC100N1080 EasyPact EZC100N circuit breaker, 80 A thermal-magnetic, 1-pole, 25 kA breaking capacity at 110-130 V AC. IEC 60947-2. Current lifecycle stage. Sourc","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Circuit Breaker Accessories"],"specifications":{"Depth":"60 mm","Width":"25 mm","title":"EZC100N1080","Height":"130 mm","Standards":"EN/IEC 60947-1 GB/T 14048.2 EN/IEC 60947-2 JIS C8201-2-2","description":"circuit breaker Easypact EZC100N - TMD - 80 A - 1 pole 1d","Control type":"Toggle","Network type":"DC AC","Mounting mode":"Fixed","Trip unit name":"TM-D","Protection type":"Short-circuit protection Overload protection","lifecycle_stage":"current","Connection pitch":"25 mm","Local signalling":"Positive contact indication","Mounting support":"Backplate","Pollution degree":"3 conforming to IEC 60664-1 3 conforming to IEC 947-1","Range of product":"EasyPact","Trip unit rating":"80 A at 50 °C","Breaking capacity":"25 kA Icu at 110...130 V AC 50/60 Hz conforming to IEC 60947-2 5 kA Icu at 125 V DC 1P conforming to IEC 60947-2 18 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 2.5 kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2 2.5 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"Easypact EZC100N","Network frequency":"50/60 Hz","Poles description":"1P","Upside connection":"Front","Device application":"Distribution","[In] rated current":"80 A at 40 °C","Downside connection":"Front","Circuit breaker name":"Easypact EZC100N","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A","Mechanical durability":"13000 cycles","Breaking capacity code":"N","IK degree of protection":"IK07 conforming to IEC 62262","IP degree of protection":"IP20 conforming to IEC 60529","Earth-leakage protection":"Without","Product or component type":"Circuit breaker","Suitability for isolation":"Yes conforming to IEC 60947-2","Neutral protection setting":"Without protection","Protected poles description":"1t","[Ui] rated insulation voltage":"690 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"125 V DC conforming to IEC 60947-2 415 V AC 50/60 Hz conforming to IEC 60947-2","Ambient air temperature for storage":"-35...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"12.5 kA at 110/130 V AC 50/60 Hz conforming to IEC 60947-2 2.5 kA at 125 V DC conforming to IEC 60947-2 9 kA at 220/230/240 V AC 50/60 Hz conforming to IEC 60947-2 1.25 kA at 380 V AC 50/60 Hz conforming to IEC 60947-2 1.25 kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$39.96","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/55bcd6a120e6adfb23f2b7c4cf5269c7.pdf","sourceUrl":"https://www.se.com/ae/en/product/EZC100N1080/circuit-breaker-easypact-ezc100n-tmd-80-a-1-pole-1d/"},"ai":{"faq":[{"question":"What is the breaking capacity of the EZC100N1080 at 240 V AC?","answer":"At 220-240 V AC 50/60 Hz, the EZC100N1080 delivers 18 kA Icu per IEC 60947-2."},{"question":"What standards does the EZC100N1080 comply with?","answer":"The EZC100N1080 is certified to EN/IEC 60947-1, GB/T 14048.2, EN/IEC 60947-2, and JIS C8201-2-2."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/EZC100N1080","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/EZC100N1080 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-07-22T19:47:38.189Z","lastPublished":"2026-07-22T19:47:38.189Z","indexable":true}}