{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"EZC100N3020","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"EZC100N3020","canonicalUrl":"https://aoctrl.com/schneider/EZC100N3020","factsUrl":"https://aoctrl.com/api/mcp/products/EZC100N3020","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact EZC100N, EZC100N3020, 3-pole thermal-magnetic circuit breaker, 20 A rated current, 10 kA Icu at 440 V AC, TM-D trip unit.","salesMarkdown":"The Schneider Electric EZC100N3020 is a 3-pole thermal-magnetic circuit breaker from the EasyPact EZC100N series, rated 20 A at 40 °C with a TM-D trip unit. It provides short-circuit and overload protection for distribution circuits in fixed-mount backplate panels. At 380 V AC the breaking capacity rises to 18 kA Icu, and at 240 V AC to 25 kA Icu, giving flexibility across common supply voltages. The trip unit rating is 20 A at 50 °C, while the rated current [In] is listed as 20 A at 40 °C. Rated operational voltage (Ue) goes to 550 V AC and 250 V DC, covering most industrial AC supplies and DC control circuits. Fixed mounting on a backplate — no DIN-rail adapter, so plan for screw-mounting in the panel. Connection pitch is 25 mm, which matches standard distribution-block spacing. The toggle control provides positive contact indication — you can see the mechanism position, not just a flag. IP20 finger-safe front; IK07 impact resistance handles accidental tool drops during commissioning. Certified to EN/IEC 60947-1, EN/IEC 60947-2, JIS C8201-2-2, and GB/T 14048.2. Mechanical durability is 13,000 cycles — adequate for a distribution breaker that cycles infrequently.","metaTitle":"Schneider Electric EZC100N3020 EasyPact EZC100N Circuit Brea","metaDescription":"Schneider Electric EZC100N3020 EasyPact EZC100N thermal-magnetic circuit breaker, 20 A rated current, 3 poles, 10 kA breaking capacity at 440 V AC. Sourced to order against an RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Circuit Breaker Accessories"],"specifications":{"Depth":"60 mm","Width":"75 mm","title":"EZC100N3020","Height":"130 mm","Standards":"EN/IEC 60947-1 JIS C8201-2-2 EN/IEC 60947-2 GB/T 14048.2","description":"circuit breaker Easypact EZC100N - TMD - 20 A - 3 poles 3d","Control type":"Toggle","Network type":"DC AC","Mounting mode":"Fixed","Trip unit name":"TM-D","Protection type":"Short-circuit protection Overload protection","lifecycle_stage":"current","Connection pitch":"25 mm","Local signalling":"Positive contact indication","Mounting support":"Backplate","Pollution degree":"3 conforming to IEC 60664-1 3 conforming to IEC 947-1","Range of product":"EasyPact","Trip unit rating":"20 A at 50 °C","Breaking capacity":"10 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2 18 kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 110...130 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 5 kA Icu at 125 V DC 1P conforming to IEC 60947-2 5 kA Icu at 250 V DC 2P conforming to IEC 60947-2 5 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"Easypact EZC100N","Network frequency":"50/60 Hz","Poles description":"3P","Upside connection":"Front","Device application":"Distribution","[In] rated current":"20 A at 40 °C","Downside connection":"Front","Circuit breaker name":"Easypact EZC100N","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A","Mechanical durability":"13000 cycles","Breaking capacity code":"N","IK degree of protection":"IK07 conforming to IEC 62262","IP degree of protection":"IP20 conforming to IEC 60529","Earth-leakage protection":"Without","Product or component type":"Circuit breaker","Suitability for isolation":"Yes conforming to IEC 60947-2","Neutral protection setting":"Without protection","Protected poles description":"3t","[Ui] rated insulation voltage":"690 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"550 V AC 50/60 Hz conforming to IEC 60947-2 250 V DC conforming to IEC 60947-2","Ambient air temperature for storage":"-35...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"5 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 9 kA at 380 V AC 50/60 Hz conforming to IEC 60947-2 12.5 kA at 110/130 V AC 50/60 Hz conforming to IEC 60947-2 12.5 kA at 220/230/240 V AC 50/60 Hz conforming to IEC 60947-2 2.5 kA at 125 V DC conforming to IEC 60947-2 2.5 kA at 250 V DC conforming to IEC 60947-2 2.5 kA at 550 V AC 50/60 Hz conforming to IEC 60947-2 7.5 kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$49.96","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/274f3197eb5e933596df6c6010f1a991.pdf","sourceUrl":"https://www.se.com/ae/en/product/EZC100N3020/circuit-breaker-easypact-ezc100n-tmd-20-a-3-poles-3d/"},"ai":{"faq":[{"question":"Who supplies EZC100N3020 and how is it quoted for volume purchases?","answer":"The EZC100N3020 is sourced through independent distribution and quoted to order against an RFQ. Availability and current pricing are confirmed at quote time."},{"question":"What is the closest alternative to EZC100N3020 in the EasyPact family?","answer":"Within the same EZC100N frame, the closest sibling would be a different trip rating — the mechanical footprint, breaking capacity, and terminal layout are identical across the range. The deciding factor is the load current: select the variant whose TM-D trip rating matches your circuit's continuous load."},{"question":"What is EZC100N3020's listed depth?","answer":"The depth is 60 mm."},{"question":"What is EZC100N3020's listed width?","answer":"The width is 75 mm."},{"question":"What compliance documentation does Schneider provide for EZC100N3020?","answer":"The breaker carries certifications to EN/IEC 60947-1, EN/IEC 60947-2, JIS C8201-2-2, and GB/T 14048.2. It is suitable for isolation per IEC 60947-2. RoHS and REACH declarations are standard Schneider documentation available on request."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/EZC100N3020","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/EZC100N3020 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-07-22T19:47:38.189Z","lastPublished":"2026-07-22T19:47:38.189Z","indexable":true}}