{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"EZC100N3025","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"EZC100N3025","canonicalUrl":"https://aoctrl.com/schneider/EZC100N3025","factsUrl":"https://aoctrl.com/api/mcp/products/EZC100N3025","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact EZC100N, 3-pole circuit breaker, 25 A thermal-magnetic TM-D trip unit, 10 kA Icu at 440 V AC, IEC 60947-2.","salesMarkdown":"The EZC100N3025 is a 3-pole EasyPact EZC100N circuit breaker with a thermal-magnetic TM-D trip unit rated 25 A at 40 °C (25 A at 50 °C). For a distribution panel feeding a 25 A lighting or small motor load, this is the right pick. Breaking capacity is the real selector here. At 400…415 V it jumps to 15 kA, and at 380 V it hits 18 kA. For a 220…240 V supply, it clears 25 kA. For isolation duty, it's certified per IEC 60947-2, meaning the open contacts provide a visible gap you can lock out. Mounting is fixed (backplate) with front-front connections — both line and load terminate on the front face, which simplifies busbar layout in a panel. The 25 mm connection pitch matches standard distribution busbar systems. IP20 finger-safe terminals, IK07 impact resistance. The EZC100N3025 carries approvals to GB/T 14048.2, EN/IEC 60947-1, EN/IEC 60947-2, and JIS C8201-2-2. That's the full suite for distribution circuit breakers in industrial and commercial panels — the IEC 60947-2 mark is what most specifiers need for a switchboard or MCC.","metaTitle":"EZC100N3025 EasyPact EZC100N 25A 3P Circuit Breaker, 10kA","metaDescription":"EZC100N3025 EasyPact EZC100N 3-pole circuit breaker, 25 A thermal-magnetic TM-D trip, 10 kA breaking capacity at 440 V AC. IEC 60947-2. Current lifecycle. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Circuit Breaker Accessories"],"specifications":{"Depth":"60 mm","Width":"75 mm","Height":"130 mm","Standards":"GB/T 14048.2 EN/IEC 60947-1 EN/IEC 60947-2 JIS C8201-2-2","Control type":"Toggle","Network type":"DC AC","Mounting mode":"Fixed","Trip unit name":"TM-D","Protection type":"Short-circuit protection Overload protection","lifecycle_stage":"current","Connection pitch":"25 mm","Local signalling":"Positive contact indication","Mounting support":"Backplate","Pollution degree":"3 conforming to IEC 60664-1 3 conforming to IEC 947-1","Range of product":"EasyPact","Trip unit rating":"25 A at 50 °C","Breaking capacity":"10 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2 18 kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 110...130 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 5 kA Icu at 125 V DC 1P conforming to IEC 60947-2 5 kA Icu at 250 V DC 2P conforming to IEC 60947-2 5 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"Easypact EZC100N","Network frequency":"50/60 Hz","Poles description":"3P","Upside connection":"Front","Device application":"Distribution","[In] rated current":"25 A at 40 °C","Downside connection":"Front","Circuit breaker name":"Easypact EZC100N","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A","Mechanical durability":"13000 cycles","Breaking capacity code":"N","IK degree of protection":"IK07 conforming to IEC 62262","IP degree of protection":"IP20 conforming to IEC 60529","Earth-leakage protection":"Without","Product or component type":"Circuit breaker","Suitability for isolation":"Yes conforming to IEC 60947-2","Neutral protection setting":"Without protection","Protected poles description":"3t","[Ui] rated insulation voltage":"690 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"550 V AC 50/60 Hz conforming to IEC 60947-2 250 V DC conforming to IEC 60947-2","Ambient air temperature for storage":"-35...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"5 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 9 kA at 380 V AC 50/60 Hz conforming to IEC 60947-2 12.5 kA at 110/130 V AC 50/60 Hz conforming to IEC 60947-2 12.5 kA at 220/230/240 V AC 50/60 Hz conforming to IEC 60947-2 2.5 kA at 125 V DC conforming to IEC 60947-2 2.5 kA at 250 V DC conforming to IEC 60947-2 2.5 kA at 550 V AC 50/60 Hz conforming to IEC 60947-2 7.5 kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$49.96","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/ac9718ae8cfc3c601e17a9486dfd2a5e.pdf","sourceUrl":"https://www.se.com/ph/en/product/EZC100N3025/circuit-breaker-easypact-ezc100n-tmd-25-a-3-poles-3d/","alternativesUrl":"https://aoctrl.com/api/mcp/products/EZC100N3025/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for EZC100N3025?","answer":"Submit an RFQ with the order code and quantity. We source this active part through independent distribution and confirm availability and current pricing at quote time — no stock count or price figure is published here because both change with the supply chain."},{"question":"What is EZC100N3025's breaking capacity at 440 V AC?","answer":"The Icu (ultimate breaking capacity) is 10 kA at 440 V AC 50/60 Hz per IEC 60947-2. At 400…415 V it rises to 15 kA, and at 380 V to 18 kA."},{"question":"What compliance documentation does this brand provide for EZC100N3025?","answer":"The breaker is certified to GB/T 14048.2, EN/IEC 60947-1, EN/IEC 60947-2, and JIS C8201-2-2. It carries IP20 finger protection and IK07 impact resistance. Isolation suitability is confirmed per IEC 60947-2."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/EZC100N3025","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/EZC100N3025 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}