{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"EZC100N3032","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"EZC100N3032","canonicalUrl":"https://aoctrl.com/schneider/EZC100N3032","factsUrl":"https://aoctrl.com/api/mcp/products/EZC100N3032","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact EZC100N series, EZC100N3032, 3-pole molded case circuit breaker, 32 A rated current, thermal-magnetic TM-D trip unit, 10 kA Icu at 440 V AC.","salesMarkdown":"This is a distribution-grade MCCB from the EasyPact EZC100N family, built for fixed backplate mounting with front-front connections. The 32 A rating at 50 °C means it carries full current in a warm panel without derating — relevant when the breaker shares an enclosure with other heat sources. Breaking capacity follows the voltage: 10 kA Icu at 440 V AC, 18 kA at 380–400 V, 25 kA at 220–240 V, and 5 kA at 550 V AC or 250 V DC (2P). The DC ratings (5 kA at 125 V DC 1P, 5 kA at 250 V DC 2P) cover control-circuit and battery-string protection, though this is primarily an AC distribution breaker. The 32 A TM-D trip unit provides overload and short-circuit protection. Dimensions: 75 mm wide, 130 mm high, 60 mm deep. The 25 mm connection pitch is standard for this frame size; front-front connections simplify panel layout and busbar routing. It also meets JIS C8201-2-2 and GB/T 14048.2, covering Japanese and Chinese installation codes respectively.","metaTitle":"Schneider EasyPact EZC100N3032 32A MCCB, 10kA at 440V","metaDescription":"Schneider Electric EasyPact EZC100N3032 3P MCCB, 32A thermal-magnetic TM-D trip unit, 10kA Icu at 440V AC. IEC 60947-2, IP20, current production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Circuit Breaker Accessories"],"specifications":{"Depth":"60 mm","Width":"75 mm","title":"EZC100N3032","Height":"130 mm","Standards":"JIS C8201-2-2 EN/IEC 60947-1 GB/T 14048.2 EN/IEC 60947-2","description":"circuit breaker Easypact EZC100N - TMD - 32 A - 3 poles 3d","Control type":"Toggle","Network type":"AC DC","Mounting mode":"Fixed","Trip unit name":"TM-D","Protection type":"Overload protection Short-circuit protection","lifecycle_stage":"current","Connection pitch":"25 mm","Local signalling":"Positive contact indication","Mounting support":"Backplate","Pollution degree":"3 conforming to IEC 60947","Range of product":"EasyPact","Trip unit rating":"32 A at 50 °C","Breaking capacity":"10 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 110...130 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 5 kA Icu at 125 V DC 1P conforming to IEC 60947-2 5 kA Icu at 250 V DC 2P conforming to IEC 60947-2 5 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 415 V AC 50/60 Hz conforming to IEC 60947-2 18 kA Icu at 380...400 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"Easypact EZC100N","Network frequency":"50/60 Hz","Poles description":"3P","Upside connection":"Front","Device application":"Distribution","[In] rated current":"32 A at 40 °C","Downside connection":"Front","Circuit breaker name":"Easypact EZC100N","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A","Mechanical durability":"13000 cycles","Breaking capacity code":"N","IK degree of protection":"IK07 conforming to EN 50102","IP degree of protection":"IP20 conforming to IEC 60529","Earth-leakage protection":"Without","Product or component type":"Circuit breaker","Suitability for isolation":"Yes conforming to IEC 60947-2","Neutral protection setting":"Without protection","Protected poles description":"3t","[Ui] rated insulation voltage":"690 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"550 V AC 50/60 Hz conforming to IEC 60947-2 250 V DC conforming to IEC 60947-2","Ambient air temperature for storage":"-35...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"5 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 2.5 kA at 125 V DC conforming to IEC 60947-2 2.5 kA at 250 V DC conforming to IEC 60947-2 2.5 kA at 550 V AC 50/60 Hz conforming to IEC 60947-2 12.5 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 12.5 kA at 110...130 V AC 50/60 Hz conforming to IEC 60947-2 9 kA at 380...400 V AC 50/60 Hz conforming to IEC 60947-2 7.5 kA at 415 V AC 50/60 Hz conforming to IEC 60947-2","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$49.96","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/0389184a5694471b9f380f27c8996c85.pdf","sourceUrl":"https://www.se.com/ng/en/product/EZC100N3032/circuit-breaker-easypact-ezc100n-tmd-32-a-3-poles-3d/"},"ai":{"faq":[{"question":"What is the breaking capacity of the EZC100N3032 at 440 V?","answer":"10 kA Icu at 440 V AC 50/60 Hz per IEC 60947-2. At 380–400 V it rises to 18 kA, and at 220–240 V to 25 kA. For DC applications, it is rated 5 kA at 125 V DC (1P) and 5 kA at 250 V DC (2P)."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/EZC100N3032","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/EZC100N3032 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-07-22T19:47:38.189Z","lastPublished":"2026-07-22T19:47:38.189Z","indexable":true}}