{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"EZC100N3060","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"EZC100N3060","canonicalUrl":"https://aoctrl.com/schneider/EZC100N3060","factsUrl":"https://aoctrl.com/api/mcp/products/EZC100N3060","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact EZC100N series, EZC100N3060, 3-pole thermal-magnetic circuit breaker, 60 A rated current, 10 kA breaking capacity at 440 V AC, IP20, backplate mount.","salesMarkdown":"The Schneider Electric EZC100N3060 is a 3-pole thermal-magnetic circuit breaker from the EasyPact EZC100N series, rated 60 A at 40 °C ambient. Breaking capacity hits 10 kA Icu at 440 V AC (50/60 Hz) per IEC 60947-2 — enough for most light industrial distribution panels. It is also rated 15 kA at 400–415 V, 18 kA at 380 V, and 25 kA at 220–240 V, so the same unit covers different line voltages without swapping frame sizes. Fixed backplate mount, not DIN rail. Connection pitch is 25 mm. IP20 finger-safe terminals; IK07 impact rating means it can take a tool drop without cracking the housing. ## Key ratings in context Operational voltage (Ue) goes to 550 V AC and 250 V DC (2-pole series connection). The 60 A trip rating is at 40 °C; at 50 °C the same trip unit holds 60 A (no derate needed up to that point). Mechanical durability is 13,000 cycles — fine for a distribution breaker that operates a few times a year, but not rated for frequent switching duty.","metaTitle":"Schneider EasyPact EZC100N3060 3P 60A Circuit Breaker, 10kA","metaDescription":"EZC100N3060 is a Schneider EasyPact EZC100N 3-pole thermal-magnetic circuit breaker, 60A rated, 10kA breaking capacity at 440V AC. Current lifecycle. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"60 mm","Width":"75 mm","Height":"130 mm","Voltage":"550 V AC 50/60 Hz conforming to IEC 60947-2 250 V DC conforming to IEC 60947-2","IP Rating":"IP20","Application":"Distribution","Control Type":"Toggle","Product Status":"Active","Terminal Pitch":"25 mm","Trip Unit Type":"Thermal-magnetic","Pollution Degree":"3 conforming to IEC 60664-1 3 conforming to IEC 947-1","Temp Storage Max":"85 °C","Temp Storage Min":"-35 °C","Breaking Capacity":"10 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2 18 kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 110...130 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 5 kA Icu at 125 V DC 1P conforming to IEC 60947-2 5 kA Icu at 250 V DC 2P conforming to IEC 60947-2 5 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2","Insulation Voltage Ui":"690 V AC 50/60 Hz conforming to IEC 60947-2","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-35...85 °C","Connection Surface Top":"Front","Mechanical Life Cycles":"13000 cycles","Connection Surface Bottom":"Front","Main Product Or Component Type":"Circuit breaker","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$49.96","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/822f65e830027df49d1851625bd99296.pdf","sourceUrl":"https://www.se.com/ae/en/product/EZC100N3060/circuit-breaker-easypact-ezc100n-tmd-60-a-3-poles-3d/","alternativesUrl":"https://aoctrl.com/api/mcp/products/EZC100N3060/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/EZC100N3060","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/EZC100N3060 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}