{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"EZC100N3100","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"EZC100N3100","canonicalUrl":"https://aoctrl.com/schneider/EZC100N3100","factsUrl":"https://aoctrl.com/api/mcp/products/EZC100N3100","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact EZC100N series, EZC100N3100, 3-pole MCCB, 100 A thermal-magnetic trip unit (TM-D), 10 kA Icu at 440 V AC, fixed mount, toggle control.","salesMarkdown":"The Schneider Electric EZC100N3100 is a 3-pole EasyPact EZC100N moulded-case circuit breaker (MCCB) with a thermal-magnetic TM-D trip unit rated 100 A at 50 °C. At 400–415 V the interrupting rating rises to 15 kA Icu, and at 380 V it reaches 18 kA Icu. For DC applications, it interrupts 5 kA Icu at 125 V DC (1-pole) or 250 V DC (2-pole). This MCCB is a fixed-mount, backplate-supported device with front-front connections (line and load both terminate on the front face). The toggle actuator provides positive contact indication, so you can visually confirm the contact position without removing the cover. IP20 finger protection and IK07 impact resistance suit it for enclosure mounting where incidental contact is possible but washdown or dust ingress is not expected. ## Protection and compliance The EZC100N3100 provides short-circuit and overload protection for distribution circuits. It is Category A (no intentional short-time delay), meaning it trips instantaneously on a fault — suitable for feeder protection where selectivity is achieved upstream. Standards compliance includes EN/IEC 60947-1, EN/IEC 60947-2, GB/T 14048.2, and JIS C8201-2-2.","metaTitle":"Schneider Electric EZC100N3100 EasyPact EZC100N 100A 3P MCCB","metaDescription":"Schneider Electric EZC100N3100 EasyPact EZC100N MCCB, 100A thermal-magnetic trip, 3-pole, 10kA Icu at 440V AC. Current lifecycle stage, sourced to order. EN/IEC 60947-2.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Circuit Breaker Accessories"],"specifications":{"Depth":"60 mm","Width":"75 mm","title":"EZC100N3100","Height":"130 mm","Standards":"EN/IEC 60947-1 GB/T 14048.2 EN/IEC 60947-2 JIS C8201-2-2","description":"circuit breaker Easypact EZC100N - TMD - 100 A - 3 poles 3d","Control type":"Toggle","Network type":"DC AC","Mounting mode":"Fixed","Trip unit name":"TM-D","Protection type":"Short-circuit protection Overload protection","lifecycle_stage":"current","Connection pitch":"25 mm","Local signalling":"Positive contact indication","Mounting support":"Backplate","Pollution degree":"3 conforming to IEC 60664-1 3 conforming to IEC 947-1","Range of product":"EasyPact","Trip unit rating":"100 A at 50 °C","Breaking capacity":"10 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2 18 kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 110...130 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 5 kA Icu at 125 V DC 1P conforming to IEC 60947-2 5 kA Icu at 250 V DC 2P conforming to IEC 60947-2 5 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"Easypact EZC100N","Network frequency":"50/60 Hz","Poles description":"3P","Upside connection":"Front","Device application":"Distribution","[In] rated current":"100 A at 40 °C","Downside connection":"Front","Circuit breaker name":"Easypact EZC100N","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A","Mechanical durability":"13000 cycles","Breaking capacity code":"N","IK degree of protection":"IK07 conforming to IEC 62262","IP degree of protection":"IP20 conforming to IEC 60529","Earth-leakage protection":"Without","Product or component type":"Circuit breaker","Suitability for isolation":"Yes conforming to IEC 60947-2","Neutral protection setting":"Without protection","Protected poles description":"3t","[Ui] rated insulation voltage":"690 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"550 V AC 50/60 Hz conforming to IEC 60947-2 250 V DC conforming to IEC 60947-2","Ambient air temperature for storage":"-35...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"5 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 9 kA at 380 V AC 50/60 Hz conforming to IEC 60947-2 12.5 kA at 110/130 V AC 50/60 Hz conforming to IEC 60947-2 12.5 kA at 220/230/240 V AC 50/60 Hz conforming to IEC 60947-2 2.5 kA at 125 V DC conforming to IEC 60947-2 2.5 kA at 250 V DC conforming to IEC 60947-2 2.5 kA at 550 V AC 50/60 Hz conforming to IEC 60947-2 7.5 kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$49.96","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/ac5080846872b38e39da2ba3567381a0.pdf","sourceUrl":"https://www.se.com/ae/en/product/EZC100N3100/circuit-breaker-easypact-ezc100n-tmd-100-a-3-poles-3d/"},"ai":{"faq":[{"question":"What is the breaking capacity of EZC100N3100 at 440 V?","answer":"The EZC100N3100 has a breaking capacity of 10 kA Icu at 440 V AC 50/60 Hz per IEC 60947-2."},{"question":"What trip unit does the EZC100N3100 use?","answer":"It uses a TM-D thermal-magnetic trip unit rated 100 A at 50 °C."},{"question":"Where can I buy the EZC100N3100?","answer":"The EZC100N3100 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at the time of quote."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/EZC100N3100","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/EZC100N3100 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-07-22T19:47:38.189Z","lastPublished":"2026-07-22T19:47:38.189Z","indexable":true}}