{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"EZC100N4032","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"EZC100N4032","canonicalUrl":"https://aoctrl.com/schneider/EZC100N4032","factsUrl":"https://aoctrl.com/api/mcp/products/EZC100N4032","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact EZC100N, 4-pole MCCB, 32 A, TM-D thermal-magnetic trip unit, 10 kA Icu at 440 V AC.","salesMarkdown":"The Schneider Electric EasyPact EZC100N4032 is a 4-pole molded-case circuit breaker (MCCB) from the EasyPact range, fitted with a TM-D thermal-magnetic trip unit rated 32 A at 40 °C (32 A at 50 °C). ## Breaking capacity — the number that matters for fault clearance The EZC100N4032 carries a breaking capacity code N, delivering 10 kA Icu at 440 V AC 50/60 Hz per IEC 60947-2. At 380–400 V AC that climbs to 18 kA Icu; at 415 V AC it's 15 kA Icu. For DC circuits, it clears 5 kA Icu at 125 V DC (1-pole) or 250 V DC (2-pole). Show me the rating, then decide. Fixed backplate mounting with front connections (upside and downside). The 4-pole footprint measures 100 mm wide × 130 mm high × 60 mm deep, with a 25 mm connection pitch. Rated IP20 (finger-safe) and IK07 impact resistance, so it's suited for enclosed distribution boards where personnel access is restricted to qualified hands. No earth-leakage protection module integrated; if you need that, it's an external add-on.","metaTitle":"Schneider EasyPact EZC100N4032 4P 32A MCCB, 10kA at 440V","metaDescription":"Schneider Electric EasyPact EZC100N4032 4P 32A MCCB, TM-D trip unit, 10 kA Icu at 440 V AC. Quoted to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"60 mm","Width":"100 mm","Height":"130 mm","Voltage":"550 V AC 50/60 Hz conforming to IEC 60947-2 250 V DC conforming to IEC 60947-2","IP Rating":"IP20","Application":"Distribution","Control Type":"Toggle","Network Type":"DC AC","Product Status":"Active","Terminal Pitch":"25 mm","Trip Unit Type":"Thermal-magnetic","Pollution Degree":"3 conforming to IEC 60947","Temp Storage Max":"85 °C","Temp Storage Min":"-35 °C","Breaking Capacity":"10 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 110...130 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 5 kA Icu at 125 V DC 1P conforming to IEC 60947-2 5 kA Icu at 250 V DC 2P conforming to IEC 60947-2 5 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 415 V AC 50/60 Hz conforming to IEC 60947-2 18 kA Icu at 380...400 V AC 50/60 Hz conforming to IEC 60947-2","Insulation Voltage Ui":"690 V AC 50/60 Hz conforming to IEC 60947-2","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-35...85 °C","Connection Surface Top":"Front","Mechanical Life Cycles":"13000 cycles","Connection Surface Bottom":"Front","Main Product Or Component Type":"Circuit breaker","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$64.95","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/72d7ffb4cb2090304e6fa3ec466f534c.pdf","sourceUrl":"https://www.se.com/vn/en/product/EZC100N4032/circuit-breaker-easypact-ezc100n-tmd-32a-4-poles-3d/","alternativesUrl":"https://aoctrl.com/api/mcp/products/EZC100N4032/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/EZC100N4032","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/EZC100N4032 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}