{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"EZC100N4060","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"EZC100N4060","canonicalUrl":"https://aoctrl.com/schneider/EZC100N4060","factsUrl":"https://aoctrl.com/api/mcp/products/EZC100N4060","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact EZC100N series, EZC100N4060, 4-pole MCCB, 60 A thermal-magnetic trip unit, 25 kA breaking capacity at 240 V AC.","salesMarkdown":"It's built for distribution duty in fixed-mount backplate panels, with front-front connections and a 25 mm pole pitch. Breaking capacity is the headline spec that decides fit. At 240 V AC, the EZC100N4060 interrupts 25 kA Icu per IEC 60947-2. Drop to 440 V and it's 10 kA; at 415 V it's 15 kA; at 380-400 V it's 18 kA. On DC, it manages 5 kA at 125 V (1-pole) or 250 V (2-pole). The 'N' breaking capacity code means this is the standard-interrupting variant of the EZC100N frame — not the high-breaking 'H' or 'S' versions. For a 60 A distribution board fed from a transformer with a known fault current below these thresholds, it's a clean fit. If your SCCR study shows fault levels above 25 kA at 240 V, you need the higher-rated sibling. Mounts fixed to a backplate — no DIN rail adapter here. The 100 mm width and 60 mm depth fit a standard distribution panel footprint; the 130 mm height is compact for a 4-pole MCCB. Front-front connections simplify busbar and cable routing. IP20 finger-safe terminals, IK07 impact resistance. The toggle actuator gives positive contact indication — you can see the mechanism position without relying on the flag alone. Compliance documentation: the EZC100N4060 carries IEC 60947-1, IEC 60947-2, JIS C8201-2-2, and GB/T 14048.2 standards. Storage temperature range -35 to 85 °C, operating -25 to 70 °C. Mechanical durability is 13,000 cycles. No earth-leakage protection or neutral protection built in — this is a straight thermal-magnetic breaker for phase protection only (3 protected poles on a 4-pole frame).","metaTitle":"Schneider Electric EZC100N4060 EasyPact EZC100N 60A 4P MCCB","metaDescription":"Schneider Electric EZC100N4060 EasyPact EZC100N MCCB, 60A thermal-magnetic trip, 4 poles, 25 kA breaking at 240V AC. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Circuit Breaker Accessories"],"specifications":{"Depth":"60 mm","Width":"100 mm","title":"EZC100N4060","Height":"130 mm","Standards":"JIS C8201-2-2 EN/IEC 60947-1 EN/IEC 60947-2 GB/T 14048.2","description":"circuit breaker, EasyPact EZC100N, TMD, 60A, 4 poles 3d","Control type":"Toggle","Network type":"DC AC","Mounting mode":"Fixed","Trip unit name":"TM-D","Protection type":"Short-circuit protection Overload protection","lifecycle_stage":"current","Connection pitch":"25 mm","Local signalling":"Positive contact indication","Mounting support":"Backplate","Pollution degree":"3 conforming to IEC 60947","Range of product":"EasyPact","Trip unit rating":"60 A at 50 °C","Breaking capacity":"10 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 110...130 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 5 kA Icu at 125 V DC 1P conforming to IEC 60947-2 5 kA Icu at 250 V DC 2P conforming to IEC 60947-2 5 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 415 V AC 50/60 Hz conforming to IEC 60947-2 18 kA Icu at 380...400 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"Easypact EZC100N","Network frequency":"50/60 Hz","Poles description":"4P","Upside connection":"Front","Device application":"Distribution","[In] rated current":"60 A at 40 °C","Downside connection":"Front","Circuit breaker name":"Easypact EZC100N","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A","Mechanical durability":"13000 cycles","Breaking capacity code":"N","IK degree of protection":"IK07 conforming to EN 50102","IP degree of protection":"IP20 conforming to IEC 60529","Earth-leakage protection":"Without","Product or component type":"Circuit breaker","Suitability for isolation":"Yes conforming to IEC 60947-2","Neutral protection setting":"Without protection","Protected poles description":"3t","[Ui] rated insulation voltage":"690 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"550 V AC 50/60 Hz conforming to IEC 60947-2 250 V DC conforming to IEC 60947-2","Ambient air temperature for storage":"-35...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"5 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 2.5 kA at 125 V DC conforming to IEC 60947-2 2.5 kA at 250 V DC conforming to IEC 60947-2 2.5 kA at 550 V AC 50/60 Hz conforming to IEC 60947-2 12.5 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 12.5 kA at 110...130 V AC 50/60 Hz conforming to IEC 60947-2 9 kA at 380...400 V AC 50/60 Hz conforming to IEC 60947-2 7.5 kA at 415 V AC 50/60 Hz conforming to IEC 60947-2","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$64.95","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/2be41b2ca63457c57131bfd7ce7ed901.pdf","sourceUrl":"https://www.se.com/vn/en/product/EZC100N4060/circuit-breaker-easypact-ezc100n-tmd-60a-4-poles-3d/"},"ai":{"faq":[{"question":"How do I get current pricing and availability for EZC100N4060?","answer":"Submit an RFQ through this listing. Availability and current pricing are confirmed at quote time through independent distribution channels."},{"question":"What is EZC100N4060's breaking capacity at 240 V AC?","answer":"The EZC100N4060 interrupts 25 kA Icu at 220-240 V AC 50/60 Hz per IEC 60947-2. At 440 V it drops to 10 kA; at 380-400 V it's 18 kA."},{"question":"What compliance standards does EZC100N4060 meet?","answer":"The EZC100N4060 complies with IEC 60947-1, IEC 60947-2, JIS C8201-2-2, and GB/T 14048.2. It's suitable for isolation per IEC 60947-2."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/EZC100N4060","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/EZC100N4060 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}