{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"EZC250F3100","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"EZC250F3100","canonicalUrl":"https://aoctrl.com/schneider/EZC250F3100","factsUrl":"https://aoctrl.com/api/mcp/products/EZC250F3100","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact EZC250F, 3-pole circuit breaker, 100 A thermal-magnetic TM-D trip unit, 10 kA Icu at 440 V AC, fixed mount, toggle control.","salesMarkdown":"It carries a 10 kA Icu breaking capacity at 440 V AC (15 kA at 400 V, 25 kA at 240 V) under IEC 60947-2, and is suitable for isolation per that standard. The 690 V rated insulation voltage and Category A utilization class mean it's sized for panelboard feeder or branch protection where fault levels stay within its interrupting envelope. The 100 A trip rating at 40 °C (same at 50 °C) sets the continuous load limit — size the upstream conductor and downstream load for that, not the breaker frame's max. The TM-D thermal-magnetic trip gives short-circuit and overload protection in one unit; the thermal element handles sustained overcurrents, the magnetic element clears fast on high faults. IP20 finger-safe protection on the front; IK07 impact rating means it handles incidental tool contact during wiring.","metaTitle":"Schneider Electric EZC250F3100 EasyPact EZC250F Circuit Brea","metaDescription":"Schneider Electric EZC250F3100 EasyPact EZC250F 3-pole circuit breaker, 100 A thermal-magnetic TM-D trip unit, 10 kA breaking capacity at 440 V AC. IEC 60947-2. Active production.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Circuit Breaker Accessories"],"specifications":{"Depth":"60 mm","Width":"105 mm","title":"EZC250F3100","Height":"165 mm","Standards":"GB/T 14048.2 EN/IEC 60947-2 EN/IEC 60947-1","description":"circuit breaker Easypact EZC250F - TMD - 100 A - 3 poles 3d","Control type":"Toggle","Network type":"DC AC","Mounting mode":"Fixed","Trip unit name":"TM-D","Protection type":"Short-circuit protection Overload protection","lifecycle_stage":"current","Connection pitch":"35 mm","Local signalling":"Positive contact indication","Mounting support":"Backplate","Pollution degree":"3 conforming to IEC 60664-1 3 conforming to IEC 947-1","Range of product":"EasyPact","Trip unit rating":"100 A at 50 °C","Breaking capacity":"10 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2 18 kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 110...130 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 5 kA Icu at 125 V DC 1P conforming to IEC 60947-2 5 kA Icu at 250 V DC 2P conforming to IEC 60947-2 5 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"Easypact EZC250F","Network frequency":"50/60 Hz","Poles description":"3P","Upside connection":"Front","Device application":"Distribution","[In] rated current":"100 A at 40 °C","Downside connection":"Front","Circuit breaker name":"Easypact EZC250F","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A","Mechanical durability":"10000 cycles","Breaking capacity code":"F","IK degree of protection":"IK07 conforming to IEC 62262","IP degree of protection":"IP20 conforming to IEC 60529","Earth-leakage protection":"Without","Product or component type":"Circuit breaker","Suitability for isolation":"Yes conforming to IEC 60947-2","Neutral protection setting":"Without protection","Protected poles description":"3t","[Ui] rated insulation voltage":"690 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"550 V AC 50/60 Hz conforming to IEC 60947-2 250 V DC conforming to IEC 60947-2","Ambient air temperature for storage":"-35...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"9 kA at 380 V AC 50/60 Hz conforming to IEC 60947-2 12.5 kA at 110/130 V AC 50/60 Hz conforming to IEC 60947-2 12.5 kA at 220/230/240 V AC 50/60 Hz conforming to IEC 60947-2 2.5 kA at 125 V DC conforming to IEC 60947-2 2.5 kA at 250 V DC conforming to IEC 60947-2 2.5 kA at 550 V AC 50/60 Hz conforming to IEC 60947-2 9 kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 7.5 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/b3f71466c85bfdbd948280a249a63103.pdf","sourceUrl":"https://www.se.com/ae/en/product/EZC250F3100/circuit-breaker-easypact-ezc250f-tmd-100-a-3-poles-3d/"},"ai":{"faq":[{"question":"Where can I buy the EZC250F3100 and get current pricing?","answer":"The EZC250F3100 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time."},{"question":"What compliance documentation does Schneider provide for the EZC250F3100?","answer":"The breaker is certified to IEC 60947-2 and IEC 60947-1, with a declared pollution degree 3 per IEC 60664-1. It carries IP20 and IK07 ratings. For RoHS, REACH, and UL documentation, refer to the manufacturer's compliance portal or request it with your RFQ."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/EZC250F3100","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/EZC250F3100 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}