{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"EZC250F3125","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"EZC250F3125","canonicalUrl":"https://aoctrl.com/schneider/EZC250F3125","factsUrl":"https://aoctrl.com/api/mcp/products/EZC250F3125","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact EZC250F, 3-pole thermal-magnetic MCCB, 125 A, TM-D trip unit, breaking capacity 10-25 kA per IEC 60947-2, IP20, IK07, fixed mounting.","salesMarkdown":"Schneider Electric EZC250F3125 is a 3-pole EasyPact EZC250F thermal-magnetic moulded-case circuit breaker (MCCB). Breaking capacity hits 10 kA Icu at 440 V AC, 15 kA at 400-415 V, 18 kA at 380 V, and 25 kA at 220-240 V — all per IEC 60947-2. For DC circuits: 5 kA Icu at 250 V DC 2P. It's Category A (no intentional short-time delay), so it's a standard distribution breaker, not a selective main. That TM-D thermal-magnetic trip curve means the thermal element handles sustained overloads (cable protection), and the magnetic element snaps on short-circuit. At 380 V that rises to 18 kA, at 220-240 V to 25 kA. Pick your system voltage, that's your interrupting rating. The 690 V rated insulation voltage (Ui) and 550 V rated operational voltage (Ue) frame the system voltage ceiling. It's rated for isolation per IEC 60947-2, so you can use it as a visible-break disconnect. Fixed mounting on a backplate with front-connect terminals — both line and load connections are front-accessed. Connection pitch is 35 mm per pole. Dimensions: 105 mm wide, 165 mm tall, 60 mm deep. IP20 finger-safe enclosure, IK07 impact resistance. Toggle control with positive contact indication — you can see the contact state through the window. No earth-leakage module on this variant; it's a straight thermal-magnetic breaker.","metaTitle":"Schneider Electric EZC250F3125 EasyPact EZC250F 125A 3P MCCB","metaDescription":"Schneider Electric EZC250F3125 EasyPact EZC250F thermal-magnetic MCCB. 125 A, 3 poles, TM-D trip unit. Breaking capacity 10-25 kA. EN/IEC 60947-2. Current lifecycle. Quoted to orde","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Depth":"60 mm","Width":"105 mm","title":"EZC250F3125","Height":"165 mm","Standards":"EN/IEC 60947-2 GB/T 14048.2 EN/IEC 60947-1","description":"circuit breaker,EasyPact EZC250F,TMD, 125A,3 poles 3d","Control type":"Toggle","Network type":"DC AC","Mounting mode":"Fixed","Trip unit name":"TM-D","Protection type":"Overload protection Short-circuit protection","lifecycle_stage":"current","Connection pitch":"35 mm","Local signalling":"Positive contact indication","Mounting support":"Backplate","Pollution degree":"3 conforming to IEC 60664-1 3 conforming to IEC 947-1","Range of product":"EasyPact","Trip unit rating":"125 A at 50 °C","Breaking capacity":"10 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2 18 kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 110...130 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 5 kA Icu at 125 V DC 1P conforming to IEC 60947-2 5 kA Icu at 250 V DC 2P conforming to IEC 60947-2 5 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"Easypact EZC250F","Network frequency":"50/60 Hz","Poles description":"3P","Upside connection":"Front","Device application":"Distribution","[In] rated current":"125 A at 40 °C","Downside connection":"Front","Circuit breaker name":"Easypact EZC250F","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A","Mechanical durability":"10000 cycles","Breaking capacity code":"F","IK degree of protection":"IK07 conforming to IEC 62262","IP degree of protection":"IP20 conforming to IEC 60529","Earth-leakage protection":"Without","Product or component type":"Circuit breaker","Suitability for isolation":"Yes conforming to IEC 60947-2","Neutral protection setting":"Without protection","Protected poles description":"3t","[Ui] rated insulation voltage":"690 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"550 V AC 50/60 Hz conforming to IEC 60947-2 250 V DC conforming to IEC 60947-2","Ambient air temperature for storage":"-35...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"9 kA at 380 V AC 50/60 Hz conforming to IEC 60947-2 12.5 kA at 110/130 V AC 50/60 Hz conforming to IEC 60947-2 12.5 kA at 220/230/240 V AC 50/60 Hz conforming to IEC 60947-2 2.5 kA at 125 V DC conforming to IEC 60947-2 2.5 kA at 250 V DC conforming to IEC 60947-2 2.5 kA at 550 V AC 50/60 Hz conforming to IEC 60947-2 9 kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 7.5 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/c71fd383c2777b5a92aeabae7ce8b01f.pdf","sourceUrl":"https://www.se.com/vn/en/product/EZC250F3125/circuit-breakereasypact-ezc250f-tmd-125a-3-poles-3d/"},"ai":{"faq":[{"question":"What is the breaking capacity of the EZC250F3125 at 440 V?","answer":"10 kA Icu at 440 V AC 50/60 Hz per IEC 60947-2. At 400-415 V it's 15 kA; at 380 V it's 18 kA; at 220-240 V it's 25 kA. For DC: 5 kA at 250 V DC 2P."},{"question":"What standards does the EZC250F3125 comply with?","answer":"EN/IEC 60947-2 and GB/T 14048.2. Also conforms to IEC 60664-1 for pollution degree 3 and IEC 62262 for IK07 impact rating."},{"question":"Where can I buy the EZC250F3125 and how is it quoted?","answer":"Sourced through independent distribution channels. Quoted to order against an RFQ — availability and current pricing are confirmed at quote time. No stock or price figures on this page."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/EZC250F3125","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/EZC250F3125 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}