{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"EZC250F3150","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"EZC250F3150","canonicalUrl":"https://aoctrl.com/schneider/EZC250F3150","factsUrl":"https://aoctrl.com/api/mcp/products/EZC250F3150","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact EZC250F series, EZC250F3150, 3-pole molded case circuit breaker, 150 A rated current, thermal-magnetic TM-D trip unit, 10 kA Icu at 440 V AC, IP20.","salesMarkdown":"The Schneider Electric EZC250F3150 is a 3-pole molded case circuit breaker from the EasyPact EZC250F range, rated 150 A at 40 °C with a thermal-magnetic TM-D trip unit. It's built for distribution duty in fixed-mount backplate panels — the 105 mm wide, 165 mm high, 60 mm deep footprint fits standard enclosure cutouts. The 10 kA Icu at 440 V AC (18 kA at 380 V, 25 kA at 240 V) covers most commercial and light industrial service-entrance and feeder applications where fault levels stay under that ceiling. Category A utilization means it's not intended for motor starting — this is a distribution breaker, not a motor circuit protector. ## Breaking capacity across voltage — the real-world read The interrupting rating climbs as system voltage drops: 25 kA Icu at 240 V AC, 18 kA at 380 V, 15 kA at 400–415 V, and 10 kA at 440 V. The DC side is more modest: 5 kA Icu at 125 V DC (1-pole) or 250 V DC (2-pole). The 690 V insulation voltage (Ui) gives headroom for 480/277 V systems common in North American commercial panels. Fixed-mount on a backplate — no DIN-rail adapter on this frame. The toggle handle provides positive contact indication (ON/OFF visible on the front face). IP20 finger-safe protection on the front; IK07 impact resistance covers incidental tool drops.","metaTitle":"Schneider Electric EZC250F3150 EasyPact EZC250F, 150 A, 3P,","metaDescription":"Schneider Electric EZC250F3150 EasyPact EZC250F molded case circuit breaker, 150 A rated current, 3 poles, 10 kA breaking capacity at 440 V AC. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Circuit Breaker Accessories"],"specifications":{"Depth":"60 mm","Width":"105 mm","title":"EZC250F3150","Height":"165 mm","Standards":"GB/T 14048.2 EN/IEC 60947-2 EN/IEC 60947-1","description":"circuit breaker Easypact EZC250F - TMD - 150 A - 3 poles 3d","Control type":"Toggle","Network type":"AC DC","Mounting mode":"Fixed","Trip unit name":"TM-D","Protection type":"Overload protection Short-circuit protection","lifecycle_stage":"current","Connection pitch":"35 mm","Local signalling":"Positive contact indication","Mounting support":"Backplate","Pollution degree":"3 conforming to IEC 60664-1 3 conforming to IEC 947-1","Range of product":"EasyPact","Trip unit rating":"150 A at 50 °C","Breaking capacity":"10 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2 18 kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 110...130 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 5 kA Icu at 125 V DC 1P conforming to IEC 60947-2 5 kA Icu at 250 V DC 2P conforming to IEC 60947-2 5 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"Easypact EZC250F","Network frequency":"50/60 Hz","Poles description":"3P","Upside connection":"Front","Device application":"Distribution","[In] rated current":"150 A at 40 °C","Downside connection":"Front","Circuit breaker name":"Easypact EZC250F","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A","Mechanical durability":"10000 cycles","Breaking capacity code":"F","IK degree of protection":"IK07 conforming to IEC 62262","IP degree of protection":"IP20 conforming to IEC 60529","Earth-leakage protection":"Without","Product or component type":"Circuit breaker","Suitability for isolation":"Yes conforming to IEC 60947-2","Neutral protection setting":"Without protection","Protected poles description":"3t","[Ui] rated insulation voltage":"690 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"550 V AC 50/60 Hz conforming to IEC 60947-2 250 V DC conforming to IEC 60947-2","Ambient air temperature for storage":"-35...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"9 kA at 380 V AC 50/60 Hz conforming to IEC 60947-2 12.5 kA at 110/130 V AC 50/60 Hz conforming to IEC 60947-2 12.5 kA at 220/230/240 V AC 50/60 Hz conforming to IEC 60947-2 2.5 kA at 125 V DC conforming to IEC 60947-2 2.5 kA at 250 V DC conforming to IEC 60947-2 2.5 kA at 550 V AC 50/60 Hz conforming to IEC 60947-2 9 kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 7.5 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/01f1957fde9e79cae00bbe5f19b4400c.pdf","sourceUrl":"https://www.se.com/ae/en/product/EZC250F3150/circuit-breaker-easypact-ezc250f-tmd-150-a-3-poles-3d/"},"ai":{"faq":[{"question":"What is the breaking capacity of EZC250F3150 at 440 V AC?","answer":"10 kA Icu at 440 V AC 50/60 Hz per IEC 60947-2. At 400–415 V it's 15 kA, and at 380 V it's 18 kA. The DC rating is 5 kA at 125 V DC (1-pole) or 250 V DC (2-pole)."},{"question":"Where can I buy EZC250F3150 and how do I get a price?","answer":"This part is sourced to order against an RFQ through independent industrial distribution channels. Submit an RFQ for current availability and pricing — confirmed at quote time, not from a static listing."},{"question":"What compliance documentation does this breaker carry?","answer":"Certified to EN/IEC 60947-2 (circuit-breaker standard) and GB/T 14048.2 (China national standard). Suitable for isolation per IEC 60947-2. IP20 front protection, IK07 impact rating, and Pollution Degree 3 per IEC 60664-1."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/EZC250F3150","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/EZC250F3150 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}