{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"EZC250F3160","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"EZC250F3160","canonicalUrl":"https://aoctrl.com/schneider/EZC250F3160","factsUrl":"https://aoctrl.com/api/mcp/products/EZC250F3160","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact EZC250F series, EZC250F3160, 3-pole circuit breaker, 160 A thermal-magnetic TM-D trip unit, breaking capacity 25 kA at 240 V AC, fixed mounting, front connections.","salesMarkdown":"The Schneider Electric EZC250F3160 is a 3-pole EasyPact EZC250F circuit breaker with a thermal-magnetic TM-D trip unit rated 160 A at 40 °C (160 A at 50 °C). The fixed-mount design with front connections and a 35 mm connection pitch integrates into a backplate-mounted panel. Breaking capacity varies with voltage: 25 kA Icu at 240 V AC, 18 kA at 380 V, 15 kA at 400–415 V, and 10 kA at 440 V AC. At 550 V AC it drops to 5 kA; in DC, 5 kA at 125 V (1P) or 250 V (2P). This F-code breaker (breaking capacity code F) is sized for downstream distribution panels where fault currents stay within those limits — coordination with an upstream higher-kA device is expected for high-SCCR service entrances. Mounts fixed to a backplate with front-facing line and load connections — no DIN-rail adapter. IP20 finger-safe enclosure (IK07 impact rating) suits indoor panel installation. Designed to GB/T 14048.2, EN/IEC 60947-1, and EN/IEC 60947-2. The toggle control provides positive contact indication. No earth-leakage or neutral protection built in — this is a straight 3-pole (3t) thermal-magnetic breaker for three-phase distribution. Rated insulation voltage 690 V AC; rated operational voltage up to 550 V AC or 250 V DC.","metaTitle":"Schneider Electric EZC250F3160 EasyPact EZC250F 160A 3P Circ","metaDescription":"Schneider Electric EZC250F3160 EasyPact EZC250F 3-pole circuit breaker, 160 A thermal-magnetic TM-D trip unit, breaking capacity 25 kA at 240 V AC. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Circuit Breaker Accessories"],"specifications":{"Depth":"60 mm","Width":"105 mm","title":"EZC250F3160","Height":"165 mm","Standards":"GB/T 14048.2 EN/IEC 60947-1 EN/IEC 60947-2","description":"circuit breaker Easypact EZC250F - TMD - 160 A - 3 poles 3d","Control type":"Toggle","Network type":"AC DC","Mounting mode":"Fixed","Trip unit name":"TM-D","Protection type":"Overload protection Short-circuit protection","lifecycle_stage":"current","Connection pitch":"35 mm","Local signalling":"Positive contact indication","Mounting support":"Backplate","Pollution degree":"3 conforming to IEC 60664-1 3 conforming to IEC 947-1","Range of product":"EasyPact","Trip unit rating":"160 A at 50 °C","Breaking capacity":"10 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2 18 kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 110...130 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 5 kA Icu at 125 V DC 1P conforming to IEC 60947-2 5 kA Icu at 250 V DC 2P conforming to IEC 60947-2 5 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"Easypact EZC250F","Network frequency":"50/60 Hz","Poles description":"3P","Upside connection":"Front","Device application":"Distribution","[In] rated current":"160 A at 40 °C","Downside connection":"Front","Circuit breaker name":"Easypact EZC250F","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A","Mechanical durability":"10000 cycles","Breaking capacity code":"F","IK degree of protection":"IK07 conforming to IEC 62262","IP degree of protection":"IP20 conforming to IEC 60529","Earth-leakage protection":"Without","Product or component type":"Circuit breaker","Suitability for isolation":"Yes conforming to IEC 60947-2","Neutral protection setting":"Without protection","Protected poles description":"3t","[Ui] rated insulation voltage":"690 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"550 V AC 50/60 Hz conforming to IEC 60947-2 250 V DC conforming to IEC 60947-2","Ambient air temperature for storage":"-35...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"9 kA at 380 V AC 50/60 Hz conforming to IEC 60947-2 12.5 kA at 110/130 V AC 50/60 Hz conforming to IEC 60947-2 12.5 kA at 220/230/240 V AC 50/60 Hz conforming to IEC 60947-2 2.5 kA at 125 V DC conforming to IEC 60947-2 2.5 kA at 250 V DC conforming to IEC 60947-2 2.5 kA at 550 V AC 50/60 Hz conforming to IEC 60947-2 9 kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 7.5 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$95.43","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/8ad9b71b7459c47a5be69e27d9be02b3.pdf","sourceUrl":"https://www.se.com/ph/en/product/EZC250F3160/circuit-breaker-easypact-ezc250f-tmd-160-a-3-poles-3d/"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/EZC250F3160","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/EZC250F3160 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}