{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"EZC250F3175","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"EZC250F3175","canonicalUrl":"https://aoctrl.com/schneider/EZC250F3175","factsUrl":"https://aoctrl.com/api/mcp/products/EZC250F3175","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact EZC250F series, EZC250F3175, 3-pole circuit breaker, 175 A thermal-magnetic TM-D trip unit, 10 kA Icu at 440 V AC, fixed mount, front connections.","salesMarkdown":"The Schneider Electric EZC250F3175 is a 3-pole EasyPact EZC250F moulded-case circuit breaker with a thermal-magnetic TM-D trip unit rated 175 A at 40 °C. The TM-D trip gives you fixed thermal overload protection (the bimetal element) and fixed magnetic short-circuit pickup; no adjustment dials, so set your coordination study around those fixed thresholds. Breaking capacity is the real selector here. At 440 V AC it interrupts 10 kA Icu (IEC 60947-2). At 400–415 V AC that climbs to 15 kA Icu, and at 380 V AC to 18 kA Icu. For 220–240 V AC circuits it handles 25 kA Icu. On DC: 5 kA Icu at 125 V DC (1-pole) or 250 V DC (2-pole). The 'F' breaking capacity code tells you this is the standard-interrupting version of the EZC250F frame — not the high-breaking 'H' variant. Dimensions: 105 mm wide, 165 mm high, 60 mm deep — fits a standard MCCB footprint in most distribution boards. IP20 finger-safe terminals; IK07 impact rating means it survives a 2 J hammer blow during panel work. Toggle control with positive contact indication — you can see and feel the contact position. Compliance documentation is straightforward: the breaker carries IEC 60947-2, EN 60947-2, GB/T 14048.2, and JIS C8201-2-2 certifications. No earth-leakage protection built in; if you need that, you add an external Vigi module or use the EZC250F with earth-leakage option. Category A utilization (no intentional short-time delay) means this breaker trips instantaneously on short-circuit — it's a feeder or branch-circuit protector, not a main breaker that needs selectivity with downstream devices via ST delay. Use it downstream of a main breaker or fuse that has a higher Icu rating and can coordinate. Mechanical durability of 10,000 cycles is typical for a distribution MCCB; fine for panel switching a few times a year, not for frequent motor-starting duty.","metaTitle":"Schneider Electric EZC250F3175 EasyPact EZC250F Circuit Brea","metaDescription":"Schneider Electric EZC250F3175 EasyPact EZC250F circuit breaker, 175 A rated current, 3 poles, thermal-magnetic TM-D trip unit, 10 kA Icu at 440 V AC. Current lifecycle, available","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Circuit Breaker Accessories"],"specifications":{"Depth":"60 mm","Width":"105 mm","title":"EZC250F3175","Height":"165 mm","Standards":"EN/IEC 60947-1 GB/T 14048.2 EN/IEC 60947-2 JIS C8201-2-2","description":"circuit breaker Easypact EZC250F - TMD - 175 A - 3 poles 3d","Control type":"Toggle","Network type":"DC AC","Mounting mode":"Fixed","Trip unit name":"TM-D","Protection type":"Short-circuit protection Overload protection","lifecycle_stage":"current","Connection pitch":"35 mm","Local signalling":"Positive contact indication","Mounting support":"Backplate","Pollution degree":"3 conforming to IEC 60664-1 3 conforming to IEC 947-1","Range of product":"EasyPact","Trip unit rating":"175 A at 50 °C","Breaking capacity":"10 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2 18 kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 110...130 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 5 kA Icu at 125 V DC 1P conforming to IEC 60947-2 5 kA Icu at 250 V DC 2P conforming to IEC 60947-2 5 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"Easypact EZC250F","Network frequency":"50/60 Hz","Poles description":"3P","Upside connection":"Front","Device application":"Distribution","[In] rated current":"175 A at 40 °C","Downside connection":"Front","Circuit breaker name":"Easypact EZC250F","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A","Mechanical durability":"10000 cycles","Breaking capacity code":"F","IK degree of protection":"IK07 conforming to IEC 62262","IP degree of protection":"IP20 conforming to IEC 60529","Earth-leakage protection":"Without","Product or component type":"Circuit breaker","Suitability for isolation":"Yes conforming to IEC 60947-2","Neutral protection setting":"Without protection","Protected poles description":"3t","[Ui] rated insulation voltage":"690 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"550 V AC 50/60 Hz conforming to IEC 60947-2 250 V DC conforming to IEC 60947-2","Ambient air temperature for storage":"-35...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"9 kA at 380 V AC 50/60 Hz conforming to IEC 60947-2 12.5 kA at 110/130 V AC 50/60 Hz conforming to IEC 60947-2 12.5 kA at 220/230/240 V AC 50/60 Hz conforming to IEC 60947-2 2.5 kA at 125 V DC conforming to IEC 60947-2 2.5 kA at 250 V DC conforming to IEC 60947-2 2.5 kA at 550 V AC 50/60 Hz conforming to IEC 60947-2 9 kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 7.5 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/1cc4e03bbb6eddc86e56e539417e2ce7.pdf","sourceUrl":"https://www.se.com/ae/en/product/EZC250F3175/circuit-breaker-easypact-ezc250f-tmd-175-a-3-poles-3d/"},"ai":{"faq":[{"question":"What is the breaking capacity of EZC250F3175 at 440 V AC?","answer":"At 440 V AC, the EZC250F3175 has a breaking capacity (Icu) of 10 kA per IEC 60947-2. At 400–415 V AC it is 15 kA, and at 380 V AC it is 18 kA."},{"question":"What certifications does EZC250F3175 carry?","answer":"The breaker is certified to IEC 60947-2, EN 60947-2, GB/T 14048.2, and JIS C8201-2-2. It is suitable for isolation per IEC 60947-2 and carries IP20 finger protection with IK07 impact rating."},{"question":"How do I get pricing and availability for EZC250F3175?","answer":"The EZC250F3175 is sourced and quoted to order against an RFQ through independent distribution. Current pricing and availability are confirmed at quote time — submit an RFQ for a firm quote."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/EZC250F3175","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/EZC250F3175 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}