{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"EZC250F3175","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"EZC250F3175","canonicalUrl":"https://aoctrl.com/schneider/EZC250F3175","factsUrl":"https://aoctrl.com/api/mcp/products/EZC250F3175","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact EZC250F series, EZC250F3175, 3-pole circuit breaker, 175 A thermal-magnetic TM-D trip unit, 10 kA Icu at 440 V AC, fixed mount, front connections.","salesMarkdown":"The Schneider Electric EZC250F3175 is a 3-pole EasyPact EZC250F moulded-case circuit breaker with a thermal-magnetic TM-D trip unit rated 175 A at 40 °C. The TM-D trip gives you fixed thermal overload protection (the bimetal element) and fixed magnetic short-circuit pickup; no adjustment dials, so set your coordination study around those fixed thresholds. Breaking capacity is the real selector here. At 440 V AC it interrupts 10 kA Icu (IEC 60947-2). At 400–415 V AC that climbs to 15 kA Icu, and at 380 V AC to 18 kA Icu. For 220–240 V AC circuits it handles 25 kA Icu. On DC: 5 kA Icu at 125 V DC (1-pole) or 250 V DC (2-pole). The 'F' breaking capacity code tells you this is the standard-interrupting version of the EZC250F frame — not the high-breaking 'H' variant. Dimensions: 105 mm wide, 165 mm high, 60 mm deep — fits a standard MCCB footprint in most distribution boards. IP20 finger-safe terminals; IK07 impact rating means it survives a 2 J hammer blow during panel work. Toggle control with positive contact indication — you can see and feel the contact position. Compliance documentation is straightforward: the breaker carries IEC 60947-2, EN 60947-2, GB/T 14048.2, and JIS C8201-2-2 certifications. No earth-leakage protection built in; if you need that, you add an external Vigi module or use the EZC250F with earth-leakage option. Category A utilization (no intentional short-time delay) means this breaker trips instantaneously on short-circuit — it's a feeder or branch-circuit protector, not a main breaker that needs selectivity with downstream devices via ST delay. Use it downstream of a main breaker or fuse that has a higher Icu rating and can coordinate. Mechanical durability of 10,000 cycles is typical for a distribution MCCB; fine for panel switching a few times a year, not for frequent motor-starting duty.","metaTitle":"Schneider Electric EZC250F3175 EasyPact EZC250F Circuit Brea","metaDescription":"Schneider Electric EZC250F3175 EasyPact EZC250F circuit breaker, 175 A rated current, 3 poles, thermal-magnetic TM-D trip unit, 10 kA Icu at 440 V AC. Current lifecycle, available","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":[],"specifications":{"Depth":"60 mm","Width":"105 mm","Height":"165 mm","Voltage":"550 V AC 50/60 Hz conforming to IEC 60947-2 250 V DC conforming to IEC 60947-2","IP Rating":"IP20","Application":"Distribution","Control Type":"Toggle","Network Type":"DC AC","Product Status":"Active","Terminal Pitch":"35 mm","Trip Unit Type":"Thermal-magnetic","Pollution Degree":"3 conforming to IEC 60664-1 3 conforming to IEC 947-1","Temp Storage Max":"85 °C","Temp Storage Min":"-35 °C","Breaking Capacity":"10 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2 18 kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 110...130 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 5 kA Icu at 125 V DC 1P conforming to IEC 60947-2 5 kA Icu at 250 V DC 2P conforming to IEC 60947-2 5 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2","Insulation Voltage Ui":"690 V AC 50/60 Hz conforming to IEC 60947-2","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-35...85 °C","Connection Surface Top":"Front","Mechanical Life Cycles":"10000 cycles","Connection Surface Bottom":"Front","Main Product Or Component Type":"Circuit breaker","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/1cc4e03bbb6eddc86e56e539417e2ce7.pdf","sourceUrl":"https://www.se.com/ae/en/product/EZC250F3175/circuit-breaker-easypact-ezc250f-tmd-175-a-3-poles-3d/","alternativesUrl":"https://aoctrl.com/api/mcp/products/EZC250F3175/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/EZC250F3175","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/EZC250F3175 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}