{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"EZC250F3250","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"EZC250F3250","canonicalUrl":"https://aoctrl.com/schneider/EZC250F3250","factsUrl":"https://aoctrl.com/api/mcp/products/EZC250F3250","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact EZC250F, EZC250F3250, molded case circuit breaker, 250 A, 3-pole, thermal-magnetic TM-D trip unit, 10 kA at 440 V AC, fixed mount, front connection.","salesMarkdown":"The EZC250F3250 is a 3-pole molded case circuit breaker from Schneider Electric's EasyPact range, rated 250 A at 40 °C and 250 A at 50 °C. The 10 kA Icu at 440 V AC is the interrupting capacity at a common industrial voltage; at 400–415 V AC it rises to 15 kA, and at 380 V AC to 18 kA. For a distribution panel feeding motor control centers or lighting, that's enough fault-clearing for most 400 V class installations without cascading upstream. Rated operational voltage goes up to 550 V AC and 250 V DC. Fixed mounting on a backplate, front connections both top and bottom. Connection pitch of 35 mm matches common busbar and lug spacing. IP20 finger-safe protection on the front, IK07 impact resistance per IEC 62262, so it handles incidental tool drops in the enclosure. ## Protection and duty The TM-D trip unit provides overload protection (thermal bimetal) and short-circuit protection (magnetic solenoid). No earth-leakage or neutral protection built in — it's a straight 3-pole breaker with all three poles protected. Category A utilization means it's not intended for frequent switching under load; it's a distribution breaker, not a motor-starter disconnect. Mechanical durability of 10,000 cycles is typical for this class — fine for infrequent switching, not for daily load-break duty.","metaTitle":"Schneider Electric EZC250F3250 EasyPact EZC250F, 250A, 3P, T","metaDescription":"Schneider Electric EZC250F3250 EasyPact EZC250F circuit breaker, 250A, 3-pole, TM-D trip unit, 10kA at 440V AC. Current lifecycle. Sourced to order. RFQ for pricing.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Circuit Breaker Accessories"],"specifications":{"Depth":"60 mm","Width":"105 mm","title":"EZC250F3250","Height":"165 mm","Standards":"EN/IEC 60947-2 GB/T 14048.2 EN/IEC 60947-1","description":"circuit breaker,EasyPact EZC250F,TMD, 250A,3 poles 3d","Control type":"Toggle","Network type":"AC DC","Mounting mode":"Fixed","Trip unit name":"TM-D","Protection type":"Overload protection Short-circuit protection","lifecycle_stage":"current","Connection pitch":"35 mm","Local signalling":"Positive contact indication","Mounting support":"Backplate","Pollution degree":"3 conforming to IEC 60664-1 3 conforming to IEC 947-1","Range of product":"EasyPact","Trip unit rating":"250 A at 50 °C","Breaking capacity":"10 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2 18 kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 110...130 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 5 kA Icu at 125 V DC 1P conforming to IEC 60947-2 5 kA Icu at 250 V DC 2P conforming to IEC 60947-2 5 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"Easypact EZC250F","Network frequency":"50/60 Hz","Poles description":"3P","Upside connection":"Front","Device application":"Distribution","[In] rated current":"250 A at 40 °C","Downside connection":"Front","Circuit breaker name":"Easypact EZC250F","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A","Mechanical durability":"10000 cycles","Breaking capacity code":"F","IK degree of protection":"IK07 conforming to IEC 62262","IP degree of protection":"IP20 conforming to IEC 60529","Earth-leakage protection":"Without","Product or component type":"Circuit breaker","Suitability for isolation":"Yes conforming to IEC 60947-2","Neutral protection setting":"Without protection","Protected poles description":"3t","[Ui] rated insulation voltage":"690 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"550 V AC 50/60 Hz conforming to IEC 60947-2 250 V DC conforming to IEC 60947-2","Ambient air temperature for storage":"-35...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"9 kA at 380 V AC 50/60 Hz conforming to IEC 60947-2 12.5 kA at 110/130 V AC 50/60 Hz conforming to IEC 60947-2 12.5 kA at 220/230/240 V AC 50/60 Hz conforming to IEC 60947-2 2.5 kA at 125 V DC conforming to IEC 60947-2 2.5 kA at 250 V DC conforming to IEC 60947-2 2.5 kA at 550 V AC 50/60 Hz conforming to IEC 60947-2 9 kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 7.5 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$123.13","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/17cb54e4d6142d44d86f7a53301f601d.pdf","sourceUrl":"https://www.se.com/vn/en/product/EZC250F3250/circuit-breakereasypact-ezc250f-tmd-250a-3-poles-3d/"},"ai":{"faq":[{"question":"What are the key ratings for EZC250F3250?","answer":"Rated 250 A continuous at 40 °C, 3-pole, thermal-magnetic TM-D trip unit. Breaking capacity is 10 kA Icu at 440 V AC, 15 kA at 400–415 V AC, and 25 kA at 220–240 V AC. Operational voltage up to 550 V AC and 250 V DC."},{"question":"What standards does EZC250F3250 comply with?","answer":"It complies with EN/IEC 60947-2, GB/T 14048.2, and EN/IEC 60947-1. It is suitable for isolation per IEC 60947-2 and rated for pollution degree 3."},{"question":"Where can I buy EZC250F3250?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/EZC250F3250","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/EZC250F3250 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}