{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"EZC250H2100","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"EZC250H2100","canonicalUrl":"https://aoctrl.com/schneider/EZC250H2100","factsUrl":"https://aoctrl.com/api/mcp/products/EZC250H2100","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact EZC250H, 2-pole MCCB, 100 A, TM-D thermal-magnetic trip, 10-85 kA Icu breaking capacity range, 550 V AC / 250 V DC.","salesMarkdown":"The Schneider Electric EZC250H2100 is a 2-pole EasyPact EZC250H moulded-case circuit breaker rated 100 A at 40 °C, with a TM-D thermal-magnetic trip unit. The 100 A rating at 50 °C tells you the breaker holds full load at elevated panel temps — useful if the enclosure runs hot. Breaking capacity spans 10 kA Icu at 550 V AC up to 85 kA Icu at 240 V AC; the 36 kA Icu at 400-415 V AC is the figure most European distribution boards care about. For DC circuits, it delivers 30 kA Icu at 125 V DC (1P) or 250 V DC (2P). The 690 V AC rated insulation voltage and 550 V AC operational voltage cover standard 400/480 V systems with headroom. The breaker is Category A — no intentional short-time delay, so it trips instantaneously on fault. That makes it a good fit for feeder or branch protection where you want fast clearing, not selective coordination downstream. The toggle control gives positive contact indication: you see the position, no guessing. IP20 finger-safe terminals and IK07 impact resistance suit it for enclosed panel mounting on a backplate. Certified to GB/T 14048.2, EN/IEC 60947-1, and EN/IEC 60947-2 — the core MCCB standards for China and Europe. No earth-leakage protection built in; if you need that, you'd add a separate RCD or use an EasyPact CVS with Vigi module.","metaTitle":"Schneider Electric EZC250H2100 EasyPact EZC250H 100A 2P MCCB","metaDescription":"Schneider Electric EZC250H2100 EasyPact EZC250H 2-pole MCCB, 100 A rated, TM-D trip unit, 10-85 kA Icu breaking capacity. Active production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Circuit Breaker Accessories"],"specifications":{"Depth":"60 mm","Width":"105 mm","title":"EZC250H2100","Height":"165 mm","Standards":"GB/T 14048.2 EN/IEC 60947-1 EN/IEC 60947-2","description":"circuit breaker,EasyPact EZC250H,TMD, 100A,2 poles 2d","Control type":"Toggle","Network type":"AC DC","Mounting mode":"Fixed","Trip unit name":"TM-D","Protection type":"Overload protection Short-circuit protection","lifecycle_stage":"current","Connection pitch":"35 mm","Local signalling":"Positive contact indication","Mounting support":"Backplate","Pollution degree":"3 conforming to IEC 60664-1 3 conforming to IEC 947-1","Range of product":"EasyPact","Trip unit rating":"100 A at 50 °C","Breaking capacity":"10 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 125 V DC 1P conforming to IEC 60947-2 30 kA Icu at 250 V DC 2P conforming to IEC 60947-2 36 kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 110...130 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"Easypact EZC250H","Network frequency":"50/60 Hz","Poles description":"2P","Upside connection":"Front","Device application":"Distribution","[In] rated current":"100 A at 40 °C","Downside connection":"Front","Circuit breaker name":"Easypact EZC250H","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A","Mechanical durability":"10000 cycles","Breaking capacity code":"H","IK degree of protection":"IK07 conforming to IEC 62262","IP degree of protection":"IP20 conforming to IEC 60529","Earth-leakage protection":"Without","Product or component type":"Circuit breaker","Suitability for isolation":"Yes conforming to IEC 60947-2","Neutral protection setting":"Without protection","Protected poles description":"2t","[Ui] rated insulation voltage":"690 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"550 V AC 50/60 Hz conforming to IEC 60947-2 250 V DC conforming to IEC 60947-2","Ambient air temperature for storage":"-35...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"5 kA at 550 V AC 50/60 Hz conforming to IEC 60947-2 15 kA at 125 V DC conforming to IEC 60947-2 15 kA at 250 V DC conforming to IEC 60947-2 18 kA at 380 V AC 50/60 Hz conforming to IEC 60947-2 18 kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 12.5 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 42.5 kA at 110/130 V AC 50/60 Hz conforming to IEC 60947-2 42.5 kA at 220/230/240 V AC 50/60 Hz conforming to IEC 60947-2","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/045371ab086096717952b4a569e37d29.pdf","sourceUrl":"https://www.se.com/vn/en/product/EZC250H2100/circuit-breakereasypact-ezc250h-tmd-100a-2-poles-2d/"},"ai":{"faq":[{"question":"Where can I buy EZC250H2100 and how do I get a price?","answer":"The EZC250H2100 is sourced to order against an RFQ through independent distribution. Submit a request for quote (RFQ) to confirm current availability and pricing at the time of your order."},{"question":"What is the breaking capacity of EZC250H2100 at 400 V AC?","answer":"At 400-415 V AC 50/60 Hz, the EZC250H2100 delivers 36 kA Icu per IEC 60947-2. That's the figure to use for selectivity studies on a 400 V distribution board."},{"question":"What compliance documentation does EZC250H2100 carry?","answer":"The breaker is certified to GB/T 14048.2, EN/IEC 60947-1, and EN/IEC 60947-2. It is suitable for isolation per IEC 60947-2. Pollution degree 3 per IEC 60664-1 and IEC 947-1 covers industrial environments."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/EZC250H2100","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/EZC250H2100 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}