{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"EZC250H2225","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"EZC250H2225","canonicalUrl":"https://aoctrl.com/schneider/EZC250H2225","factsUrl":"https://aoctrl.com/api/mcp/products/EZC250H2225","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact EZC250H series, EZC250H2225, 2-pole circuit breaker, 225 A rated current, thermal-magnetic TM-D trip unit, 10 kA Icu at 550 V AC, IP20, backplate mount.","salesMarkdown":"## Integrator's note on the EZC250H2225 The Schneider Electric EZC250H2225 is a 2-pole EasyPact EZC250H circuit breaker rated 225 A at 40 °C, with a thermal-magnetic TM-D trip unit handling short-circuit and overload protection. Breaking capacity hits 10 kA Icu at 550 V AC — enough for most distribution panels on 400 V systems where fault levels stay under that ceiling. The fixed backplate mount and front connections simplify panel layout; IP20 enclosure keeps fingers out but expects a sealed cabinet in wet areas. At 400…415 V AC the breaker delivers 36 kA Icu, which coordinates well with downstream 25 kA-rated MCCBs in a typical 400 V distribution board. The 10 kA rating at 550 V AC covers the high-voltage end for 480 V line-to-line systems. Fixed backplate mount, 105 mm wide, 165 mm tall, 60 mm deep. IK07 impact rating handles light tool drops during commissioning.","metaTitle":"Schneider Electric EZC250H2225 EasyPact EZC250H, 225 A, 2P,","metaDescription":"Schneider Electric EZC250H2225 EasyPact EZC250H circuit breaker, 225 A, 2-pole, thermal-magnetic TM-D trip unit, 10 kA Icu at 550 V AC. Active production, sourced to order. Request","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"60 mm","Width":"105 mm","Height":"165 mm","Voltage":"550 V AC 50/60 Hz conforming to IEC 60947-2 250 V DC conforming to IEC 60947-2","IP Rating":"IP20","Application":"Distribution","Control Type":"Toggle","Product Status":"Active","Terminal Pitch":"35 mm","Trip Unit Type":"Thermal-magnetic","Pollution Degree":"3 conforming to IEC 60664-1 3 conforming to IEC 947-1","Temp Storage Max":"85 °C","Temp Storage Min":"-35 °C","Breaking Capacity":"10 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 125 V DC 1P conforming to IEC 60947-2 30 kA Icu at 250 V DC 2P conforming to IEC 60947-2 36 kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 110...130 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2","Insulation Voltage Ui":"690 V AC 50/60 Hz conforming to IEC 60947-2","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-35...85 °C","Connection Surface Top":"Front","Mechanical Life Cycles":"10000 cycles","Connection Surface Bottom":"Front","Main Product Or Component Type":"Circuit breaker","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/7a00d2380238894953698b5607a17be3.pdf","sourceUrl":"https://www.se.com/ph/en/product/EZC250H2225/circuit-breaker-easypact-ezc250h-tmd-225-a-2-poles-2d/","alternativesUrl":"https://aoctrl.com/api/mcp/products/EZC250H2225/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/EZC250H2225","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/EZC250H2225 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}