{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"EZC250H3200","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"EZC250H3200","canonicalUrl":"https://aoctrl.com/schneider/EZC250H3200","factsUrl":"https://aoctrl.com/api/mcp/products/EZC250H3200","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact EZC250H, 3-pole MCCB, 200 A rated at 40 °C, TM-D thermal-magnetic trip unit, breaking capacity 10-85 kA depending on voltage, IEC 60947-2.","salesMarkdown":"The EZC250H3200 is a 3-pole moulded-case circuit breaker from the Schneider EasyPact series, rated 200 A at 40 °C ambient (derated to 200 A at 50 °C per the TM-D trip unit curve). Breaking capacity varies with system voltage: 85 kA at 240 V AC, 36 kA at 415 V AC, and 10 kA at 550 V AC. That 10 kA at 550 V is the limiting case for a 480 V line-to-line system; the 36 kA at 415 V covers most European 400 V panels. The part is utilisation category A, meaning it is not intended for frequent switching under load — it is a distribution breaker, not a motor-starter disconnect. Mounting is fixed (backplate), not DIN-rail, so plan for a dedicated panel footprint. The front-connection terminals (upside and downside) accept cable lugs at a 35 mm pitch. IP20 finger-safe on the front face; IK07 impact rating means it withstands a 2 J hammer blow, adequate for a locked panel. The toggle handle gives positive contact indication — you can visually confirm the contact position without removing the cover. No earth-leakage or neutral protection built in; this is a straight 3-pole breaker with three protected poles and no neutral pole. The IEC 60947-2 certification covers the breaking capacity claims, isolation suitability, and pollution degree 3 rating.","metaTitle":"Schneider Electric EZC250H3200 EasyPact EZC250H 200A 3P MCCB","metaDescription":"Schneider Electric EZC250H3200 EasyPact EZC250H 200A 3-pole MCCB. Breaking capacity 10-85 kA. TM-D thermal-magnetic trip. Current lifecycle, sourced to order. Quoted on request.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Circuit Breaker Accessories"],"specifications":{"Depth":"60 mm","Width":"105 mm","title":"EZC250H3200","Height":"165 mm","Standards":"EN/IEC 60947-1 GB/T 14048.2 EN/IEC 60947-2","description":"circuit breaker Easypact EZC250H - TMD - 200 A - 3 poles 3d","Control type":"Toggle","Network type":"AC DC","Mounting mode":"Fixed","Trip unit name":"TM-D","Protection type":"Overload protection Short-circuit protection","lifecycle_stage":"current","Connection pitch":"35 mm","Local signalling":"Positive contact indication","Mounting support":"Backplate","Pollution degree":"3 conforming to IEC 60664-1 3 conforming to IEC 947-1","Range of product":"EasyPact","Trip unit rating":"200 A at 50 °C","Breaking capacity":"10 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 125 V DC 1P conforming to IEC 60947-2 30 kA Icu at 250 V DC 2P conforming to IEC 60947-2 36 kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 110...130 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"Easypact EZC250H","Network frequency":"50/60 Hz","Poles description":"3P","Upside connection":"Front","Device application":"Distribution","[In] rated current":"200 A at 40 °C","Downside connection":"Front","Circuit breaker name":"Easypact EZC250H","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A","Mechanical durability":"10000 cycles","Breaking capacity code":"H","IK degree of protection":"IK07 conforming to IEC 62262","IP degree of protection":"IP20 conforming to IEC 60529","Earth-leakage protection":"Without","Product or component type":"Circuit breaker","Suitability for isolation":"Yes conforming to IEC 60947-2","Neutral protection setting":"Without protection","Protected poles description":"3t","[Ui] rated insulation voltage":"690 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"550 V AC 50/60 Hz conforming to IEC 60947-2 250 V DC conforming to IEC 60947-2","Ambient air temperature for storage":"-35...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"5 kA at 550 V AC 50/60 Hz conforming to IEC 60947-2 15 kA at 125 V DC conforming to IEC 60947-2 15 kA at 250 V DC conforming to IEC 60947-2 18 kA at 380 V AC 50/60 Hz conforming to IEC 60947-2 18 kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 12.5 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 42.5 kA at 110/130 V AC 50/60 Hz conforming to IEC 60947-2 42.5 kA at 220/230/240 V AC 50/60 Hz conforming to IEC 60947-2","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$157.86","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/09036a2c39e8e0afd3109120debd6329.pdf","sourceUrl":"https://www.se.com/ae/en/product/EZC250H3200/circuit-breaker-easypact-ezc250h-tmd-200-a-3-poles-3d/"},"ai":{"faq":[{"question":"Where can I buy EZC250H3200 and how is it quoted?","answer":"The part is sourced to order through independent distribution. Submit an RFQ for current pricing and availability — no stock count or lead-time figure is published here, but the supply channel is open and quoted on request."},{"question":"What is the breaking capacity of EZC250H3200 at 400 V?","answer":"At 400–415 V AC 50/60 Hz, the Icu is 36 kA per IEC 60947-2. At 440 V it drops to 25 kA, and at 550 V to 10 kA. The 36 kA at 400 V covers most European distribution panels."},{"question":"Does EZC250H3200 include earth-leakage protection?","answer":"No. The TM-D trip unit provides only thermal-magnetic overload and short-circuit protection. Earth-leakage protection is not built in — specify a separate RCD or a breaker with a Vigi add-on if required."},{"question":"What compliance documentation is available for EZC250H3200?","answer":"The breaker carries IEC 60947-2 certification, which covers the breaking capacity, isolation suitability, and pollution degree 3 rating. It also meets GB/T 14048.2 for China. RoHS and REACH compliance are standard for the EasyPact series, though not explicitly listed in the spec record."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/EZC250H3200","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/EZC250H3200 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}