{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"EZC250H3225","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"EZC250H3225","canonicalUrl":"https://aoctrl.com/schneider/EZC250H3225","factsUrl":"https://aoctrl.com/api/mcp/products/EZC250H3225","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact EZC250H series, EZC250H3225, 3P 225A thermal-magnetic circuit breaker, 36 kA Icu at 400 V AC, IEC 60947-2.","salesMarkdown":"The Schneider Electric EZC250H3225 is a 3-pole thermal-magnetic circuit breaker from the EasyPact EZC250H series, rated 225 A at 40 °C and carrying a TM-D trip unit for overload and short-circuit protection. At 550 V AC it drops to 10 kA Icu, so if your line side is a 480 V or 550 V transformer, the available fault current at that point must stay under 10 kA or you need a current-limiting upstream device. Fixed backplate mounting with front-facing connections. Dimensions are 165 mm high × 105 mm wide × 60 mm deep. Positive contact indication gives a visible gap confirmation for lockout/tagout. The 10,000-cycle mechanical durability is typical for a distribution breaker; if your application cycles the breaker weekly as a disconnect, that is roughly a 200-year life — not a constraint. The manufacturer provides RoHS, REACH, and CE declarations; UL/CSA listing is not stated in the evidence, so verify with your local Schneider representative if North American approvals are required.","metaTitle":"Schneider Electric EZC250H3225 EasyPact EZC250H 225A 3P Circ","metaDescription":"Schneider Electric EZC250H3225 EasyPact EZC250H 3P 225A thermal-magnetic circuit breaker. 36kA Icu at 400V AC. IEC 60947-2. Current lifecycle. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Circuit Breaker Accessories"],"specifications":{"Depth":"60 mm","Width":"105 mm","title":"EZC250H3225","Height":"165 mm","Standards":"EN/IEC 60947-2 EN/IEC 60947-1 GB/T 14048.2","description":"circuit breaker Easypact EZC250H - TMD - 225 A - 3 poles 3d","Control type":"Toggle","Network type":"AC DC","Mounting mode":"Fixed","Trip unit name":"TM-D","Protection type":"Overload protection Short-circuit protection","lifecycle_stage":"current","Connection pitch":"35 mm","Local signalling":"Positive contact indication","Mounting support":"Backplate","Pollution degree":"3 conforming to IEC 60664-1 3 conforming to IEC 947-1","Range of product":"EasyPact","Trip unit rating":"225 A at 50 °C","Breaking capacity":"10 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 125 V DC 1P conforming to IEC 60947-2 30 kA Icu at 250 V DC 2P conforming to IEC 60947-2 36 kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 110...130 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"Easypact EZC250H","Network frequency":"50/60 Hz","Poles description":"3P","Upside connection":"Front","Device application":"Distribution","[In] rated current":"225 A at 40 °C","Downside connection":"Front","Circuit breaker name":"Easypact EZC250H","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A","Mechanical durability":"10000 cycles","Breaking capacity code":"H","IK degree of protection":"IK07 conforming to IEC 62262","IP degree of protection":"IP20 conforming to IEC 60529","Earth-leakage protection":"Without","Product or component type":"Circuit breaker","Suitability for isolation":"Yes conforming to IEC 60947-2","Neutral protection setting":"Without protection","Protected poles description":"3t","[Ui] rated insulation voltage":"690 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"550 V AC 50/60 Hz conforming to IEC 60947-2 250 V DC conforming to IEC 60947-2","Ambient air temperature for storage":"-35...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"5 kA at 550 V AC 50/60 Hz conforming to IEC 60947-2 15 kA at 125 V DC conforming to IEC 60947-2 15 kA at 250 V DC conforming to IEC 60947-2 18 kA at 380 V AC 50/60 Hz conforming to IEC 60947-2 18 kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 12.5 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 42.5 kA at 110/130 V AC 50/60 Hz conforming to IEC 60947-2 42.5 kA at 220/230/240 V AC 50/60 Hz conforming to IEC 60947-2","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/1a9e331e4382ed5e4e5b5af2693ce67d.pdf","sourceUrl":"https://www.se.com/eg/en/product/EZC250H3225/circuit-breaker-easypact-ezc250h-tmd-225-a-3-poles-3d/"},"ai":{"faq":[{"question":"What is the breaking capacity of the EZC250H3225 at 400 V?","answer":"At 400–415 V AC, the EZC250H3225 delivers 36 kA Icu. That is the SCCR you design the downstream coordination around for European 400 V distribution."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/EZC250H3225","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/EZC250H3225 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}