{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"EZC250H3250","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"EZC250H3250","canonicalUrl":"https://aoctrl.com/schneider/EZC250H3250","factsUrl":"https://aoctrl.com/api/mcp/products/EZC250H3250","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact EZC250H, EZC250H3250, 3P circuit breaker, 250 A, thermal-magnetic TM-D trip unit, 10-85 kA breaking capacity, 60 mm depth, 105 mm width, 165 mm height.","salesMarkdown":"The EZC250H3250 is a 3-pole EasyPact EZC250H circuit breaker from Schneider Electric, rated 250 A at 40 °C ambient with a thermal-magnetic TM-D trip unit. The 250 A trip rating at 50 °C means the breaker holds full rated current in a warm panel — useful when the enclosure is stacked with other heat-generating devices. The breaking capacity varies by voltage: 85 kA Icu at 240 V AC, 36 kA at 400 V AC, and 10 kA at 550 V AC. At 400 V, that 36 kA Icu is typical for a distribution board downstream of a transformer; the 10 kA at 550 V covers industrial line-to-line supplies where fault current is lower. The 690 V rated insulation voltage and 550 V AC / 250 V DC operational voltage confirm it handles standard three-phase 480 V and 600 V class systems, plus DC circuits for battery or UPS tie-ins. The 3t protected poles with no neutral protection means it's a straight three-pole breaker for a three-phase load — no switched neutral. ## Deployment context Fixed mounting on a backplate with front connections top and bottom — this breaker bolts into a panel, not onto a DIN rail. The toggle control gives positive contact indication so an operator can visually confirm the breaker is open or closed without metering. Designed to EN/IEC 60947-2 and GB/T 14048.2 — the global standard for low-voltage molded-case circuit breakers. IK07 impact resistance handles light tool drops during panel assembly. Mechanical durability of 10,000 cycles is typical for a distribution breaker — not for frequent switching, but fine for protection duty where it operates a few times a year.","metaTitle":"Schneider Electric EZC250H3250 EasyPact EZC250H Circuit Brea","metaDescription":"Schneider Electric EZC250H3250 EasyPact EZC250H 3P circuit breaker, 250 A rated current, thermal-magnetic TM-D trip unit, 10-85 kA breaking capacity. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Circuit Breaker Accessories"],"specifications":{"Depth":"60 mm","Width":"105 mm","title":"EZC250H3250","Height":"165 mm","Standards":"EN/IEC 60947-2 EN/IEC 60947-1 GB/T 14048.2","description":"circuit breaker Easypact EZC250H - TMD - 250 A - 3 poles 3d","Control type":"Toggle","Network type":"AC DC","Mounting mode":"Fixed","Trip unit name":"TM-D","Protection type":"Overload protection Short-circuit protection","lifecycle_stage":"current","Connection pitch":"35 mm","Local signalling":"Positive contact indication","Mounting support":"Backplate","Pollution degree":"3 conforming to IEC 60664-1 3 conforming to IEC 947-1","Range of product":"EasyPact","Trip unit rating":"250 A at 50 °C","Breaking capacity":"10 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 125 V DC 1P conforming to IEC 60947-2 30 kA Icu at 250 V DC 2P conforming to IEC 60947-2 36 kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 110...130 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"Easypact EZC250H","Network frequency":"50/60 Hz","Poles description":"3P","Upside connection":"Front","Device application":"Distribution","[In] rated current":"250 A at 40 °C","Downside connection":"Front","Circuit breaker name":"Easypact EZC250H","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A","Mechanical durability":"10000 cycles","Breaking capacity code":"H","IK degree of protection":"IK07 conforming to IEC 62262","IP degree of protection":"IP20 conforming to IEC 60529","Earth-leakage protection":"Without","Product or component type":"Circuit breaker","Suitability for isolation":"Yes conforming to IEC 60947-2","Neutral protection setting":"Without protection","Protected poles description":"3t","[Ui] rated insulation voltage":"690 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"550 V AC 50/60 Hz conforming to IEC 60947-2 250 V DC conforming to IEC 60947-2","Ambient air temperature for storage":"-35...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"5 kA at 550 V AC 50/60 Hz conforming to IEC 60947-2 15 kA at 125 V DC conforming to IEC 60947-2 15 kA at 250 V DC conforming to IEC 60947-2 18 kA at 380 V AC 50/60 Hz conforming to IEC 60947-2 18 kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 12.5 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 42.5 kA at 110/130 V AC 50/60 Hz conforming to IEC 60947-2 42.5 kA at 220/230/240 V AC 50/60 Hz conforming to IEC 60947-2","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/71b2290f064fb2c5c99b3859af4798a8.pdf","sourceUrl":"https://www.se.com/ae/en/product/EZC250H3250/circuit-breaker-easypact-ezc250h-tmd-250-a-3-poles-3d/"},"ai":{"faq":[{"question":"How do I get current pricing and availability for EZC250H3250?","answer":"The EZC250H3250 is sourced to order against an RFQ through independent distribution. Submit a request for quote to confirm current pricing and availability at the time of your order."},{"question":"What is the breaking capacity of EZC250H3250 at 400 V?","answer":"At 400...415 V AC 50/60 Hz, the EZC250H3250 delivers 36 kA Icu per IEC 60947-2. This is sufficient for most distribution boards downstream of a transformer with typical fault levels."},{"question":"What compliance documentation does this brand provide for EZC250H3250?","answer":"The EZC250H3250 is designed to EN/IEC 60947-2 and GB/T 14048.2 standards. It carries IP20 finger protection and IK07 impact resistance. The manufacturer typically provides a declaration of conformity and test reports upon request through the supply channel."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/EZC250H3250","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/EZC250H3250 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}