{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"EZC250N3100","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"EZC250N3100","canonicalUrl":"https://aoctrl.com/schneider/EZC250N3100","factsUrl":"https://aoctrl.com/api/mcp/products/EZC250N3100","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact EZC250N, EZC250N3100, 3-pole thermal-magnetic MCCB, 100 A rated current, 20 kA Icu at 440 V AC, TM-D trip unit, fixed mount.","salesMarkdown":"The EZC250N3100 is a 3-pole EasyPact EZC250N MCCB rated 100 A at 40 °C and 100 A at 50 °C — the thermal-magnetic TM-D trip unit handles overload and short-circuit protection without an earth-leakage module. The headline breaking capacity is 20 kA Icu at 440 V AC 50/60 Hz per IEC 60947-2; that means it can safely interrupt a fault up to 20 kA at that voltage without welding contacts or cascading upstream. At 240 V AC the same frame delivers 50 kA Icu, so it covers high-fault service-entrance panels on lower-voltage legs. The 690 V rated insulation voltage and 550 V max operational voltage confirm it fits 400 V distribution networks with headroom. IP20 finger-safe terminals and IK07 impact resistance suit it for general-purpose industrial panels, not washdown zones. Designed and tested to EN/IEC 60947-2 and GB/T 14048.2, with pollution degree 3 per IEC 60664-1 — suitable for industrial environments with conductive dust or condensation.","metaTitle":"Schneider Electric EZC250N3100 EasyPact EZC250N, 100 A, 20 k","metaDescription":"Schneider Electric EZC250N3100 EasyPact EZC250N circuit breaker, 100 A, 20 kA Icu at 440 V AC, thermal-magnetic TM-D trip unit, 3-pole, current production, sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Circuit Breaker Accessories"],"specifications":{"Depth":"60 mm","Width":"105 mm","title":"EZC250N3100","Height":"165 mm","Standards":"EN/IEC 60947-2 GB/T 14048.2 EN/IEC 60947-1","description":"circuit breaker,EasyPact EZC250N,TMD, 100A,3 poles 3d","Control type":"Toggle","Network type":"DC AC","Mounting mode":"Fixed","Trip unit name":"TM-D","Protection type":"Overload protection Short-circuit protection","lifecycle_stage":"current","Connection pitch":"35 mm","Local signalling":"Positive contact indication","Mounting support":"Backplate","Pollution degree":"3 conforming to IEC 60664-1 3 conforming to IEC 947-1","Range of product":"EasyPact","Trip unit rating":"100 A at 50 °C","Breaking capacity":"20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 110...130 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 125 V DC 1P conforming to IEC 60947-2 20 kA Icu at 250 V DC 2P conforming to IEC 60947-2 25 kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2 8 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"Easypact EZC250N","Network frequency":"50/60 Hz","Poles description":"3P","Upside connection":"Front","Device application":"Distribution","[In] rated current":"100 A at 40 °C","Downside connection":"Front","Circuit breaker name":"Easypact EZC250N","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A","Mechanical durability":"10000 cycles","Breaking capacity code":"N","IK degree of protection":"IK07 conforming to IEC 62262","IP degree of protection":"IP20 conforming to IEC 60529","Earth-leakage protection":"Without","Product or component type":"Circuit breaker","Suitability for isolation":"Yes conforming to IEC 60947-2","Neutral protection setting":"Without protection","Protected poles description":"3t","[Ui] rated insulation voltage":"690 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"550 V AC 50/60 Hz conforming to IEC 60947-2 250 V DC conforming to IEC 60947-2","Ambient air temperature for storage":"-35...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"10 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 25 kA at 110/130 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 125 V DC conforming to IEC 60947-2 10 kA at 250 V DC conforming to IEC 60947-2 25 kA at 220/230/240 V AC 50/60 Hz conforming to IEC 60947-2 4 kA at 550 V AC 50/60 Hz conforming to IEC 60947-2 12.5 kA at 380 V AC 50/60 Hz conforming to IEC 60947-2 12.5 kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$129.50","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/3af89ee61f57b87f96f82ddfd2c1dc07.pdf","sourceUrl":"https://www.se.com/vn/en/product/EZC250N3100/circuit-breakereasypact-ezc250n-tmd-100a-3-poles-3d/"},"ai":{"faq":[{"question":"How do I get current pricing and availability for EZC250N3100?","answer":"Pricing and stock levels are confirmed at quote time. Submit an RFQ through this listing; the part is sourced to order through independent distribution channels."},{"question":"What is the breaking capacity of EZC250N3100 at 440 V?","answer":"The EZC250N3100 is rated 20 kA Icu at 440 V AC 50/60 Hz per IEC 60947-2. At 240 V AC the same frame delivers 50 kA Icu."},{"question":"What compliance documentation does Schneider provide for EZC250N3100?","answer":"The part is certified to EN/IEC 60947-2 and GB/T 14048.2, with pollution degree 3 per IEC 60664-1. It carries IEC 60947-2 isolation suitability. RoHS and REACH declarations are standard for Schneider EasyPact products; request them with your RFQ."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/EZC250N3100","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/EZC250N3100 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}