{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"EZC250N4100","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"EZC250N4100","canonicalUrl":"https://aoctrl.com/schneider/EZC250N4100","factsUrl":"https://aoctrl.com/api/mcp/products/EZC250N4100","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact EZC250N, circuit breaker, 4P, 100 A, TM-D trip unit, 20 kA Icu at 440 V AC, front connections, fixed mount.","salesMarkdown":"The Schneider Electric EZC250N4100 is a 4-pole EasyPact EZC250N circuit breaker with a fixed thermal-magnetic TM-D trip unit rated 100 A at 40 °C (100 A at 50 °C). The N breaking capacity code means it delivers 20 kA Icu at 440 V AC 50/60 Hz, with higher ratings at lower voltages: 50 kA Icu at 220...240 V AC and 25 kA Icu at 380...415 V AC. For DC circuits, it offers 20 kA Icu at 125 V DC (1P) and 20 kA Icu at 250 V DC (2P). This makes it suitable for main or branch feeder protection where fault levels are moderate. Mounts fixed to a backplate via the 35 mm connection pitch. Front-facing connections on both line and load sides simplify busbar or cable routing in a panel. The toggle handle provides positive contact indication — you can see the contact state without removing the cover. IP20 finger-safe protection on the front, IK07 impact resistance. Pollution degree 3 per IEC 60947 means it tolerates conductive pollution in industrial environments.","metaTitle":"Schneider Electric EZC250N4100 EasyPact EZC250N Circuit Brea","metaDescription":"Schneider Electric EZC250N4100 EasyPact EZC250N circuit breaker. 100 A thermal-magnetic trip unit, 4 poles, 20 kA Icu at 440 V AC. Sourced to order against an RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Circuit Breaker Accessories"],"specifications":{"Depth":"60 mm","Width":"140 mm","title":"EZC250N4100","Height":"165 mm","Standards":"JIS C8201-2-2 GB/T 14048.2 EN/IEC 60947-1 EN/IEC 60947-2","description":"circuit breaker Easypact EZC250N - TMD - 100 A - 4 poles 3d","Control type":"Toggle","Network type":"DC AC","Mounting mode":"Fixed","Trip unit name":"TM-D","Protection type":"Overload protection Short-circuit protection","lifecycle_stage":"current","Connection pitch":"35 mm","Local signalling":"Positive contact indication","Mounting support":"Backplate","Pollution degree":"3 conforming to IEC 60947","Range of product":"EasyPact","Trip unit rating":"100 A at 50 °C","Breaking capacity":"20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 125 V DC 1P conforming to IEC 60947-2 20 kA Icu at 250 V DC 2P conforming to IEC 60947-2 8 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"Easypact EZC250N","Network frequency":"50/60 Hz","Poles description":"4P","Upside connection":"Front","Device application":"Distribution","[In] rated current":"100 A at 40 °C","Downside connection":"Front","Circuit breaker name":"Easypact EZC250N","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A","Mechanical durability":"10000 cycles","Breaking capacity code":"N","IK degree of protection":"IK07 conforming to EN 50102","IP degree of protection":"IP20 conforming to IEC 60529","Earth-leakage protection":"Without","Product or component type":"Circuit breaker","Suitability for isolation":"Yes conforming to IEC 60947-2","Neutral protection setting":"Without protection","Protected poles description":"3t","[Ui] rated insulation voltage":"690 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"550 V AC 50/60 Hz conforming to IEC 60947-2 250 V DC conforming to IEC 60947-2","Ambient air temperature for storage":"-35...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"10 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 25 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 125 V DC conforming to IEC 60947-2 10 kA at 250 V DC conforming to IEC 60947-2 4 kA at 550 V AC 50/60 Hz conforming to IEC 60947-2 12.5 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$130.83","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/af7b3ec85b3b36b5143d8569021c5b3b.pdf","sourceUrl":"https://www.se.com/ph/en/product/EZC250N4100/circuit-breaker-easypact-ezc250n-tmd-100-a-4-poles-3d/"},"ai":{"faq":[{"question":"Where can I buy EZC250N4100 and how do I get a price?","answer":"The EZC250N4100 is sourced and quoted to order against an RFQ through independent distribution. Submit an RFQ for current pricing and availability."},{"question":"What is EZC250N4100's breaking capacity at 440 V AC?","answer":"20 kA Icu at 440 V AC 50/60 Hz per IEC 60947-2. At 380...415 V AC it rises to 25 kA Icu."},{"question":"What compliance documentation does this brand provide for EZC250N4100?","answer":"The breaker is certified to JIS C8201-2-2, GB/T 14048.2, EN/IEC 60947-1, and EN/IEC 60947-2. It carries IP20 per IEC 60529 and IK07 per EN 50102."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/EZC250N4100","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/EZC250N4100 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}