{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"EZC250N4160","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"EZC250N4160","canonicalUrl":"https://aoctrl.com/schneider/EZC250N4160","factsUrl":"https://aoctrl.com/api/mcp/products/EZC250N4160","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact EZC250N, thermal-magnetic circuit breaker, 4 poles, 160 A, TM-D trip unit, 20 kA Icu at 440 V AC.","salesMarkdown":"The Schneider Electric EZC250N4160 is a 4-pole EasyPact EZC250N circuit breaker rated 160 A at 40 °C, with a TM-D thermal-magnetic trip unit. This breaker is a fixed-mount backplate unit — no DIN-rail clip, so plan for screw-down installation on a panel backplate. Connection pitch is 35 mm, matching standard bus-bar spacing for a 4-pole breaker. ## Protection profile and coordination The TM-D trip unit combines a thermal bimetal for overload protection and a magnetic coil for short-circuit protection. It protects 3 poles with no neutral protection and no built-in earth-leakage module — if you need ground-fault protection, you add an external relay or a different breaker variant. Utilization category A means it's not intended for frequent switching of motor loads under load; it's a distribution breaker, sized for cable and bus protection in a distribution panel. The 10,000-cycle mechanical durability is typical for a panelboard breaker — fine for infrequent switching, not for daily motor starting.","metaTitle":"Schneider Electric EZC250N4160 EasyPact EZC250N Circuit Brea","metaDescription":"Schneider Electric EZC250N4160 EasyPact EZC250N circuit breaker, 160 A rated current, 4 poles, thermal-magnetic TM-D trip unit, 20 kA breaking capacity at 440 V AC. Sourced to orde","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"60 mm","Width":"140 mm","Height":"165 mm","Voltage":"550 V AC 50/60 Hz conforming to IEC 60947-2 250 V DC conforming to IEC 60947-2","IP Rating":"IP20","Application":"Distribution","Control Type":"Toggle","Product Status":"Active","Terminal Pitch":"35 mm","Trip Unit Type":"Thermal-magnetic","Pollution Degree":"3 conforming to IEC 60947","Temp Storage Max":"85 °C","Temp Storage Min":"-35 °C","Breaking Capacity":"20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 125 V DC 1P conforming to IEC 60947-2 20 kA Icu at 250 V DC 2P conforming to IEC 60947-2 8 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2","Insulation Voltage Ui":"690 V AC 50/60 Hz conforming to IEC 60947-2","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-35...85 °C","Connection Surface Top":"Front","Mechanical Life Cycles":"10000 cycles","Connection Surface Bottom":"Front","Main Product Or Component Type":"Circuit breaker","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$169.53","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/5e473decdb22535bba0bbe494d05274a.pdf","sourceUrl":"https://www.se.com/ae/en/product/EZC250N4160/circuit-breaker-easypact-ezc250n-tmd-160-a-4-poles-3d/","alternativesUrl":"https://aoctrl.com/api/mcp/products/EZC250N4160/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/EZC250N4160","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/EZC250N4160 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}