{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"EZC250N44080","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"EZC250N44080","canonicalUrl":"https://aoctrl.com/schneider/EZC250N44080","factsUrl":"https://aoctrl.com/api/mcp/products/EZC250N44080","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact EZC250N, EZC250N44080, 80 A thermal-magnetic MCCB, 4 poles, 20 kA Icu at 440 V AC, IEC 60947-2.","salesMarkdown":"Four poles protected (4t), no neutral protection. This is a Category A breaker — no intentional short-time delay, so it trips instantaneously on fault, sized for distribution duty where selective coordination is handled upstream. ## Breaking capacity and voltage ratings Breaking capacity code N: 20 kA Icu at 440 V AC, 25 kA at 380–415 V AC, 50 kA at 220–240 V AC, and 8 kA at 550 V AC — all per IEC 60947-2. On DC: 20 kA at 125 V DC (1P) and 250 V DC (2P). Rated insulation voltage 690 V AC; operational voltage up to 550 V AC or 250 V DC. Fixed mounting on a backplate, 140 mm wide × 165 mm high × 60 mm deep. Connection pitch 35 mm. IP20 finger-safe enclosure; IK07 impact resistance. Certified to IEC 60947-1, IEC 60947-2, JIS C8201-2-2, and GB/T 14048.2. Positive contact indication on the toggle. Mechanical durability 10,000 cycles.","metaTitle":"Schneider Electric EZC250N44080 EasyPact EZC250N 80A 4P MCCB","metaDescription":"Schneider Electric EZC250N44080 EasyPact EZC250N MCCB, 80 A thermal-magnetic trip, 4 poles, 20 kA Icu at 440 V AC. IEC 60947-2. Active production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"60 mm","Width":"140 mm","Height":"165 mm","Standards":"JIS C8201-2-2 EN/IEC 60947-1 GB/T 14048.2 EN/IEC 60947-2","Control type":"Toggle","Network type":"DC AC","Mounting mode":"Fixed","Trip unit name":"TM-D","Protection type":"Overload protection Short-circuit protection","lifecycle_stage":"current","Connection pitch":"35 mm","Local signalling":"Positive contact indication","Mounting support":"Backplate","Pollution degree":"3 conforming to IEC 60947","Range of product":"EasyPact","Trip unit rating":"80 A at 50 °C","Breaking capacity":"20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 125 V DC 1P conforming to IEC 60947-2 20 kA Icu at 250 V DC 2P conforming to IEC 60947-2 8 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"Easypact EZC250N","Network frequency":"50/60 Hz","Poles description":"4P","Upside connection":"Front","Device application":"Distribution","[In] rated current":"80 A at 40 °C","Downside connection":"Front","Circuit breaker name":"Easypact EZC250N","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A","Mechanical durability":"10000 cycles","Breaking capacity code":"N","IK degree of protection":"IK07 conforming to EN 50102","IP degree of protection":"IP20 conforming to IEC 60529","Earth-leakage protection":"Without","Product or component type":"Circuit breaker","Suitability for isolation":"Yes conforming to IEC 60947-2","Neutral protection setting":"Without protection","Protected poles description":"4t","[Ui] rated insulation voltage":"690 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"550 V AC 50/60 Hz conforming to IEC 60947-2 250 V DC conforming to IEC 60947-2","Ambient air temperature for storage":"-35...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"10 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 25 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 125 V DC conforming to IEC 60947-2 10 kA at 250 V DC conforming to IEC 60947-2 4 kA at 550 V AC 50/60 Hz conforming to IEC 60947-2 12.5 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/06fb2d28480096a9cbb119879aaef5ba.pdf","sourceUrl":"https://www.se.com/vn/en/product/EZC250N44080/circuit-breaker-easypact-ezc250n-tmd-80-a-4-poles-4d/","alternativesUrl":"https://aoctrl.com/api/mcp/products/EZC250N44080/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of EZC250N44080 at 440 V AC?","answer":"20 kA Icu at 440 V AC 50/60 Hz per IEC 60947-2. At 380–415 V AC it rises to 25 kA."},{"question":"How do I get current pricing and availability for EZC250N44080?","answer":"This part is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time."},{"question":"What compliance documentation does this brand provide for EZC250N44080?","answer":"The breaker is certified to IEC 60947-1, IEC 60947-2, JIS C8201-2-2, and GB/T 14048.2. It carries IP20 and IK07 ratings and is suitable for isolation per IEC 60947-2."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/EZC250N44080","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/EZC250N44080 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}