{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"EZC250N44225","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"EZC250N44225","canonicalUrl":"https://aoctrl.com/schneider/EZC250N44225","factsUrl":"https://aoctrl.com/api/mcp/products/EZC250N44225","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact EZC250N, 4-pole MCCB, 225 A thermal-magnetic TM-D trip unit, 20 kA Icu at 440 V AC, IP20, IEC 60947-2.","salesMarkdown":"The Schneider Electric EasyPact EZC250N44225 is a 4-pole moulded-case circuit breaker (MCCB) from the EasyPact EZC250N series, fitted with a TM-D thermal-magnetic trip unit rated 225 A at 50 °C. The TM-D trip provides overload and short-circuit protection via a thermal-magnetic mechanism — the thermal element handles sustained overcurrents, the magnetic element clears high-fault events instantly. No earth-leakage protection is built in (specified as 'Without'). The EZC250N44225 carries a breaking capacity code 'N' and delivers 20 kA Icu at 440 V AC 50/60 Hz per IEC 60947-2. At 380–415 V AC the rating rises to 25 kA Icu; at 220–240 V AC it reaches 50 kA Icu. For DC circuits, it is rated 20 kA Icu at 125 V DC (1-pole) and 20 kA Icu at 250 V DC (2-pole). At 550 V AC the rating drops to 8 kA Icu — a key constraint if your line voltage runs high. The breaker is utilisation category A, meaning it is not intended for frequent switching of motor loads under normal conditions — it is a distribution breaker, not a motor-protective device. Fixed-mount design for backplate installation. Front-front connections (both line and load side terminate on the front face), which simplifies busbar routing in a panel but means you need clearance in front for cable access. The connection pitch is 35 mm. IP20 finger-safe protection on the front; the enclosure itself is rated IK07 for impact resistance. Dimensions: 165 mm high, 140 mm wide, 60 mm deep. Designed and tested to IEC 60947-1 and IEC 60947-2, with additional compliance to JIS C8201-2-2 and GB/T 14048.2.","metaTitle":"Schneider EasyPact EZC250N44225 MCCB, 225 A, 20 kA","metaDescription":"Schneider Electric EasyPact EZC250N44225 4-pole MCCB, 225 A thermal-magnetic trip, 20 kA Icu at 440 V AC. Active production, sourced to order. IEC 60947-2, IP20.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"60 mm","Width":"140 mm","Height":"165 mm","Standards":"JIS C8201-2-2 EN/IEC 60947-1 GB/T 14048.2 EN/IEC 60947-2","Control type":"Toggle","Network type":"AC DC","Mounting mode":"Fixed","Trip unit name":"TM-D","Protection type":"Overload protection Short-circuit protection","lifecycle_stage":"current","Connection pitch":"35 mm","Local signalling":"Positive contact indication","Mounting support":"Backplate","Pollution degree":"3 conforming to IEC 60947","Range of product":"EasyPact","Trip unit rating":"225 A at 50 °C","Breaking capacity":"20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 125 V DC 1P conforming to IEC 60947-2 20 kA Icu at 250 V DC 2P conforming to IEC 60947-2 8 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"Easypact EZC250N","Network frequency":"50/60 Hz","Poles description":"4P","Upside connection":"Front","Device application":"Distribution","[In] rated current":"225 A at 40 °C","Downside connection":"Front","Circuit breaker name":"Easypact EZC250N","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A","Mechanical durability":"10000 cycles","Breaking capacity code":"N","IK degree of protection":"IK07 conforming to EN 50102","IP degree of protection":"IP20 conforming to IEC 60529","Earth-leakage protection":"Without","Product or component type":"Circuit breaker","Suitability for isolation":"Yes conforming to IEC 60947-2","Neutral protection setting":"Without protection","Protected poles description":"4t","[Ui] rated insulation voltage":"690 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"550 V AC 50/60 Hz conforming to IEC 60947-2 250 V DC conforming to IEC 60947-2","Ambient air temperature for storage":"-35...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"10 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 25 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 125 V DC conforming to IEC 60947-2 10 kA at 250 V DC conforming to IEC 60947-2 4 kA at 550 V AC 50/60 Hz conforming to IEC 60947-2 12.5 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/7dc2a06135402c977f926b60bc687bfd.pdf","sourceUrl":"https://www.se.com/vn/en/product/EZC250N44225/circuit-breaker-easypact-ezc250n-tmd-225-a-4-poles-4d/","alternativesUrl":"https://aoctrl.com/api/mcp/products/EZC250N44225/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy EZC250N44225 and get a price?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Submit an RFQ for current availability and pricing — no stock or price figures are published here."},{"question":"What is the breaking capacity of EZC250N44225 at 440 V?","answer":"20 kA Icu at 440 V AC 50/60 Hz per IEC 60947-2. At 380–415 V it is 25 kA; at 220–240 V it is 50 kA."},{"question":"What standards does EZC250N44225 comply with?","answer":"It complies with IEC 60947-1, IEC 60947-2, JIS C8201-2-2, and GB/T 14048.2. Pollution degree 3, suitable for isolation."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/EZC250N44225","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/EZC250N44225 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}