{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"EZC400H3400","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"EZC400H3400","canonicalUrl":"https://aoctrl.com/schneider/EZC400H3400","factsUrl":"https://aoctrl.com/api/mcp/products/EZC400H3400","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact EZC400H, EZC400H3400, 3-pole molded case circuit breaker, 400 A thermal-magnetic trip unit TM-D, 50 kA Icu at 380-440 V AC, IEC 60947-2, IP20, black.","salesMarkdown":"The Schneider Electric EZC400H3400 is a 3-pole molded case circuit breaker from the EasyPact EZC400H series, rated 400 A at 50 °C (trip unit TM-D). The thermal-magnetic trip unit provides both overload protection (thermal curve) and short-circuit protection (magnetic instantaneous trip set at 3500 A). Breaking capacity is 50 kA Icu at 380 V AC, 400-415 V AC, and 440 V AC per IEC 60947-2. At 220-240 V AC the Icu rises to 70 kA. Electrical durability is 4000 cycles at 415 V AC, mechanical durability 10,000 cycles. Mounts fixed to a backplate (not DIN rail) with front connections both top and bottom. IP20 finger-safe protection on the front; IK07 impact rating means it withstands a 2 J hammer blow — fine for general industrial enclosures. Pollution degree 3 per IEC 60947, so it's rated for conductive environments (condensation, light dust). Physical footprint: 255 mm high, 185 mm wide, 140 mm deep. Connection pitch (pole spacing) is 44 mm. The breaker uses a toggle handle for manual control and provides positive contact indication — the handle position mechanically reflects the contact state, not a separate flag. No earth-leakage protection module is integrated; neutral protection is not provided (3-pole, no neutral pole). If ground-fault or neutral protection is required, an external add-on must be wired downstream. Standards compliance includes IEC 60947-2, EN 60947-2, JIS C8201-2-2, and GB/T 14048.2. No UL or CSA listing is stated in the record.","metaTitle":"Schneider Electric EZC400H3400 EasyPact EZC400H, 400 A, 50 k","metaDescription":"Schneider Electric EZC400H3400 EasyPact EZC400H circuit breaker, 400 A rated at 50 °C, 50 kA Icu at 380-440 V AC, IEC 60947-2, active production, available to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":[],"specifications":{"Color":"Black","Depth":"140 mm","Width":"185 mm","Height":"255 mm","Voltage":"440 V AC 50/60 Hz conforming to IEC 60947-2","IP Rating":"IP20","Application":"Distribution","Control Type":"Toggle","Product Status":"Active","Terminal Pitch":"44 mm","Trip Unit Type":"Thermal-magnetic","Pollution Degree":"3 conforming to IEC 60947","Temp Storage Max":"85 °C","Temp Storage Min":"-35 °C","Breaking Capacity":"50 kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 70 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2","Insulation Voltage Ui":"690 V AC 50/60 Hz conforming to IEC 60947-2","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-35...85 °C","Connection Surface Top":"Front","Electrical Life Cycles":"Category A: 4000 cycles 415 V AC 50/60 Hz conforming to IEC 60947-2","Mechanical Life Cycles":"10000 cycles","Connection Surface Bottom":"Front","Main Product Or Component Type":"Circuit breaker","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/c8f370832684220ea0517200de97e6a4.pdf","sourceUrl":"https://www.se.com/ph/en/product/EZC400H3400/circuit-breaker-easypact-ezc400h-tmd-400-a-3-poles-3d/","alternativesUrl":"https://aoctrl.com/api/mcp/products/EZC400H3400/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/EZC400H3400","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/EZC400H3400 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}