{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"EZC400H4400","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"EZC400H4400","canonicalUrl":"https://aoctrl.com/schneider/EZC400H4400","factsUrl":"https://aoctrl.com/api/mcp/products/EZC400H4400","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact EZC400H, EZC400H4400, 400 A thermal-magnetic MCCB, 4 poles, 50 kA Icu at 400-415 V AC, fixed mount, front connection.","salesMarkdown":"The Schneider Electric EZC400H4400 is a 400 A thermal-magnetic MCCB from the EasyPact EZC400H series, built for distribution duty in fixed-mount switchboards. The trip unit is rated 400 A at 50 °C — that's the continuous current it carries without tripping at that ambient, so in a 40 °C panel it handles the same 400 A with extra thermal headroom. The TM-D trip combines a thermal bimetal for overload protection and a fixed magnetic trip set at 4000 A for short-circuit protection. At 220-240 V AC it rises to 70 kA Icu. The 'H' in the name designates this high-breaking-capacity version, which gives selectivity headroom downstream of a larger upstream device. The 4-pole version (4P) switches all three phases plus the neutral, though the neutral pole is unprotected — it tracks the phase poles mechanically. Fixed mount on a backplate, front connection both top and bottom. The 45 mm pole pitch matches standard busbar spacing for panelboard integration. IP20 finger-safe terminals; IK07 impact resistance means it withstands accidental tool strikes during panel wiring.","metaTitle":"Schneider Electric EZC400H4400 EasyPact EZC400H 400A 4P MCCB","metaDescription":"Schneider Electric EZC400H4400 EasyPact EZC400H MCCB, 400A at 50°C, 4 poles, 50 kA Icu at 400-415 V AC. Current production, sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":[],"specifications":{"Color":"Black","Depth":"140 mm","Width":"185 mm","Height":"255 mm","Voltage":"440 V AC 50/60 Hz conforming to IEC 60947-2","IP Rating":"IP20","Application":"Distribution","Control Type":"Toggle","Product Status":"Active","Terminal Pitch":"45 mm","Trip Unit Type":"Thermal-magnetic","Pollution Degree":"3 conforming to IEC 60947","Temp Storage Max":"85 °C","Temp Storage Min":"-35 °C","Insulation Voltage Ui":"690 V AC 50/60 Hz conforming to IEC 60947-2","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-35...85 °C","Connection Surface Top":"Front","Electrical Life Cycles":"Category A: 4000 cycles 415 V AC 50/60 Hz conforming to IEC 60947-2","Mechanical Life Cycles":"10000 cycles","Connection Surface Bottom":"Front","Main Product Or Component Type":"Circuit breaker","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/d9644d90b5c0258efef34442c0a6620e.pdf","sourceUrl":"https://www.se.com/vn/en/product/EZC400H4400/circuit-breaker-easypact-ezc400h-tmd-400-a-4-poles-3d/","alternativesUrl":"https://aoctrl.com/api/mcp/products/EZC400H4400/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/EZC400H4400","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/EZC400H4400 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}