{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"EZC400N3250","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"EZC400N3250","canonicalUrl":"https://aoctrl.com/schneider/EZC400N3250","factsUrl":"https://aoctrl.com/api/mcp/products/EZC400N3250","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact EZC400N, 3-pole circuit breaker, 400 A rated, 36 kA Icu at 440 V AC, thermal-magnetic TM-D trip unit, fixed mount.","salesMarkdown":"The EZC400N3250 is a 3-pole EasyPact EZC400N circuit breaker from Schneider Electric, rated 400 A at 40 °C with a thermal-magnetic TM-D trip unit. This breaker carries a 36 kA Icu (ultimate breaking capacity) at 440 V AC, 50/60 Hz, per IEC 60947-2. At 220/230 V AC it bumps to 40 kA Icu. The 'N' in the part number tells you it's the standard breaking capacity level in the EZC400 family; there's also an 'H' (high) and 'S' (superior) variant if you need more. The TM-D trip unit is thermal-magnetic — a bimetal strip handles overloads (slow response to sustained overcurrent), and a solenoid handles short-circuits (instantaneous trip). The magnetic trip is factory-set to 3500 A, which is about 8.75x the 400 A frame rating. That's a typical fixed magnetic setting for distribution breakers; it avoids nuisance tripping on motor inrush but clears a hard fault fast. Overload protection is adjustable via the TM-D rating plug — this unit ships with a 250 A plug at 50 °C, so if your ambient in the panel runs hot, the breaker derates accordingly. No earth-leakage module built in; you add an external Vigi unit if you need ground-fault protection. Mounts fixed to a backplate — no DIN rail here. Dimensions are 255 mm high, 185 mm wide, 140 mm deep. The 44 mm pole pitch is standard for this class of molded-case breaker, so bus-bar kits and lug kits from the EasyPac range fit without surprises. Front-connect top and bottom means you land cables straight in without reaching around the back. IP20 finger-safe protection on the front; IK07 impact rating means it shrugs off a tool drop or a panel door slam. Pollution degree 3 per IEC 60947 — that's conductive pollution (like dust with moisture), so it's fine in most industrial enclosures but not sealed for washdown. Meets EN/IEC 60947-1 and 60947-2 (low-voltage switchgear and controlgear), plus GB/T 14048.2 (Chinese national standard) and JIS C8201-2-2 (Japanese industrial standard). Utilisation category A means it's not intended for frequent switching under load; that's for the contactor, not the breaker.","metaTitle":"EZC400N3250 EasyPact EZC400N 3P 400A Circuit Breaker, 36kA I","metaDescription":"Schneider Electric EZC400N3250 EasyPact EZC400N 3-pole circuit breaker, 400 A rated current, 36 kA Icu at 440 V AC. Active production. Sourced to order. Quoted against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Color":"Black","Depth":"140 mm","Width":"185 mm","Height":"255 mm","Voltage":"440 V AC 50/60 Hz conforming to IEC 60947-2","IP Rating":"IP20","Application":"Distribution","Control Type":"Toggle","Product Status":"Active","Terminal Pitch":"44 mm","Trip Unit Type":"Thermal-magnetic","Pollution Degree":"3 conforming to IEC 60947","Temp Storage Max":"85 °C","Temp Storage Min":"-35 °C","Breaking Capacity":"36 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 40 kA Icu at 220/230 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2","Insulation Voltage Ui":"690 V AC 50/60 Hz conforming to IEC 60947-2","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-35...85 °C","Connection Surface Top":"Front","Electrical Life Cycles":"Category A: 4000 cycles 415 V AC 50/60 Hz conforming to IEC 60947-2","Mechanical Life Cycles":"10000 cycles","Connection Surface Bottom":"Front","Main Product Or Component Type":"Circuit breaker","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/678137c46136b4a01e7d90c78d76e6af.pdf","sourceUrl":"https://www.se.com/th/en/product/EZC400N3250/circuit-breaker-easypact-ezc400n-tmd-250-a-3-poles-3d/","alternativesUrl":"https://aoctrl.com/api/mcp/products/EZC400N3250/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/EZC400N3250","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/EZC400N3250 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}