{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"EZC400N3300","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"EZC400N3300","canonicalUrl":"https://aoctrl.com/schneider/EZC400N3300","factsUrl":"https://aoctrl.com/api/mcp/products/EZC400N3300","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact EZC400N, EZC400N3300, 3-pole molded case circuit breaker, 400 A rated at 40 °C, 36 kA Icu at 440 V AC, TM-D thermal-magnetic trip unit, fixed mount.","salesMarkdown":"If your enclosure runs hotter, the TM-D thermal-magnetic trip unit will derate; the trip unit itself is rated 300 A at 50 °C, so that's your ceiling in a warm cabinet. For a 400 A distribution breaker feeding a downstream panel, that 36 kA gives you solid selectivity headroom against most transformer secondary faults. The Utilisation category is A, meaning it's not intended for frequent switching of motor loads — this is a distribution breaker, not a motor circuit protector. Fixed mount on a backplate, front connection both top and bottom. IP20 finger-safe protection means it's suitable for enclosed distribution boards — no shock hazard during maintenance with the door open. IK07 impact resistance handles accidental tool drops during commissioning. Complies with EN/IEC 60947-2 and 60947-1, plus GB/T 14048.2 and JIS C8201-2-2 for Chinese and Japanese markets.","metaTitle":"Schneider Electric EZC400N3300 EasyPact EZC400N, 400 A, 3P,","metaDescription":"Schneider Electric EZC400N3300 EasyPact EZC400N circuit breaker, 400 A rated at 40 °C, 3-pole, 36 kA Icu at 440 V AC. TM-D thermal-magnetic trip. Current lifecycle stage. Quoted to","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":[],"specifications":{"Color":"Black","Depth":"140 mm","Width":"185 mm","Height":"255 mm","Voltage":"440 V AC 50/60 Hz conforming to IEC 60947-2","IP Rating":"IP20","Application":"Distribution","Control Type":"Toggle","Product Status":"Active","Terminal Pitch":"44 mm","Trip Unit Type":"Thermal-magnetic","Pollution Degree":"3 conforming to IEC 60947","Temp Storage Max":"85 °C","Temp Storage Min":"-35 °C","Breaking Capacity":"36 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 40 kA Icu at 220/230 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2","Insulation Voltage Ui":"690 V AC 50/60 Hz conforming to IEC 60947-2","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-35...85 °C","Connection Surface Top":"Front","Electrical Life Cycles":"Category A: 4000 cycles 415 V AC 50/60 Hz conforming to IEC 60947-2","Mechanical Life Cycles":"10000 cycles","Connection Surface Bottom":"Front","Main Product Or Component Type":"Circuit breaker","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/8bef46621fa9352be4b14d8b592dc84f.pdf","sourceUrl":"https://www.se.com/ae/en/product/EZC400N3300/circuit-breaker-easypact-ezc400n-tmd-300-a-3-poles-3d/","alternativesUrl":"https://aoctrl.com/api/mcp/products/EZC400N3300/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/EZC400N3300","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/EZC400N3300 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}