{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"EZC400N44400N","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"EZC400N44400N","canonicalUrl":"https://aoctrl.com/schneider/EZC400N44400N","factsUrl":"https://aoctrl.com/api/mcp/products/EZC400N44400N","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact EZC400N series, EZC400N44400N, 4-pole molded-case circuit breaker, 400 A thermal-magnetic TM-D trip unit, 36 kA Icu at 440 V AC, fixed mount, IP20.","salesMarkdown":"The 36 kA Icu at 440 V AC (IEC 60947-2) is the N-frame breaking capacity — enough for most distribution panels downstream of a transformer, but not for high-fault industrial mains. At 220/230 V it handles 40 kA Icu, so it's comfortable on 208Y/120 V or 240 V services too. The TM-D trip is a fixed thermal-magnetic curve — no interchangeable trip blocks, no electronic adjustment. The magnetic pickup is fixed at 4000 A (10× In), so it's a standard distribution curve, not a motor-protection or selective-coordination curve. For distribution feeders and general branch protection, that's fine. For motor circuits you'd want a Mag-Gard or electronic trip. ## Where it goes — panel and deployment context Fixed-mount, backplate-mounted breaker with front-front connections — line and load both terminate on the front face. The 45 mm pole pitch matches standard EasyPact busbar and accessory spacing. IK07 impact resistance handles incidental tool drops during maintenance. The toggle control and positive contact indication give a clear visual of breaker state — no ambiguity on whether it's tripped or off. ## Standards and compliance — what the approvals mean Listed to IEC 60947-2, EN 60947-2, GB/T 14048.2, and JIS C8201-2-2. The IEC 60947-2 standard covers low-voltage switchgear and controlgear for circuit breakers — it's the global benchmark for MCCB performance, thermal and magnetic calibration, and breaking capacity verification. The GB/T and JIS variants mean it's accepted in Chinese and Japanese markets without additional testing. No earth-leakage protection built in; if you need RCD functionality, you add a Vigicompact module or an external RCCB.","metaTitle":"EZC400N44400N Schneider EasyPact EZC400N 400A 4P MCCB, 36kA","metaDescription":"Schneider Electric EasyPact EZC400N44400N 400A 4-pole MCCB, 36 kA Icu at 440 V AC. Thermal-magnetic TM-D trip unit. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":[],"specifications":{"Color":"Black","Depth":"140 mm","Width":"140 mm","Height":"255 mm","Voltage":"440 V AC 50/60 Hz conforming to IEC 60947-2","IP Rating":"IP20","Application":"Distribution","Control Type":"Toggle","Product Status":"Active","Terminal Pitch":"45 mm","Trip Unit Type":"Thermal-magnetic","Pollution Degree":"3 conforming to IEC 60947","Temp Storage Max":"85 °C","Temp Storage Min":"-35 °C","Breaking Capacity":"36 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 40 kA Icu at 220/230 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2","Insulation Voltage Ui":"690 V AC 50/60 Hz conforming to IEC 60947-2","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-35...85 °C","Connection Surface Top":"Front","Electrical Life Cycles":"Category A: 4000 cycles 415 V AC 50/60 Hz conforming to IEC 60947-2","Mechanical Life Cycles":"10000 cycles","Connection Surface Bottom":"Front","Main Product Or Component Type":"Circuit breaker","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/40767bb4a3be74cd474a8cc38ad0fce5.pdf","sourceUrl":"https://www.se.com/vn/en/product/EZC400N44400N/circuit-breaker-easypact-ezc400n-tmd-400-a-4-poles-4d/","alternativesUrl":"https://aoctrl.com/api/mcp/products/EZC400N44400N/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/EZC400N44400N","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/EZC400N44400N when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}