{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"EZC630H44500N","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"EZC630H44500N","canonicalUrl":"https://aoctrl.com/schneider/EZC630H44500N","factsUrl":"https://aoctrl.com/api/mcp/products/EZC630H44500N","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact EZC630H, EZC630H44500N, 4-pole MCCB, 630 A rated current at 40 °C, 50 kA Icu at 380 V AC, thermal-magnetic TM-D trip unit, IP20, fixed mount.","salesMarkdown":"The 50 kA Icu at 380 V AC (50/60 Hz) is the interrupting capacity at that voltage — it safely clears a fault up to that level without damage, per IEC 60947-2. At 440 V AC the same 50 kA holds; at 220/230 V AC it rises to 70 kA. That H breaking-capacity code means it handles high prospective fault currents common in distribution switchboards, so you can use it downstream of a transformer without cascading upstream breakers. The trip unit is rated 500 A at 50 °C — note the derating from the 630 A at 40 °C base. The magnetic trip threshold is fixed at 3500 A (about 5.6× In), which is typical for thermal-magnetic MCCBs protecting distribution feeders against short-circuits while allowing motor inrush. Fixed-mount backplate installation, front-front connections (line and load both front-accessible). Dimensions: 255 mm high, 185 mm wide, 140 mm deep. The 44 mm pole pitch matches standard busbar spacing for 4-pole breakers. IP20 finger-safe terminals; IK07 impact resistance for panel mounting.","metaTitle":"Schneider EasyPact EZC630H44500N MCCB, 630 A, 50 kA, 4P","metaDescription":"Schneider Electric EasyPact EZC630H44500N MCCB, 630 A rated current at 40 °C, 50 kA Icu at 380 V AC, 4 poles, thermal-magnetic TM-D trip unit. Current production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":[],"specifications":{"Color":"Black","Depth":"140 mm","Width":"185 mm","Height":"255 mm","Voltage":"440 V AC 50/60 Hz conforming to IEC 60947-2","IP Rating":"IP20","Application":"Distribution","Control Type":"Toggle","Product Status":"Active","Terminal Pitch":"44 mm","Trip Unit Type":"Thermal-magnetic","Pollution Degree":"3 conforming to IEC 60947","Temp Storage Max":"85 °C","Temp Storage Min":"-35 °C","Insulation Voltage Ui":"690 V AC 50/60 Hz conforming to IEC 60947-2","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-35...85 °C","Connection Surface Top":"Front","Electrical Life Cycles":"Category A: 3000 cycles 415 V AC 50/60 Hz conforming to IEC 60947-2","Mechanical Life Cycles":"10000 cycles","Connection Surface Bottom":"Front","Main Product Or Component Type":"Circuit breaker","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/959e0ef5eade245fe545b2a94349bc3e.pdf","sourceUrl":"https://www.se.com/ae/en/product/EZC630H44500N/circuit-breaker-easypact-ezc630h-tmd-500-a-4-poles-4d/","alternativesUrl":"https://aoctrl.com/api/mcp/products/EZC630H44500N/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/EZC630H44500N","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/EZC630H44500N when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}