{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"EZC630N3600N","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"EZC630N3600N","canonicalUrl":"https://aoctrl.com/schneider/EZC630N3600N","factsUrl":"https://aoctrl.com/api/mcp/products/EZC630N3600N","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact EZC630N, circuit breaker, 630 A at 40 °C, 36 kA Icu at 440 V AC, thermal-magnetic TM-D trip unit, 3 poles, IP20.","salesMarkdown":"## 630 A thermal-magnetic breaker, 36 kA at 440 V — panel fit and protection The Schneider Electric EZC630N3600N is a 3-pole EasyPact EZC630N circuit breaker rated 630 A at 40 °C with a thermal-magnetic TM-D trip unit. Its 36 kA Icu at 440 V AC (50/60 Hz) per IEC 60947-2 means it can safely interrupt faults up to that level without cascading upstream — a key number for the site electrical engineer checking SCCR headroom and selectivity coordination. Mounts fixed to a backplate (not DIN rail), with front-front connections and a 45 mm pole pitch. The IP20 enclosure and IK07 impact rating suit it for enclosed panel installation where personnel access is controlled. ## Trip unit and protection characteristics The TM-D thermal-magnetic trip unit provides overload and short-circuit protection. Magnetic tripping current is 5000 A. Mechanical durability is 10000 cycles; electrical durability is 3000 cycles at 415 V AC. No earth-leakage or neutral protection built in.","metaTitle":"Schneider Electric EZC630N3600N EasyPact EZC630N, 630 A, 36","metaDescription":"Schneider Electric EasyPact EZC630N circuit breaker, 630 A at 40 °C, 36 kA Icu at 440 V AC, thermal-magnetic TM-D trip unit, 3P, IP20. Current lifecycle. Sourced to order against R","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Color":"Black","Depth":"110 mm","Width":"140 mm","Height":"255 mm","Voltage":"440 V AC 50/60 Hz conforming to IEC 60947-2","IP Rating":"IP20","Application":"Distribution","Control Type":"Toggle","Product Status":"Active","Terminal Pitch":"45 mm","Trip Unit Type":"Thermal-magnetic","Pollution Degree":"3 conforming to IEC 60947","Temp Storage Max":"85 °C","Temp Storage Min":"-35 °C","Insulation Voltage Ui":"690 V AC 50/60 Hz conforming to IEC 60947-2","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-35...85 °C","Connection Surface Top":"Front","Electrical Life Cycles":"Category A: 3000 cycles 415 V AC 50/60 Hz conforming to IEC 60947-2","Mechanical Life Cycles":"10000 cycles","Connection Surface Bottom":"Front","Main Product Or Component Type":"Circuit breaker","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$495.47","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/0ffa29b647e089fc2c2e96538b0b6f6e.pdf","sourceUrl":"https://www.se.com/vn/en/product/EZC630N3600N/circuit-breakereasypact-ezc630n-tmd-600a-3-poles-3d/","alternativesUrl":"https://aoctrl.com/api/mcp/products/EZC630N3600N/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/EZC630N3600N","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/EZC630N3600N when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}