{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"EZC630N3600N","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"EZC630N3600N","canonicalUrl":"https://aoctrl.com/schneider/EZC630N3600N","factsUrl":"https://aoctrl.com/api/mcp/products/EZC630N3600N","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact EZC630N, circuit breaker, 630 A at 40 °C, 36 kA Icu at 440 V AC, thermal-magnetic TM-D trip unit, 3 poles, IP20.","salesMarkdown":"## 630 A thermal-magnetic breaker, 36 kA at 440 V — panel fit and protection The Schneider Electric EZC630N3600N is a 3-pole EasyPact EZC630N circuit breaker rated 630 A at 40 °C with a thermal-magnetic TM-D trip unit. Its 36 kA Icu at 440 V AC (50/60 Hz) per IEC 60947-2 means it can safely interrupt faults up to that level without cascading upstream — a key number for the site electrical engineer checking SCCR headroom and selectivity coordination. Mounts fixed to a backplate (not DIN rail), with front-front connections and a 45 mm pole pitch. The IP20 enclosure and IK07 impact rating suit it for enclosed panel installation where personnel access is controlled. ## Trip unit and protection characteristics The TM-D thermal-magnetic trip unit provides overload and short-circuit protection. Magnetic tripping current is 5000 A. Mechanical durability is 10000 cycles; electrical durability is 3000 cycles at 415 V AC. No earth-leakage or neutral protection built in.","metaTitle":"Schneider Electric EZC630N3600N EasyPact EZC630N, 630 A, 36","metaDescription":"Schneider Electric EasyPact EZC630N circuit breaker, 630 A at 40 °C, 36 kA Icu at 440 V AC, thermal-magnetic TM-D trip unit, 3P, IP20. Current lifecycle. Sourced to order against R","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Circuit Breaker Accessories"],"specifications":{"Depth":"110 mm","Width":"140 mm","title":"EZC630N3600N","Colour":"Black","Height":"255 mm","Standards":"EN/IEC 60947-2 GB/T 14048.2 JIS C8201-2-2 EN/IEC 60947-1","description":"circuit breaker,Easypact EZC630N,TMD, 600A,3 poles 3d","Control type":"Toggle","Network type":"AC","Mounting mode":"Fixed","Trip unit name":"TM-D","Protection type":"Overload protection Short-circuit protection","lifecycle_stage":"current","Connection pitch":"45 mm","Local signalling":"Positive contact indication","Mounting support":"Backplate","Pollution degree":"3 conforming to IEC 60947","Quantity per set":"1 piece","Range of product":"EasyPact","Trip unit rating":"600 A at 50 °C","Breaking capacity":"36 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 40 kA Icu at 220/230 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"Easypact EZC630N","Network frequency":"50/60 Hz","Poles description":"3P","Upside connection":"Front","Device application":"Distribution","[In] rated current":"630 A at 40 °C","Downside connection":"Front","Circuit breaker name":"Easypact EZC630N","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A","Electrical durability":"Category A: 3000 cycles 415 V AC 50/60 Hz conforming to IEC 60947-2","Mechanical durability":"10000 cycles","Breaking capacity code":"N","IK degree of protection":"IK07 conforming to EN 50102","IP degree of protection":"IP20 conforming to IEC 60529","Earth-leakage protection":"Without","Magnetic tripping current":"5000 A","Product or component type":"Circuit breaker","Suitability for isolation":"Yes conforming to IEC 60947-2","Contact position indicator":"Yes","Neutral protection setting":"Without protection","Protected poles description":"3t","[Ui] rated insulation voltage":"690 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"440 V AC 50/60 Hz conforming to IEC 60947-2","Long time delay adjustment type":"Fixed","Ambient air temperature for storage":"-35...85 °C","Long time pick-up adjustment type Ir":"Fixed","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"18 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 40 kA at 220/230 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 380 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$495.47","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/0ffa29b647e089fc2c2e96538b0b6f6e.pdf","sourceUrl":"https://www.se.com/vn/en/product/EZC630N3600N/circuit-breakereasypact-ezc630n-tmd-600a-3-poles-3d/"},"ai":{"faq":[{"question":"What are the key ratings of EZC630N3600N?","answer":"Rated 630 A at 40 °C, breaking capacity 36 kA Icu at 440 V AC, thermal-magnetic TM-D trip, 3 poles, IP20."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/EZC630N3600N","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/EZC630N3600N when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}