{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"EZC630N4400N","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"EZC630N4400N","canonicalUrl":"https://aoctrl.com/schneider/EZC630N4400N","factsUrl":"https://aoctrl.com/api/mcp/products/EZC630N4400N","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact EZC630N, EZC630N4400N, 4-pole circuit breaker, 630 A at 40 °C, 36 kA Icu at 440 V AC, thermal-magnetic TM-D trip unit, fixed mounting, IP20.","salesMarkdown":"The Schneider Electric EZC630N4400N is a 4-pole EasyPact EZC630N circuit breaker rated 630 A at 40 °C with a TM-D thermal-magnetic trip unit. It is marked Category A, meaning it is not intended for selective coordination with other breakers in series — plan for full discrimination upstream if needed. ## Deployment context This breaker mounts fixed to a backplate with front-front connections — no DIN-rail clip, so panel layout needs dedicated mounting holes and busbar takeoffs. The 185 mm width and 255 mm height determine the cutout and enclosure fill factor. IP20 means finger-safe but not washdown; install inside a locked panel. IK07 gives basic impact resistance for the enclosure face. Designed and tested to EN/IEC 60947-2 (circuit-breaker standard), EN/IEC 60947-1 (general rules), JIS C8201-2-2, and GB/T 14048.2.","metaTitle":"Schneider Electric EZC630N4400N EasyPact EZC630N, 630 A, 36","metaDescription":"Schneider Electric EZC630N4400N EasyPact EZC630N circuit breaker, 630 A rated at 40 °C, 36 kA breaking capacity at 440 V AC, 4 poles, thermal-magnetic TM-D trip unit. Current lifec","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":[],"specifications":{"Color":"Black","Depth":"140 mm","Width":"185 mm","Height":"255 mm","Voltage":"440 V AC 50/60 Hz conforming to IEC 60947-2","IP Rating":"IP20","Application":"Distribution","Control Type":"Toggle","Product Status":"Active","Terminal Pitch":"44 mm","Trip Unit Type":"Thermal-magnetic","Pollution Degree":"3 conforming to IEC 60947","Temp Storage Max":"85 °C","Temp Storage Min":"-35 °C","Breaking Capacity":"36 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 40 kA Icu at 220/230 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2","Insulation Voltage Ui":"690 V AC 50/60 Hz conforming to IEC 60947-2","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-35...85 °C","Connection Surface Top":"Front","Electrical Life Cycles":"Category A: 3000 cycles 415 V AC 50/60 Hz conforming to IEC 60947-2","Mechanical Life Cycles":"10000 cycles","Connection Surface Bottom":"Front","Main Product Or Component Type":"Circuit breaker","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/0f031463e992fd267d1c205da3558afd.pdf","sourceUrl":"https://www.se.com/vn/en/product/EZC630N4400N/circuit-breaker-easypact-ezc630n-tmd-400a-4-poles-3d/","alternativesUrl":"https://aoctrl.com/api/mcp/products/EZC630N4400N/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/EZC630N4400N","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/EZC630N4400N when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}