{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"EZC630N44400N","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"EZC630N44400N","canonicalUrl":"https://aoctrl.com/schneider/EZC630N44400N","factsUrl":"https://aoctrl.com/api/mcp/products/EZC630N44400N","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact EZC630N, molded case circuit breaker, 630 A at 40 °C, 4 poles, TM-D thermal-magnetic trip unit, 36 kA Icu at 440 V AC, IP20, fixed mount.","salesMarkdown":"The TM-D thermal-magnetic trip unit handles overloads (thermal) and short-circuits (magnetic) in one block, with a fixed magnetic trip threshold of 4000 A. That magnetic setting means the breaker holds through motor inrush and transformer energization up to roughly 6.3× In, then clears hard faults above that point. Breaking capacity is 36 kA Icu at 440 V AC 50/60 Hz per IEC 60947-2, and 40 kA Icu at 220/230 V AC. The N breaking capacity code places it in the standard-interrupting range for the EZC family, adequate for most secondary distribution panels not directly on the utility transformer secondary. Fixed-mount design with backplate mounting support — no DIN-rail adapter on this frame size. The 140 mm width and 255 mm height fit standard panel cutouts for a 630 A frame MCCB. Connection pitch is 45 mm, matching common busbar drilling patterns for this ampacity class. IP20 finger protection on the front face is standard; the IK07 impact rating means the enclosure withstands a 2 J hammer blow — enough for accidental tool contact during panel work. Mechanical durability is rated at 10,000 cycles; electrical durability at 3,000 cycles under 415 V AC Category A load per IEC 60947-2. Category A means the breaker is not intended for frequent switching of motor loads — it is a distribution breaker, not a contactor replacement. For applications requiring frequent on-load switching, a contactor in series with this MCCB is the standard topology. The suitability-for-isolation marking (yes, per IEC 60947-2) means the breaker can serve as a visible-break disconnect for lockout/tagout procedures, provided the positive contact indication is verified.","metaTitle":"Schneider Electric EZC630N44400N EasyPact Circuit Breaker, 6","metaDescription":"Schneider Electric EZC630N44400N EasyPact EZC630N molded case circuit breaker, 630 A rated current at 40 °C, 36 kA Icu at 440 V AC, 4P, TM-D thermal-magnetic trip unit, IP20. Curre","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":[],"specifications":{"Color":"Black","Depth":"140 mm","Width":"140 mm","Height":"255 mm","Voltage":"440 V AC 50/60 Hz conforming to IEC 60947-2","IP Rating":"IP20","Application":"Distribution","Control Type":"Toggle","Product Status":"Active","Terminal Pitch":"45 mm","Trip Unit Type":"Thermal-magnetic","Pollution Degree":"3 conforming to IEC 60947","Temp Storage Max":"85 °C","Temp Storage Min":"-35 °C","Breaking Capacity":"36 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 40 kA Icu at 220/230 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2","Insulation Voltage Ui":"690 V AC 50/60 Hz conforming to IEC 60947-2","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-35...85 °C","Connection Surface Top":"Front","Electrical Life Cycles":"Category A: 3000 cycles 415 V AC 50/60 Hz conforming to IEC 60947-2","Mechanical Life Cycles":"10000 cycles","Connection Surface Bottom":"Front","Main Product Or Component Type":"Circuit breaker","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/4e0c05894c0b054f9f09ea38a99658b8.pdf","sourceUrl":"https://www.se.com/ae/en/product/EZC630N44400N/circuit-breaker-easypact-ezc630n-tmd-400-a-4-poles-4d/","alternativesUrl":"https://aoctrl.com/api/mcp/products/EZC630N44400N/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/EZC630N44400N","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/EZC630N44400N when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}