{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"EZC630N44500N","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"EZC630N44500N","canonicalUrl":"https://aoctrl.com/schneider/EZC630N44500N","factsUrl":"https://aoctrl.com/api/mcp/products/EZC630N44500N","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact EZC630N, 630A thermal-magnetic MCCB, 4 poles, 36 kA Icu at 440 V AC, TM-D trip unit, fixed mount, IP20.","salesMarkdown":"The Schneider Electric EasyPact EZC630N44500N is a 4-pole molded-case circuit breaker (MCCB) rated 630 A at 40 °C, built for distribution applications in commercial and industrial panels. It carries a TM-D thermal-magnetic trip unit — thermal for overload protection, magnetic for short-circuit — with a magnetic tripping threshold of 5000 A. The 36 kA Icu at 440 V AC (50/60 Hz) per IEC 60947-2 tells you it can safely interrupt a fault up to that level without welding contacts or cascading upstream. That's the number that governs selectivity coordination with downstream breakers. Fixed backplate mount, front-front connections (line and load both front-accessible). The 140 mm width and 255 mm height mean it occupies a standard MCCB footprint on a backplate or inside a distribution cabinet. Connection pitch is 45 mm — lines up with common busbar systems. IP20 finger-safe terminals per IEC 60529; IK07 impact rating per EN 50102 means the enclosure shrugs off a 2 J hammer blow during installation.","metaTitle":"Schneider Electric EasyPact EZC630N44500N 630A 4P MCCB, 36kA","metaDescription":"Schneider Electric EasyPact EZC630N44500N circuit breaker, 630A rated at 40°C, 4 poles, TM-D trip unit, 36 kA Icu at 440 V AC. IEC 60947-2. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":[],"specifications":{"Color":"Black","Depth":"140 mm","Width":"140 mm","Height":"255 mm","Voltage":"440 V AC 50/60 Hz conforming to IEC 60947-2","IP Rating":"IP20","Application":"Distribution","Control Type":"Toggle","Product Status":"Active","Terminal Pitch":"45 mm","Trip Unit Type":"Thermal-magnetic","Pollution Degree":"3 conforming to IEC 60947","Temp Storage Max":"85 °C","Temp Storage Min":"-35 °C","Breaking Capacity":"36 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 40 kA Icu at 220/230 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2","Insulation Voltage Ui":"690 V AC 50/60 Hz conforming to IEC 60947-2","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-35...85 °C","Connection Surface Top":"Front","Electrical Life Cycles":"Category A: 3000 cycles 415 V AC 50/60 Hz conforming to IEC 60947-2","Mechanical Life Cycles":"10000 cycles","Connection Surface Bottom":"Front","Main Product Or Component Type":"Circuit breaker","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/51c91f1b0b45e066f6ae83b03f4dbb25.pdf","sourceUrl":"https://www.se.com/vn/en/product/EZC630N44500N/circuit-breaker-easypact-ezc630n-tmd-500-a-4-poles-4d/","alternativesUrl":"https://aoctrl.com/api/mcp/products/EZC630N44500N/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/EZC630N44500N","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/EZC630N44500N when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}