{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"EZC630N44600N","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"EZC630N44600N","canonicalUrl":"https://aoctrl.com/schneider/EZC630N44600N","factsUrl":"https://aoctrl.com/api/mcp/products/EZC630N44600N","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact EZC630N, molded case circuit breaker, 630 A, 4P, TM-D thermal-magnetic trip unit, 36 kA Icu at 440 V AC.","salesMarkdown":"The Schneider Electric EZC630N44600N is a 4-pole EasyPact EZC630N molded case circuit breaker rated 630 A at 40 °C, with a TM-D thermal-magnetic trip unit. Its 36 kA Icu at 440 V AC (50/60 Hz) per IEC 60947-2 means it can safely interrupt fault currents up to that level on a 400 V distribution bus without upstream coordination failure — the spec that decides whether this breaker clears a bolted fault or lets it cascade. The N breaking capacity code positions it for commercial and light industrial distribution panels, not heavy industrial high-fault locations. Magnetic tripping current is 5000 A, so the instantaneous trip threshold is set at roughly 8× In — typical for thermal-magnetic MCCBs protecting distribution feeders against bolted faults while riding through motor inrush. The 36 kA Icu at 440 V AC is the maximum interrupting rating; at 400/415 V it holds at 36 kA, and at 220/230 V it rises to 40 kA. Electrical durability is 3000 cycles at 415 V AC in Category A (non-frequent switching). Mechanical durability is 10,000 cycles. For a distribution MCCB that sees occasional switching, this is adequate; for frequent load-break duty, a contactor should handle the switching cycles. If selectivity is required, a Category B breaker (with intentional delay) is needed upstream. Fixed mounting on a backplate, with front-front connections (line and load both front-accessible). Dimensions are 255 mm high × 140 mm wide × 140 mm deep. IP20 finger-safe protection on the front cover; IK07 impact resistance.","metaTitle":"Schneider Electric EZC630N44600N EasyPact EZC630N, 630 A, 36","metaDescription":"Schneider Electric EasyPact EZC630N44600N molded case circuit breaker, 630 A rated current, 36 kA breaking capacity at 440 V AC, 4P, TM-D trip unit. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":[],"specifications":{"Color":"Black","Depth":"140 mm","Width":"140 mm","Height":"255 mm","Voltage":"440 V AC 50/60 Hz conforming to IEC 60947-2","IP Rating":"IP20","Application":"Distribution","Control Type":"Toggle","Product Status":"Active","Terminal Pitch":"45 mm","Trip Unit Type":"Thermal-magnetic","Pollution Degree":"3 conforming to IEC 60947","Temp Storage Max":"85 °C","Temp Storage Min":"-35 °C","Breaking Capacity":"36 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 40 kA Icu at 220/230 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2","Insulation Voltage Ui":"690 V AC 50/60 Hz conforming to IEC 60947-2","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-35...85 °C","Connection Surface Top":"Front","Electrical Life Cycles":"Category A: 3000 cycles 415 V AC 50/60 Hz conforming to IEC 60947-2","Mechanical Life Cycles":"10000 cycles","Connection Surface Bottom":"Front","Main Product Or Component Type":"Circuit breaker","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/e44d9e6c04b78939e69f89705e1aaf28.pdf","sourceUrl":"https://www.se.com/ae/en/product/EZC630N44600N/circuit-breaker-easypact-ezc630n-tmd-600-a-4-poles-4d/","alternativesUrl":"https://aoctrl.com/api/mcp/products/EZC630N44600N/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/EZC630N44600N","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/EZC630N44600N when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}