{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"EZCV250H3080","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"EZCV250H3080","canonicalUrl":"https://aoctrl.com/schneider/EZCV250H3080","factsUrl":"https://aoctrl.com/api/mcp/products/EZCV250H3080","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact EZCV250H, 80 A, 3-pole, thermal-magnetic MCCB, 100 kA Icu at 240 V AC, TM-D trip unit, IP20, IEC 60947-2.","salesMarkdown":"## What this 80 A MCCB delivers for a distribution panel The Schneider Electric EZCV250H3080 is a 3-pole EasyPact EZCV250H moulded-case circuit breaker with a TM-D thermal-magnetic trip unit rated 80 A at 40 °C. At 380–415 V AC the breaking capacity is 36 kA Icu, and at 440 V AC it's 25 kA Icu, so the voltage at the point of installation governs the rating you design to. Fixed-mount, backplate installation. The 105 mm width and 165 mm height fit standard EasyPact cutout patterns; depth is 68 mm. Connection pitch is 35 mm, and both line and load connections are front-accessible — no need to reach behind the panel. IP20 finger-safe terminals keep live parts covered during commissioning.","metaTitle":"Schneider Electric EZCV250H3080 EasyPact MCCB, 80 A, 100 kA,","metaDescription":"Schneider Electric EZCV250H3080 EasyPact EZCV250H circuit breaker, 80 A thermal-magnetic trip, 100 kA breaking capacity at 240 V AC. IEC 60947-2. Sourced to order against an RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"68 mm","Width":"105 mm","Height":"165 mm","Standards":"EN/IEC 60947-2 JIS C8201-2-2 GB/T 14048.2 EN/IEC 60947-1","Control type":"Toggle","Network type":"AC","Mounting mode":"Fixed","Trip unit name":"TM-D","Protection type":"Short-circuit protection Earth-leakage protection Overload protection","lifecycle_stage":"current","Connection pitch":"35 mm","Local signalling":"Positive contact indication","Mounting support":"Backplate","Pollution degree":"3 conforming to IEC 60947","Range of product":"EasyPact","Trip unit rating":"80 A at 40 °C","Breaking capacity":"100 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"Easypact EZCV250H","Network frequency":"50/60 Hz","Poles description":"3P","Upside connection":"Front","Device application":"Distribution","[In] rated current":"80 A at 40 °C","Downside connection":"Front","Circuit breaker name":"Easypact EZCV250H","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A","Mechanical durability":"10000 cycles","Breaking capacity code":"H","IK degree of protection":"IK07 conforming to EN 50102","IP degree of protection":"IP20 conforming to IEC 60529","Earth-leakage protection":"With","Product or component type":"Circuit breaker","Suitability for isolation":"Yes conforming to IEC 60947-2","Neutral protection setting":"Without protection","Protected poles description":"3t","[Ui] rated insulation voltage":"440 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"440 V AC 50/60 Hz conforming to IEC 60947-2","Ambient air temperature for storage":"-35...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"12.5 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 18 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/fd2a5f06d32503957bd80a4c9e320dc4.pdf","sourceUrl":"https://www.se.com/vn/en/product/EZCV250H3080/circuit-breaker-easypact-ezcv250h-tmd-80-a-3-poles-3d/","alternativesUrl":"https://aoctrl.com/api/mcp/products/EZCV250H3080/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of EZCV250H3080 at different voltages?","answer":"100 kA Icu at 220–240 V AC, 36 kA Icu at 380–415 V AC, and 25 kA Icu at 440 V AC, all per IEC 60947-2. The rating you design to depends on the actual line voltage at the installation point."},{"question":"What standards does EZCV250H3080 comply with?","answer":"EN/IEC 60947-2, JIS C8201-2-2, and GB/T 14048.2 — covering European, Japanese, and Chinese regulatory frameworks. It also carries an IK07 impact rating and IP20 finger-safe protection."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/EZCV250H3080","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/EZCV250H3080 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}