{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"EZCV250H3150","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"EZCV250H3150","canonicalUrl":"https://aoctrl.com/schneider/EZCV250H3150","factsUrl":"https://aoctrl.com/api/mcp/products/EZCV250H3150","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact EZCV250H series, EZCV250H3150, molded case circuit breaker, 3P, 150 A at 40 °C, TM-D trip unit, 100 kA Icu at 240 V AC, 36 kA at 415 V, 25 kA at 440 V, IP20, front-connected.","salesMarkdown":"The EZCV250H3150 is a 3-pole molded case circuit breaker from the Schneider Electric EasyPact EZCV250H family, rated 150 A at 40 °C with a thermal-magnetic TM-D trip unit. The TM-D trip unit combines a thermal element for overload protection and a magnetic element for short-circuit protection, plus integrated earth-leakage protection, so it covers ground faults in the same package without an external module. Breaking capacity is 100 kA Icu at 220–240 V AC, 36 kA at 380–415 V, and 25 kA at 440 V AC, all per IEC 60947-2. Verify available fault current against the 440 V rating if your system runs at that voltage. Standards compliance covers IEC 60947-2, EN/IEC 60947-1, JIS C8201-2-2, and GB/T 14048.2 — so it is accepted in European, Japanese, and Chinese installations. Fixed mounting on a backplate — not DIN-rail snap-on. The 105 mm width and 165 mm height fit standard MCCB panel cutouts; depth is 68 mm including the front-connected terminals. Connection pitch is 35 mm, matching typical busbar or cable-lug spacing for 150 A class breakers. IP20 finger protection on the front face; the enclosure itself is IK07 rated for impact resistance per EN 50102. Mechanical durability is 10,000 cycles — typical for a distribution MCCB not used for frequent switching. If your application requires daily load switching, consider a contactor in series; this breaker is designed for protection and infrequent manual operation via the toggle handle.","metaTitle":"Schneider Electric EZCV250H3150 EasyPact MCCB, 150 A, 3P, TM","metaDescription":"Schneider Electric EZCV250H3150 EasyPact EZCV250H molded case circuit breaker, 150 A at 40 °C, 3-pole, thermal-magnetic TM-D trip unit, 100 kA Icu at 240 V AC. Current lifecycle st","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"68 mm","Width":"105 mm","Height":"165 mm","Standards":"JIS C8201-2-2 EN/IEC 60947-2 EN/IEC 60947-1 GB/T 14048.2","Control type":"Toggle","Network type":"AC","Mounting mode":"Fixed","Trip unit name":"TM-D","Protection type":"Short-circuit protection Overload protection Earth-leakage protection","lifecycle_stage":"current","Connection pitch":"35 mm","Local signalling":"Positive contact indication","Mounting support":"Backplate","Pollution degree":"3 conforming to IEC 60947","Range of product":"EasyPact","Trip unit rating":"150 A at 40 °C","Breaking capacity":"100 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"Easypact EZCV250H","Network frequency":"50/60 Hz","Poles description":"3P","Upside connection":"Front","Device application":"Distribution","[In] rated current":"150 A at 40 °C","Downside connection":"Front","Circuit breaker name":"Easypact EZCV250H","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A","Mechanical durability":"10000 cycles","Breaking capacity code":"H","IK degree of protection":"IK07 conforming to EN 50102","IP degree of protection":"IP20 conforming to IEC 60529","Earth-leakage protection":"With","Product or component type":"Circuit breaker","Suitability for isolation":"Yes conforming to IEC 60947-2","Neutral protection setting":"Without protection","Protected poles description":"3t","[Ui] rated insulation voltage":"440 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"440 V AC 50/60 Hz conforming to IEC 60947-2","Ambient air temperature for storage":"-35...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"12.5 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 18 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/162a345e583b5e9b8b3bf47180546896.pdf","sourceUrl":"https://www.se.com/ph/en/product/EZCV250H3150/circuit-breaker-easypact-ezcv250h-tmd-150-a-3-poles-3d/","alternativesUrl":"https://aoctrl.com/api/mcp/products/EZCV250H3150/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of the EZCV250H3150 at different voltages?","answer":"100 kA Icu at 220–240 V AC, 36 kA at 380–415 V AC, and 25 kA at 440 V AC, all per IEC 60947-2. The 240 V rating is the highest; the 440 V figure is the one to check if your system runs at that voltage."},{"question":"Does the EZCV250H3150 include earth-leakage protection?","answer":"Yes, earth-leakage protection is integrated into the breaker — no external module or relay required. It covers ground faults in addition to the thermal-magnetic overload and short-circuit protection."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/EZCV250H3150","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/EZCV250H3150 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}