{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"EZCV250H44125","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"EZCV250H44125","canonicalUrl":"https://aoctrl.com/schneider/EZCV250H44125","factsUrl":"https://aoctrl.com/api/mcp/products/EZCV250H44125","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact EZCV250H series, molded case circuit breaker, 4-pole, 125 A at 40 °C, 100 kA Icu at 240 V AC, TM-D thermal-magnetic trip unit with earth-leakage protection.","salesMarkdown":"The Schneider Electric EZCV250H44125 is a 4-pole molded case circuit breaker from the EasyPact EZCV250H series, rated 125 A at 40 °C with a TM-D thermal-magnetic trip unit and integral earth-leakage protection. The H breaking capacity code tells you this is the high-end interrupt rating for the frame — not the standard or economy variant — so it handles high-fault scenarios without cascading upstream. At 440 V AC the Icu drops to 25 kA, so if your line side is a 440 V distribution transformer, that's your coordination ceiling. Earth-leakage protection is built in, so you don't need a separate RCCB downstream — one device covers overload, short-circuit, and ground fault. ## Where it goes in the panel Fixed mounting on a backplate, with front-facing connections top and bottom — no DIN-rail clip, so you bolt it to a mounting plate in the enclosure. The 35 mm connection pitch matches standard busbar systems and lug kits. IP20 finger-safe on the front, but the terminals need enclosure protection. IK07 impact rating handles tool drops during panel work.","metaTitle":"Schneider EasyPact EZCV250H44125 MCCB, 125 A, 100 kA","metaDescription":"Schneider EasyPact EZCV250H44125 MCCB, 125 A rated at 40 °C, 100 kA breaking capacity at 240 V, 4-pole, TM-D trip, earth-leakage protection. Active production, sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":[],"specifications":{"Depth":"68 mm","Width":"140 mm","Height":"165 mm","Voltage":"440 V AC 50/60 Hz conforming to IEC 60947-2","IP Rating":"IP20","Application":"Distribution","Control Type":"Toggle","Product Status":"Active","Terminal Pitch":"35 mm","Trip Unit Type":"Thermal-magnetic","Pollution Degree":"3 conforming to IEC 60947","Temp Storage Max":"85 °C","Temp Storage Min":"-35 °C","Insulation Voltage Ui":"440 V AC 50/60 Hz conforming to IEC 60947-2","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-35...85 °C","Connection Surface Top":"Front","Mechanical Life Cycles":"10000 cycles","Connection Surface Bottom":"Front","Main Product Or Component Type":"Circuit breaker","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/44d79488c1f7e0182a7c2feeb0e3d415.pdf","sourceUrl":"https://www.se.com/ae/en/product/EZCV250H44125/circuit-breaker-easypact-ezcv250h-tmd-125-a-4-poles-4d/","alternativesUrl":"https://aoctrl.com/api/mcp/products/EZCV250H44125/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/EZCV250H44125","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/EZCV250H44125 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}