{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"EZCV250N3250","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"EZCV250N3250","canonicalUrl":"https://aoctrl.com/schneider/EZCV250N3250","factsUrl":"https://aoctrl.com/api/mcp/products/EZCV250N3250","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact EZCV250N, 3-pole MCCB, 250 A at 40 °C, TM-D thermal-magnetic trip, 20 kA Icu at 440 V AC, with earth-leakage protection, IP20, backplate mount.","salesMarkdown":"The Schneider Electric EZCV250N3250 is a 3-pole moulded-case circuit breaker from the EasyPact EZCV250N range, rated 250 A at 40 °C and built for distribution duty in commercial and industrial panels. The 20 kA Icu at 440 V AC (IEC 60947-2) is the interrupting rating that governs its fault-clearing capability on a 400 V line; the 85 kA Icu at 240 V AC is higher but only relevant for lower-voltage taps. For a 380–415 V supply the rating is 25 kA Icu, which is the more common figure for European 400 V distribution boards. The TM-D trip unit is a fixed thermal-magnetic design — the thermal element responds to sustained overloads, the magnetic element to short-circuit peaks. Category A utilisation means it is not intended for motor starting under frequent switching; it is a distribution breaker for feeder and branch circuits. The 10,000-cycle mechanical durability is typical for a panel-mounted MCCB that sees occasional switching, not daily operation. Pollution degree 3 (IEC 60947) means it is rated for conductive pollution in an industrial enclosure — standard for a backplate-mounted breaker in a non-sealed panel. Mounts fixed to a backplate — no DIN-rail adapter. Front connections on both line and load sides, with a 35 mm connection pitch that matches standard busbar systems. Dimensions are 105 mm wide by 165 mm high by 68 mm deep, so it occupies a 3-pole MCCB footprint typical for 250 A frames. The toggle control and positive contact indication give a visual open/closed status without needing auxiliary contacts.","metaTitle":"Schneider Electric EZCV250N3250 EasyPact EZCV250N, 250A 3P M","metaDescription":"Schneider Electric EZCV250N3250 EasyPact EZCV250N MCCB. 250 A rated current, 20 kA breaking at 440 V AC, thermal-magnetic TM-D trip unit with earth-leakage protection. Current life","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"68 mm","Width":"105 mm","Height":"165 mm","Standards":"JIS C8201-2-2 EN/IEC 60947-1 EN/IEC 60947-2 GB/T 14048.2","Control type":"Toggle","Network type":"AC","Mounting mode":"Fixed","Trip unit name":"TM-D","Protection type":"Short-circuit protection Earth-leakage protection Overload protection","lifecycle_stage":"current","Connection pitch":"35 mm","Local signalling":"Positive contact indication","Mounting support":"Backplate","Pollution degree":"3 conforming to IEC 60947","Range of product":"EasyPact","Trip unit rating":"250 A at 40 °C","Breaking capacity":"20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"Easypact EZCV250N","Network frequency":"50/60 Hz","Poles description":"3P","Upside connection":"Front","Device application":"Distribution","[In] rated current":"250 A at 40 °C","Downside connection":"Front","Circuit breaker name":"Easypact EZCV250N","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A","Mechanical durability":"10000 cycles","Breaking capacity code":"N","IK degree of protection":"IK07 conforming to EN 50102","IP degree of protection":"IP20 conforming to IEC 60529","Earth-leakage protection":"With","Product or component type":"Circuit breaker","Suitability for isolation":"Yes conforming to IEC 60947-2","Neutral protection setting":"Without protection","Protected poles description":"3t","[Ui] rated insulation voltage":"440 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"440 V AC 50/60 Hz conforming to IEC 60947-2","Ambient air temperature for storage":"-35...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"10 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 42.5 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 12.5 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/a661c6b9e36c99adf158f56fd75197e0.pdf","sourceUrl":"https://www.se.com/vn/en/product/EZCV250N3250/circuit-breaker-easypact-ezcv250n-tmd-250a-3-poles-3d/","alternativesUrl":"https://aoctrl.com/api/mcp/products/EZCV250N3250/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for EZCV250N3250?","answer":"Submit an RFQ through this listing. The part is sourced through independent distribution and quoted to order; availability and current pricing are confirmed at quote time."},{"question":"What is the breaking capacity of EZCV250N3250 at 440 V?","answer":"The breaking capacity is 20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2. At 380–415 V it is 25 kA Icu, and at 220–240 V it is 85 kA Icu."},{"question":"What compliance documentation does this breaker carry?","answer":"It is certified to IEC 60947-2, EN 60947-2, GB/T 14048.2, and JIS C8201-2-2. It is suitable for isolation per IEC 60947-2 and carries IP20 and IK07 protection ratings."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/EZCV250N3250","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/EZCV250N3250 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}