{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"EZCV250N4080","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"EZCV250N4080","canonicalUrl":"https://aoctrl.com/schneider/EZCV250N4080","factsUrl":"https://aoctrl.com/api/mcp/products/EZCV250N4080","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact EZCV250N, EZCV250N4080, 4-pole molded case circuit breaker, 80 A thermal-magnetic trip unit, 20 kA Icu at 440 V AC, earth-leakage protection, IP20, backplate mount.","salesMarkdown":"The thermal-magnetic trip provides overload protection (thermal element) and short-circuit protection (magnetic element), plus integrated earth-leakage protection, all in one device. Breaking capacity is the critical figure for fault-withstand capability: 20 kA Icu at 440 V AC 50/60 Hz per IEC 60947-2. At 380–415 V AC the rating rises to 25 kA Icu, and at 220–240 V AC to 85 kA Icu — the higher the voltage, the harder it is to quench the arc, so the lower the interrupting rating. For selectivity (discrimination) you would need a Category B breaker with a short-time delay. The EZCV250N4080 is suited for distribution as a main or branch breaker where coordination is handled upstream or by a separate selectivity study. ## Deployment context Mounts fixed to a backplate (not DIN-rail) with front-connect terminals on both line and load sides. The 35 mm connection pitch matches standard busbar systems and panel-mounting patterns. IP20 finger-safe protection is sufficient for enclosed panel installation; the IK07 impact rating means the enclosure withstands a 2 J hammer blow — adequate for industrial cabinet environments where accidental tool strikes occur. It also complies with GB/T 14048.2 (Chinese national standard) and JIS C8201-2-2 (Japanese industrial standard). The suitability-for-isolation marking (IEC 60947-2) confirms it can be used as a disconnecting means with a visible open gap.","metaTitle":"Schneider Electric EZCV250N4080 EasyPact EZCV250N, 80 A, 20","metaDescription":"Schneider Electric EZCV250N4080 EasyPact EZCV250N circuit breaker, 80 A thermal-magnetic trip, 20 kA Icu at 440 V AC, 4P, earth-leakage protection. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":[],"specifications":{"Depth":"68 mm","Width":"140 mm","Height":"165 mm","Voltage":"440 V AC 50/60 Hz conforming to IEC 60947-2","IP Rating":"IP20","Application":"Distribution","Control Type":"Toggle","Product Status":"Active","Terminal Pitch":"35 mm","Trip Unit Type":"Thermal-magnetic","Pollution Degree":"3 conforming to IEC 60947","Temp Storage Max":"85 °C","Temp Storage Min":"-35 °C","Insulation Voltage Ui":"440 V AC 50/60 Hz conforming to IEC 60947-2","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-35...85 °C","Connection Surface Top":"Front","Mechanical Life Cycles":"10000 cycles","Connection Surface Bottom":"Front","Main Product Or Component Type":"Circuit breaker","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/e0176f93bf8157b095fa4217f999a1c9.pdf","sourceUrl":"https://www.se.com/ae/en/product/EZCV250N4080/circuit-breaker-easypact-ezcv250n-tmd-80-a-4-poles-4d/","alternativesUrl":"https://aoctrl.com/api/mcp/products/EZCV250N4080/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/EZCV250N4080","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/EZCV250N4080 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}