{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"EZCV250N4200","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"EZCV250N4200","canonicalUrl":"https://aoctrl.com/schneider/EZCV250N4200","factsUrl":"https://aoctrl.com/api/mcp/products/EZCV250N4200","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact EZCV250N, molded case circuit breaker, 200 A, 4 poles, 20 kA Icu at 440 V AC, thermal-magnetic TM-D trip unit with earth-leakage protection, front connections, IP20, backplate mount.","salesMarkdown":"The 200 A rating at 40 °C sets the continuous current capacity — sized for a main feeder or large subfeed on a 200 A bus. The TM-D thermal-magnetic trip unit combines overload protection (thermal element) with short-circuit protection (magnetic element); the earth-leakage protection adds a ground-fault trip, so it covers the three protection types listed in a single device. The breaking capacity is the key fault-handling number: 20 kA Icu at 440 V AC means it can safely interrupt a fault current up to 20,000 A at that voltage without failing — sufficient for most secondary distribution panels where the available fault current is under 20 kA. At 380–415 V the rating rises to 25 kA, and at 220–240 V to 85 kA, giving headroom on lower-voltage systems. The 440 V rated operational voltage and insulation voltage match standard 400 V class networks. Fixed mounting on a backplate — no DIN-rail adapter, so plan for bolt-down installation in the enclosure. Dimensions: 165 mm height, 140 mm width, 68 mm depth. IP20 finger-safe protection and IK07 impact resistance suit panel-mount indoor use; pollution degree 3 means it tolerates conductive pollution (condensation, light dust) typical in industrial switchgear. The toggle control provides local on/off and trip indication with positive contact indication — the handle position shows contact state even without power. Also compliant with JIS C8201-2-2 and GB/T 14048.2, so it carries acceptance in Japanese and Chinese markets. Category A indicates no intentional short-time delay; it trips instantaneously on fault, coordinating with downstream devices in a selective scheme only if their let-through energy is lower.","metaTitle":"Schneider EZCV250N4200 EasyPact EZCV250N, 200 A, 4P, 20 kA a","metaDescription":"Schneider Electric EasyPact EZCV250N4200 molded case circuit breaker, 200 A, 4 poles, 20 kA Icu at 440 V AC, thermal-magnetic TM-D trip unit with earth-leakage protection. Active l","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"68 mm","Width":"140 mm","Height":"165 mm","Standards":"EN/IEC 60947-1 JIS C8201-2-2 GB/T 14048.2 EN/IEC 60947-2","Control type":"Toggle","Network type":"AC","Mounting mode":"Fixed","Trip unit name":"TM-D","Protection type":"Overload protection Earth-leakage protection Short-circuit protection","lifecycle_stage":"current","Connection pitch":"35 mm","Local signalling":"Positive contact indication","Mounting support":"Backplate","Pollution degree":"3 conforming to IEC 60947","Range of product":"EasyPact","Trip unit rating":"200 A at 40 °C","Breaking capacity":"20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"Easypact EZCV250N","Network frequency":"50/60 Hz","Poles description":"4P","Upside connection":"Front","Device application":"Distribution","[In] rated current":"200 A at 40 °C","Downside connection":"Front","Circuit breaker name":"Easypact EZCV250N","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A","Mechanical durability":"10000 cycles","Breaking capacity code":"N","IK degree of protection":"IK07 conforming to EN 50102","IP degree of protection":"IP20 conforming to IEC 60529","Earth-leakage protection":"With","Product or component type":"Circuit breaker","Suitability for isolation":"Yes conforming to IEC 60947-2","Neutral protection setting":"Without protection","Protected poles description":"3t","[Ui] rated insulation voltage":"440 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"440 V AC 50/60 Hz conforming to IEC 60947-2","Ambient air temperature for storage":"-35...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"10 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 42.5 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 12.5 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/0fa7523bbafdfcc3f66251304927dac8.pdf","sourceUrl":"https://www.se.com/ae/en/product/EZCV250N4200/circuit-breaker-easypact-ezcv250n-tmd-200-a-4-poles-4d/","alternativesUrl":"https://aoctrl.com/api/mcp/products/EZCV250N4200/alternatives.json"},"ai":{"faq":[{"question":"What are the key specifications of EZCV250N4200?","answer":"Rated 200 A at 40 °C, 4 poles, breaking capacity 20 kA Icu at 440 V AC, thermal-magnetic TM-D trip unit with earth-leakage protection, front connections, backplate mount, IP20."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/EZCV250N4200","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/EZCV250N4200 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}