{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"EZCV250N44200","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"EZCV250N44200","canonicalUrl":"https://aoctrl.com/schneider/EZCV250N44200","factsUrl":"https://aoctrl.com/api/mcp/products/EZCV250N44200","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact EZCV250N, MCCB, 200 A, 4P, 20 kA Icu at 440 V AC, TM-D trip unit, earth-leakage protection.","salesMarkdown":"It carries a 20 kA Icu breaking capacity at 440 V AC (50/60 Hz) per IEC 60947-2, and 85 kA at 220–240 V AC. If your panel runs hotter — say 50 °C — you derate per the manufacturer's curve; the TM-D trip unit is thermal-magnetic, so the thermal element responds to ambient. The 4-pole configuration with all four poles protected (4t) means it switches and protects all phases and the neutral, common for three-phase distribution where the neutral is switched. Earth-leakage protection built in (no separate module needed) covers ground-fault detection on the load side. That's standard for a distribution MCCB in an unheated enclosure. The IP20 finger-safe terminals and IK07 impact resistance handle routine panel access without special guarding. Mounts fixed to a backplate — no DIN rail adapter on this frame. Front-front connections (line and load both front-accessed) simplify busbar routing in a distribution board. The 140 mm width and 165 mm height fit standard MCCB cutouts; the 68 mm depth leaves room for rear cable exit. Connection pitch is 35 mm, matching common busbar spacing.","metaTitle":"Schneider Electric EZCV250N44200 EasyPact EZCV250N, 200 A, 4","metaDescription":"Schneider Electric EZCV250N44200 EasyPact EZCV250N circuit breaker. 200 A, 4-pole, 20 kA Icu at 440 V AC. TM-D trip unit, earth-leakage protection. Current lifecycle stage. Sourced","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"68 mm","Width":"140 mm","Height":"165 mm","Standards":"GB/T 14048.2 EN/IEC 60947-2 JIS C8201-2-2 EN/IEC 60947-1","Control type":"Toggle","Network type":"AC","Mounting mode":"Fixed","Trip unit name":"TM-D","Protection type":"Short-circuit protection Earth-leakage protection Overload protection","lifecycle_stage":"current","Connection pitch":"35 mm","Local signalling":"Positive contact indication","Mounting support":"Backplate","Pollution degree":"3 conforming to IEC 60947","Range of product":"EasyPact","Trip unit rating":"200 A at 40 °C","Breaking capacity":"20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"Easypact EZCV250N","Network frequency":"50/60 Hz","Poles description":"4P","Upside connection":"Front","Device application":"Distribution","[In] rated current":"200 A at 40 °C","Downside connection":"Front","Circuit breaker name":"Easypact EZCV250N","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A","Mechanical durability":"10000 cycles","Breaking capacity code":"N","IK degree of protection":"IK07 conforming to EN 50102","IP degree of protection":"IP20 conforming to IEC 60529","Earth-leakage protection":"With","Product or component type":"Circuit breaker","Suitability for isolation":"Yes conforming to IEC 60947-2","Neutral protection setting":"Without protection","Protected poles description":"4t","[Ui] rated insulation voltage":"440 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"440 V AC 50/60 Hz conforming to IEC 60947-2","Ambient air temperature for storage":"-35...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"10 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 42.5 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 12.5 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/8268a91c44e9c4edddcb1e9a580d25a8.pdf","sourceUrl":"https://www.se.com/vn/en/product/EZCV250N44200/circuit-breaker-easypact-ezcv250n-tmd-200-a-4-poles-3d/","alternativesUrl":"https://aoctrl.com/api/mcp/products/EZCV250N44200/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings of the EZCV250N44200?","answer":"The EZCV250N44200 is a 200 A, 4-pole MCCB with a TM-D thermal-magnetic trip unit, 20 kA Icu at 440 V AC, and integral earth-leakage protection."},{"question":"What compliance standards does the EZCV250N44200 meet?","answer":"The breaker complies with GB/T 14048.2, EN/IEC 60947-2, and JIS C8201-2-2. It is suitable for isolation per IEC 60947-2 and carries IP20 and IK07 protection ratings."},{"question":"Where can I buy the EZCV250N44200?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/EZCV250N44200","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/EZCV250N44200 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}