{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"EZS100E3016","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"EZS100E3016","canonicalUrl":"https://aoctrl.com/schneider/EZS100E3016","factsUrl":"https://aoctrl.com/api/mcp/products/EZS100E3016","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact EZS, EZS100E3016, thermal-magnetic circuit breaker, 16 A, 3P, 50 kA Icu at 240 V AC, TM-D trip unit.","salesMarkdown":"The breaking capacity reaches 50 kA Icu at 220/240 V AC and 25 kA Icu at 380/400 V AC — figures that govern its use in high-fault-current panelboards where upstream coordination matters. The TM-D trip unit has a fixed thermal pickup at 1× In and a magnetic instantaneous threshold at 300 kA (integral instant protection), meaning magnetic trips only on very high faults, not on motor inrush. The 50 kA Icu at 240 V AC is the maximum short-circuit current the breaker can interrupt once and remain functional; at 415 V it drops to 25 kA, and at 440 V to 17 kA. Fixed backplate mounting, front connections both top and bottom. Pollution degree 3 (IEC 60947-1) means it tolerates conductive pollution in industrial enclosures — no special sealing needed inside a standard IP40 panel. The IP40 housing keeps out tools and fingers but not water; mount it in a dry cabinet or add an outer enclosure for washdown areas.","metaTitle":"Schneider Electric EZS100E3016 EasyPact EZS MCB, 16 A, 3P, 5","metaDescription":"Schneider Electric EZS100E3016 EasyPact EZS thermal-magnetic circuit breaker, 16 A, 3-pole, 50 kA Icu at 240 V AC. Sourced to order against RFQ. EN/IEC 60947-2.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":[],"specifications":{"Depth":"60 mm","Width":"75 mm","Height":"130 mm","Voltage":"440 V AC 50/60 Hz conforming to EN/IEC 60947-2 400 V AC 50/60 Hz conforming to GB 14048.2","IP Rating":"IP40","Control Type":"Toggle","Product Status":"Active","Terminal Pitch":"25 mm","Trip Unit Type":"Thermal-magnetic","Pollution Degree":"3 conforming to IEC 60947-1","Temp Storage Max":"85 °C","Temp Storage Min":"-50 °C","Breaking Capacity":"50 kA Icu at 220/240 V AC 50/60 Hz conforming to EN/IEC 60947-2 25 kA Icu at 380/400 V AC 50/60 Hz conforming to EN/IEC 60947-2 25 kA Icu at 415 V AC 50/60 Hz conforming to EN/IEC 60947-2 17 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 40 kA Icu at 200/230 V AC 50/60 Hz conforming to GB 14048.2 25 kA Icu at 380/400 V AC 50/60 Hz conforming to GB 14048.2","Insulation Voltage Ui":"690 V conforming to EN/IEC 60947-2","Temp Operating Max":"70 °C","Temp Operating Min":"-35 °C","Temperature Storage":"-50...85 °C","Connection Surface Top":"Front","Electrical Life Cycles":"4000 cycles 415 V In/2 conforming to EN/IEC 60947-2 8000 cycles 400 V In conforming to GB 14048.2","Mechanical Life Cycles":"13000 cycles conforming to EN/IEC 60947-2 20000 cycles conforming to GB 14048.2","Connection Surface Bottom":"Front","Main Product Or Component Type":"Circuit breaker","Ambient Air Temperature Operation":"-35...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/a6a311882912971145f9aee8f490e8a7.pdf","sourceUrl":"https://www.se.com/th/en/product/EZS100E3016/circuit-breaker-easypact-ezs100e-with-tmd-trip-unit-16a-3p-3d/","alternativesUrl":"https://aoctrl.com/api/mcp/products/EZS100E3016/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/EZS100E3016","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/EZS100E3016 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}