{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"EZS100E3032","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"EZS100E3032","canonicalUrl":"https://aoctrl.com/schneider/EZS100E3032","factsUrl":"https://aoctrl.com/api/mcp/products/EZS100E3032","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact EZS, circuit breaker, 3P, 32 A, TM-D trip, 50 kA Icu at 240 V AC, EN/IEC 60947-2.","salesMarkdown":"It's built for distribution duty — overload and short-circuit protection on AC networks — and carries a 50 kA Icu breaking capacity at 220/240 V AC (25 kA at 380/400 V). The 690 V rated insulation voltage and Category A utilisation class mean it's sized for panel feed or sub-feed protection, not motor starting. The 32 A TM-D trip is fixed — no field-adjustable long-time pickup. That's fine for a dedicated feeder; less flexible if you're trying to squeeze it onto a variable load. At 415 V it drops to 17 kA Icu. The IP40 enclosure and IK07 impact rating suit clean indoor panel mounting — no washdown, no outdoor exposure. Fixed backplate mount, 25 mm connection pitch, front-facing connections top and bottom. Neutral is on the left. Toggle control, so manual on/off and trip indication are visible through the IP40 cover.","metaTitle":"Schneider Electric EZS100E3032 EasyPact EZS, 32 A, 3P, 50 kA","metaDescription":"Schneider Electric EZS100E3032 EasyPact EZS circuit breaker, 32 A, 3P, 50 kA Icu at 240 V AC. EN/IEC 60947-2. Current production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":[],"specifications":{"Depth":"60 mm","Width":"75 mm","Height":"130 mm","Voltage":"440 V AC 50/60 Hz conforming to EN/IEC 60947-2 400 V AC 50/60 Hz conforming to GB 14048.2","IP Rating":"IP40","Control Type":"Toggle","Product Status":"Active","Terminal Pitch":"25 mm","Trip Unit Type":"Thermal-magnetic","Pollution Degree":"3 conforming to IEC 60947-1","Temp Storage Max":"85 °C","Temp Storage Min":"-50 °C","Insulation Voltage Ui":"690 V conforming to EN/IEC 60947-2","Temp Operating Max":"70 °C","Temp Operating Min":"-35 °C","Temperature Storage":"-50...85 °C","Connection Surface Top":"Front","Connection Surface Bottom":"Front","Main Product Or Component Type":"Circuit breaker","Ambient Air Temperature Operation":"-35...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/ec07f9614c6fbee6f120dd2ea23352bf.pdf","sourceUrl":"https://www.se.com/th/en/product/EZS100E3032/circuit-breaker-easypact-ezs100e-with-tmd-trip-unit-32a-3p-3d/","alternativesUrl":"https://aoctrl.com/api/mcp/products/EZS100E3032/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/EZS100E3032","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/EZS100E3032 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}