{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"EZS630N3500","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"EZS630N3500","canonicalUrl":"https://aoctrl.com/schneider/EZS630N3500","factsUrl":"https://aoctrl.com/api/mcp/products/EZS630N3500","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact EZS, circuit breaker, 3P, 500 A at 40 °C, TM-D thermal-magnetic trip unit, 70 kA Icu at 240 V AC, IEC 60947-2.","salesMarkdown":"At 400 V AC the breaking capacity is still 50 kA Icu, which covers most North American 480Y/277 V and European 400 V distribution panels. The TM-D trip unit provides fixed long-time pickup at 1 In (500 A) and a fixed magnetic instantaneous trip threshold, so there is no field-adjustable thermal or magnetic dial. That simplifies ordering — you get one setting — but means the breaker is not a candidate for systems needing coordination curve tuning. The 5000 kA integral instant protection rating is the maximum prospective short-circuit current the trip element can withstand, not the system SCCR; the system SCCR is governed by the Icu values at the actual system voltage. ## Deployment context Fixed backplate mounting with front-front connections (line and load both front-facing). The 45 mm pole pitch matches standard busbar and cable lug spacing for 500 A class breakers.","metaTitle":"Schneider Electric EZS630N3500 EasyPact EZS Circuit Breaker,","metaDescription":"Schneider Electric EZS630N3500 EasyPact EZS circuit breaker, 500 A rated current, 70 kA breaking capacity at 240 V, 3-pole, TM-D trip unit. IEC 60947-2. Sourced to order against RF","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":[],"specifications":{"Depth":"110 mm","Width":"182 mm","Height":"257 mm","Voltage":"440 V AC 50/60 Hz conforming to EN/IEC 60947-2 400 V AC 50/60 Hz conforming to GB 14048.2","IP Rating":"IP40","Control Type":"Toggle","Product Status":"Active","Terminal Pitch":"45 mm","Trip Unit Type":"Thermal-magnetic","Pollution Degree":"3 conforming to IEC 60947-1","Temp Storage Max":"85 °C","Temp Storage Min":"-50 °C","Breaking Capacity":"70 kA Icu at 220/240 V AC 50/60 Hz conforming to EN/IEC 60947-2 50 kA Icu at 380/400 V AC 50/60 Hz conforming to EN/IEC 60947-2 50 kA Icu at 415 V AC 50/60 Hz conforming to EN/IEC 60947-2 42 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 70 kA Icu at 220/230 V AC 50/60 Hz conforming to GB 14048.2 50 kA Icu at 440 V AC 50/60 Hz conforming to GB 14048.2","Insulation Voltage Ui":"690 V conforming to EN/IEC 60947-2","Temp Operating Max":"70 °C","Temp Operating Min":"-35 °C","Temperature Storage":"-50...85 °C","Connection Surface Top":"Front","Electrical Life Cycles":"8000 cycles 415 V In/2 conforming to EN/IEC 60947-2 8000 cycles 400 V In conforming to GB 14048.2","Mechanical Life Cycles":"15000 cycles conforming to EN/IEC 60947-2 10000 cycles conforming to GB 14048.2","Connection Surface Bottom":"Front","Main Product Or Component Type":"Circuit breaker","Ambient Air Temperature Operation":"-35...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/b0b3ad403bfeb0a3717d7d50da9a3459.pdf","sourceUrl":"https://www.se.com/th/en/product/EZS630N3500/circuit-breaker-easypact-ezs630n-with-tmd-trip-unit-500a-3p-3d/","alternativesUrl":"https://aoctrl.com/api/mcp/products/EZS630N3500/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/EZS630N3500","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/EZS630N3500 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}