{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"FRN0261G2W-4GU","brand":"Fuji Electric","brandSlug":"fuji-electric","productSlug":"FRN0261G2W-4GU","canonicalUrl":"https://aoctrl.com/fuji-electric/FRN0261G2W-4GU","factsUrl":"https://aoctrl.com/api/mcp/products/FRN0261G2W-4GU","rawCanonicalId":null},"summary":{"shortDescription":"Fuji Electric FRENIC-Eco series, FRN0261G2W-4GU, 200 hp variable frequency drive, 240 A output, 380-480 VAC three-phase input, NEMA 1 enclosure.","salesMarkdown":"## Drive specs for the line-down decision The Fuji FRN0261G2W-4GU is a 200 hp variable frequency drive from the FRENIC-Eco series, rated for 240 A continuous output on a 380-480 VAC three-phase supply. That 240 A is the number that governs the motor branch circuit — match it to the full-load amp rating of your 200 hp motor, not the nameplate horsepower alone. The drive accepts 380-480 VAC +10%/-15% and delivers 0-460 VAC output over a 0.1 to 120 Hz frequency range, so it covers 50/60 Hz line supplies and can overspeed a standard motor if the load allows. This is a variable-torque drive, meaning it's optimized for centrifugal loads like fans and pumps in HVAC applications. The starting torque is 50% at 1 Hz, which is typical for a variable-torque curve — enough to accelerate a fan wheel unloaded, but not for a high-breakaway conveyor or extruder. If your load requires constant torque across the speed range, this drive will need derating; the FRENIC-Eco series has a constant-torque sibling that would be the correct pick. ## I/O and control — what connects where The drive has 7 digital inputs, 3 analog inputs, 5 digital outputs, and 2 analog outputs. No Ethernet port is included. Control is via the keypad or remote contacts. The keypad shows motor speed in percent, output frequency, output current, output voltage, alarm codes, and function codes — enough for commissioning and basic fault-finding without a laptop. For remote operation, the drive accepts a dry-contact start/stop signal. The dynamic braking circuit is present, but no brake chopper is included — if you need rapid deceleration on a high-inertia fan, you'll add an external braking unit and resistor.","metaTitle":"FRN0261G2W-4GU Fuji FRENIC-Eco VFD, 200 hp, 240 A","metaDescription":"Fuji FRN0261G2W-4GU FRENIC-Eco VFD, 200 hp, 240 A output, 380-480 VAC input, NEMA 1. Active production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["AC Drive (VFD) 480V"],"specifications":{"Color":"Blue","Style":"Heat Sink","title":"FRN0261G2W-4GU","Series":"FRENIC - Eco","Displays":"Motor Speed With Percent, Alarm Code, Menu, Function Code","Enclosure":"Open","Standards":"UL508C, C22.2 No.14, EN50178-1997","Input Type":"Analog; Digital","Protection":"Drive Thermal Overload; Motor Thermal Overload; Over breaking; Overvoltage; Phase Failure; Phase to Phase or Phase to Ground Short Circuit; Under voltage","Application":"HV AC","Output Type":"Analog; Digital","description":"FUJI ELECTRIC Variable Frequency Drive: 460V AC, 200 hp Max Output Power, 240 A Max Output Current","Control Type":"Keypad, Remote","Display Type":"LCD, LED","Input Voltage":"460V AC","Overall Depth":"12-3/8 in","Overall Width":"20-7/8 in","Torque @ 1 Hz":"50%","Control Method":"Variable Frequency Control","Input Phase AC":"Three","Output Voltage":"480V AC","Overall Height":"29-1/8 in","Digital Readout":"Output Frequency, Output Current, Output Voltage","Dynamic Braking":"Yes","Input Frequency":"50/60 Hz","Output Phase AC":"Three","Starting Torque":"50%","lifecycle_stage":"current","Enclosure Rating":"NEMA 1","Number of Inputs":"(7) Digital; (3) Analog","Number of Outputs":"(5) Digital; (2) Analog","Start/Stop Control":"Programmable","Torque Application":"Variable Torque","Input Voltage Range":"380V-480V AC +10% / -15%","Maximum Output Power":"200 hp","Output Voltage Range":"0V AC to 460V AC","Brake Chopper Included":"No","Ethernet Port Included":"No","Maximum Output Current":"240 A","Output Frequency Range":"0.1 to 120 Hz","With Bypass / No Bypass":"No Bypass","Accepts Input Control Signal":"Remote Contact","Adjustable Acceleration Time":"0 to 3,600 sec","Adjustable Deceleration Time":"0 to 3,600 sec","With Line Contactor / No Line Contactor":"No Line Contactor"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/f850783d98a76d6cc1fbf268bd45b0cd.pdf","sourceUrl":null},"ai":{"faq":[{"question":"What are the key ratings for this drive?","answer":"The drive is rated for 200 hp maximum output power and 240 A maximum output current, with an input voltage range of 380-480 VAC +10%/-15% and an output frequency range of 0.1 to 120 Hz."},{"question":"What certifications does this drive carry?","answer":"It carries UL 508C, CSA C22.2 No.14, and EN 50178 certifications, covering the US, Canada, and European industrial markets."},{"question":"What is the closest alternative to this drive in the same family?","answer":"The FRENIC-Eco series includes constant-torque variants for applications like conveyors or extruders. If your load requires constant torque across the speed range, the constant-torque sibling would be the correct pick — this variable-torque unit is optimized for centrifugal loads like fans and pumps."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/fuji-electric/FRN0261G2W-4GU","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/fuji-electric/FRN0261G2W-4GU when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}