{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"FX1N-60MT-001","brand":"Mitsubishi Electric","brandSlug":"mitsubishi","productSlug":"FX1N-60MT-001","canonicalUrl":"https://aoctrl.com/mitsubishi/FX1N-60MT-001","factsUrl":"https://aoctrl.com/api/mcp/products/FX1N-60MT-001","rawCanonicalId":null},"summary":{"shortDescription":"Mitsubishi Electric FX1N series PLC, FX1N-60MT-001, 36 inputs, 128 output relay points, AC100-240V, 50/60Hz, EOL stage.","salesMarkdown":"## What the EOL status means for your BOM line The FX1N-60MT-001: No official successor order code is listed in the manufacturer's records. For a BOM that requires this exact model, the only path is the surplus and broker market — availability and pricing are confirmed at RFQ time, not before. ## I/O configuration and power supply This PLC provides 36 input points (X000–X177, octal numbering) and supports up to 128 output relay points (Y000–Y177) when expansion is used. The input format is sink-type with a rated voltage of AC100–240V at 50/60Hz. The power supply includes a 250V 3.15A fuse and draws an inrush current of up to 30A for 5ms at AC100V or 50A at AC200V. Grounding must be Class D (ground resistance 100Ω or less) per the specification. ## Program memory and real-time clock The program memory holds up to 8000 steps including file registers, with a comment capacity also at 8000 steps. A built-in real-time clock tracks dates from 1980 to 2079 with leap-year correction and a typical monthly deviation of ±45 seconds at 25°C. The clock is backed by a large-capacitor that charges in 30 minutes and holds the time for 10 days; an optional battery can extend backup. The PLC includes 256 special auxiliary relays (M8000–M8255), 384 general-purpose auxiliary relays (M0–M383), and 128 pointers for JUMP and CALL branch instructions (P0–P127). Timers include 200 on-delay 100ms timers (T0–T199, 0.1–3276.7 seconds) and 46-point 10ms timers (T200–T245, 0.01–327.67 seconds). ## Environmental and mechanical limits The FX1N-60MT-001 is rated for use in atmospheres free of corrosive gases, flammable gases, and conductive dust. It should not be used in pressurized environments above 2000m or under conditions exceeding atmospheric pressure, as failure risk increases.","metaTitle":"Mitsubishi FX1N-60MT-001 PLC, 36 inputs, AC100-240V, EOL","metaDescription":"Mitsubishi FX1N-60MT-001 PLC with 36 inputs, 128 output relay points, AC100-240V supply, 50/60Hz.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["PLCs (Programmable Logic Controllers)"],"specifications":{"10ms":"T200 ~ T245 46-point (0.01 to 327.67 seconds)","Other":"You can use the built-in analog volume two points as an analog timer VR1: D8030, VR2: D8031 2 points (0 to 255)","State":"Initial state (EEPROM keep) : S0 ~ S9 10 points * Notes on the keep area keep area and non-keep-area is fixed. (Change is not allowed in the parameter) in order to reliably keep the EEPROM is required energizing time of the sequencer is more than five consecutive minutes.","title":"FX1N-60MT-001","Device":"Input and output relay : Input relay : X000 ~ X177 128 points (octal number) extension when used with","Ground":"D Grounding Class (Ground Resistance: 100Omu Or Less) Ground, Please Dedicated Ground Or Shared Ground.","Impact":"147M / S 2, Action Time 11Ms, X At Half-Sine Pulse, Y, Z 3 Times Each Direction Criterion, According To IEC61131-2","ON OFF":"Y000, Y001: 5 s following Y002 later: 0.2ms or less","Counter":"16-bit up : C0 ~ C15 16 points (0 to 32,767 counts)","Nesting":"[Master control] N0 N7 8 points (for MC instruction)","Pointer":"JUMP, for CALL branch : P0 ~ P127 128 points (CJ instruction, for the CALL instruction, for the END jump P63)","Constant":"Decimal number (K) : 16-bit: -32,768 + 32,767 32-bit: -2,147,483,648 ~ + 2,147,483,647","Frequency":"57 ~ 150Hz : Acceleration: 9.8M / S 2 X, Y, Z Each Direction 10 Times (For A Total Of Each 80 Minutes) Criteria, According To IEC61131-2","Peak load":"Resistance load : 0.5A or less / output per point 0.8A or less / COM terminal per one","Anti-noise":"Noise voltage 1,000Vp-p, noise width 1 s, due to rising 1ns, cycle 30 ~ 100Hz of noise simulator","ON voltage":"1.5V","Power Fuse":"250V 3.15A","For special":"M8000 ~ M8255 256 points","Total score":"128 points or less (at the time of expansion in combination)","description":"Fx1n Series Programmable Controllers","Advanced use":"Or Less 2,000M Can Not Be Used Under The Pressurized Environment To More Than Atmospheric Pressure. There Is A Possibility Of Failure.","Input format":"sink","Output relay":"Y000 ~ Y177 128 points (octal number) extension when used with","Rated voltage":"AC100 ~ 240V","Response time":"OFF ON : Y000, Y001: 5 s following Y002 later: 0.2ms or less","X010 or later":"More than 3.5mA","Inductive load":"12W / DC24V","Inrush current":"Maximum 30A 5ms or less / AC100V, maximum 50A 5ms or less / AC200V","Program memory":"The maximum memory capacity : 8000 step comment, up to 8000 steps, including the file register","Use atmosphere":"Corrosive, there is no flammable gas, conductive dust (dust) that is not terribly","Auxiliary relay":"For general use : M0 ~ M383 384 points","Hexadecimal (H)":"16-bit: 0 FFFF 32 bit: 0 ~ FFFFFFFF","Input impedance":"X000 ~ X007 : 3.3k","Input interrupt":"I00 ~ I50 6 points","Rated frequency":"50 / 60Hz","Real-time clock":"Clock function : Built from 1980 to 2079 years (with leap year correction) The year 2-digit / 4-digit switch, monthly deviation ± 45 seconds (25 ) * Notes on the clock function the current time a large-capacity capacitor of the clock that is built-in (built-in) in has been backed up. Large-capacity capacitor (built-in) becomes a full charge in the current time of 30 minutes, and holds the current value of 10 days. In addition, it can also be held in the battery when you use the optional battery.","Shipping Weight":"1.8 Kg","lifecycle_stage":"eol_hot","32-Bit Up / Down":"C200 ~ C219 20 points (-2,147,483,648 ~ + 2,147,483,647 count)","For 16-bit index":"V0 ~ V7, Z0 ~ Z7 16 points","Number of inputs":"36 points (40) in () is the number of occupied, the difference between the effective number is empty number.","Timer (on-delay)":"100ms : T0 ~ T199 200 points (0.1 to 3,276.7 seconds)","Maximum frequency":"100kHz","Number of outputs":"24 points","Power consumption":"35W includes input current worth of (per point 7mA or 5mA,).","Relative humidity":"35 ~ 85% RH (non-condensing) ..... operation","Withstand voltage":". When Performing A Withstand Voltage Test, Please Go Between The Ground Terminal Of Each Terminal And The Basic Unit At A Voltage Of Below Power Supply Terminal (AC Power) And Between The Ground Terminal: AC1.5KV 1 Minute DC24V Service Power Supply, And Input Terminal The (DC24V) And Between The Ground Terminal: AC500V 1 Minute Output Terminal (Transistor) And Between The Ground Terminal: AC500V 1 Minute","16 Bit For Special":"D8000 ~ D8255 256 points","Circuit insulation":"Photocoupler","High-speed counter":"[32-bit high-speed up / down (EEPROM keep)] C235 C255 1 phase: 60KHz, 10KHz 2 phase: 30kHz, 5kHz There is a limit to the number and input frequency that can be used by the conditions used. * Notes on the keep area keep area and non-keep-area is fixed. (Change is not allowed in the parameter) in order to reliably keep the EEPROM is required energizing time of the sequencer is more than five consecutive minutes.","Ambient temperature":"0 ~ 55 ····· operation, -20 ~ 70 ····· during storage","DC24V service power":"400mA is unrelated to the expansion block of connection.","Estimated Lead Time":"1-10 Working Days.","Input response time":"About 10Ms X000 X007 has a built-in digital filter, can be changed in 1ms unit to 0 ~ 15ms by the D8020. If 0 is specified, X000, X001 is 10 s, X002 ~ X007 will be 50 s.","Input signal format":"No-voltage contact input NPN open collector transistor","Protective function":"There is password protection function (by keyword function)","Type of instruction":"Basic instruction : Sequence Instruction: 27 -step ladder instructions: two","File register (keep)":"D1000 ~ D7999 maximum 7000 points (the program area in the 500-point units from the D1000 by the parameter as a file register (set to EEPROM) Allowed)","Input signal current":"X000 ~ X007 : 7mA / DC24V","Input signal voltage":"DC24V ± 10%","Output type / format":"Transistor / sink output","Programming language":"Sequence program","Vibration resistance":"When the DIN rail mounting : Frequency: 10 ~ 57Hz : Amplitude Half: 0.035Mm X, Y, Z Each Direction 10 Times (For A Total Of Each 80 Minutes) Criteria, According To IEC61131-2","1 Phase 1 Count Input":"[C235, C236] Up To Two Points: The Best 60KHz High Speed Compared To SET / RESET When Using: 30KHz [C237 C245] Up To 4 Points: Up To 10KHz High Speed Compared To SET / RESET When Using: 10KHz Sequencer Is Processed By The High-Speed Counter And Pulse Density Instruction The Sum Of The Frequency (The Two-Phase Counter Summing Up The 2 Times The Input Frequency) Is A 60KHz Maximum. During The High-Speed Comparison SET / RESET Use, The Sum Of the frequency at which the sequencer is treated with high-speed counter and pulse density instruction (the two-phase counter summing up the 2 times the input frequency) is the maximum 30kHz is.","1-Phase 2-Count Input":"[C246] Up To One Point: The Best 60KHz High Speed Compared To SET / RESET When Using: 30KHz [C247 C250] Up To Two Points: The Best 10KHz High Speed Compared To SET / RESET When Using: 10KHz Frequency At Which The Sequencer Is Treated With High-Speed Counter And Pulse Density Instruction (The Two-Phase Counter Summing Up The 2 Times The Input Frequency) Of The Total Is 60KHz Maximum. During The High-Speed Comparison SET / RESET Use, The Sum Of The Frequency at which the sequencer is treated with high -speed counter and pulse density instruction (the two-phase counter summing up the 2 times the input frequency) is the maximum 30kHz is.","2-Phase 2-Count Input":"[C251] Up To One Point: The Best 30KHz High Speed Compared To SET / RESET When Using: 15KHz [C252 C255] Up To Two Points: The Best 5KHz High Speed Compared To SET / RESET When Using: 5KHz High-Speed Counter And Pulse Density Instruction Frequency On Which The Sequencer Process In (The Two-Phase Counter Summing Up The 2 Times The Input Frequency) Of The Total Is 60KHz Maximum. During The High-Speed Comparison SET / RESET Use, The Sum Of The Frequency At which the sequencer is treated with high- speed counter and pulse density instruction (the two-phase counter summing up the 2 times the input frequency) is the maximum 30kHz is.","External power supply":"DC5 ~ 30V","Insulation resistance":". When Performing The Insulation Resistance Test, Please Go Between The Ground Terminal Of Each Terminal And The Basic Unit At A Voltage Of Below Power Supply Terminal (AC Power) And Between The Ground Terminal: DC500V 5Emuomega More In Insulation Resistance Tester DC24V Service Power Supply , And The Input Terminal (DC24V) And Between The Ground Terminal: DC500V 5Emuomega More In Insulation Resistance Tester And The Output Terminal (Transistor) Ground Terminal Between: DC500V 5Emuomega More In Insulation Resistance Tester","For Keep (EEPROM keep)":"S10 ~ S127 118 points * Notes on the keep area keep area and non-keep-area is fixed. (Change is not allowed in the parameter) in order to reliably keep the EEPROM is required energizing time of the sequencer is more than five consecutive minutes.","Input connection shape":"Removable terminal block (M3 screws)","16-bit up (EEPROM keep)":"C16 ~ C31 16 points (0 to 32,767 counts) * Notes on the keep area keep area and non-keep-area is fixed. (Change is not allowed in the parameter) in order to reliably keep the EEPROM is required energizing time of the sequencer is more than five consecutive minutes.","Allowable voltage range":"AC85 ~ 264V","Input Operation Display":"Input ON when the LED lights up","Input and output points":"Number of inputs : 128 points or less (at the time of expansion combination) However, the following 128 points in the input and output total","Output connection shape":"Terminal block (M3 screws)","Positioning instruction":"ABS Current Value · Read ([D] ABS) · Homing [ZRN] (Without DOG Search Function) Near Point DOG: To Slow Down In The ON, The Near Point DOG:. Stops At OFF (Homing Operation Of Counting The Zero- Signal And Different Point From) , Variable-Speed Pulse Output [PLSV] , Relative Positioning [DRVI] - Absolute Positioning [DRVA] Pulse Output Format: Pulse Train Tasu Direction","Application Instructions":"3.7 to the number of 100 s / instruction","Corresponding basic unit":"Transistor output type basic unit","Input circuit insulation":"Photocoupler","Output operation display":"Photocoupler drive when LED lighting","Pulse output instruction":"Output Pulse (PLSY) , Acceleration And Pulse Output With Speed (PLSR) Pulse Output Format: Pulse Train (The Direction Is Controlled By The Sequence)","For Keep (capacitor keep)":"S128 ~ S999 872 points * Notes on the keep area keep area and non-keep-area is fixed. (Parameter change is not allowed) large-capacity capacitor (built-in) becomes a full charge in the current time of 30 minutes, and holds the current value of 10 days. When the voltage of the large-capacity capacitor is reduced there is that the state of the capacitor keep the device can not be properly maintained. Or when used for the first time after purchasing the FX1N Series PLC, when you want to use after the state that does not put a long time power supply, please initialize the capacitor keep the device. Also, before you resume operation, please do the setting of the device and the current time necessary for the operation.","Number of controlled axes":"Independent 2-axis","16-Bit Up (Capacitor Keep)":"C32 ~ C199 168 points (0 to 32,767 counts) * Notes on the keep area keep area and non-keep-area is fixed. (Parameter change is not allowed) large-capacity capacitor (built-in) becomes a full charge in the current time of 30 minutes, and holds the current value of 10 days. When the voltage of the large-capacity capacitor is reduced there is that the state of the capacitor keep the device can not be properly maintained. Or when used for the first time after purchasing the FX1N Series PLC, when you want to use after the state that does not put a long time power supply, please initialize the capacitor keep the device. Also, before you resume operation, please do the setting of the device and the current time necessary for the operation.","Arithmetic processing speed":"Basic instruction : 0.55 ~ 0.7 s / instruction","Direct mounting at the time":"Frequency: 10 ~ 57Hz : Amplitude Half: 0.075 mm X, Y, Z Each Direction 10 Times (For A Total Of Each 80 Minutes) Criteria, According To IEC61131-2","Input ON sensitivity current":"X000 ~ X007 : More than 4.5mA","Open circuit leakage current":"0.1mA / DC30V","16 bit for Keep (EEPROM keep)":"D128 ~ D255 128 points * Notes on the keep area keep area and non-keep-area is fixed. (Change is not allowed in the parameter) in order to reliably keep the EEPROM is required energizing time of the sequencer is more than five consecutive minutes.","Input OFF sensitivity current":"1.5mA or less","RUN during the write function":"Yes (can change programs during the sequencer RUN)","Remote I / O points (CC-Link)":"The actual I / O, including below 128 points","Memory cassette (memory board)":"FX1N-EEPROM-8L (8000 step EEPROM)","Input and output control method":"Batch processing method (END when the instruction is executed), input and output refresh command, Pulse catch function","16 bit for Keep (capacitor keep)":"D256 ~ D7999 7744 points * Notes on the keep area keep area and non-keep-area is fixed. (Parameter change is not allowed) large-capacity capacitor (built-in) becomes a full charge in the current time of 30 minutes, and holds the current value of 10 days. When the voltage of the large-capacity capacitor is reduced there is that the state of the capacitor keep the device can not be properly maintained. Or when used for the first time after purchasing the FX1N Series PLC, when you want to use after the state that does not put a long time power supply, please initialize the capacitor keep the device. Also, before you resume operation, please do the setting of the device and the current time necessary for the operation.","32-Bit Up / Down (Capacitor Keep)":"C220 ~ C234 15 points (-2,147,483,648 ~ + 2,147,483,647 count) * Notes on the keep area is keep the area and non-keep-area is fixed. (Parameter change is not allowed) large-capacity capacitor (built-in) becomes a full charge in the current time of 30 minutes, and holds the current value of 10 days. When the voltage of the large-capacity capacitor is reduced there is that the state of the capacitor keep the device can not be properly maintained. Or when used for the first time after purchasing the FX1N Series PLC, when you want to use after the state that does not put a long time power supply, please initialize the capacitor keep the device. Also, before you resume operation, please do the setting of the device and the current time necessary for the operation.","The arithmetic and control system":"Stored program repeat operation method, there interrupt instruction","Built-in memory capacity and format":"8000 step EEPROM (memory backup required)","1ms Integration Type (Capacitor Keep)":"T246 ~ T249 4 points (0.001 to 32.767 seconds) * Notes on the keep area is keep the area and non-keep-area is fixed. (Parameter change is not allowed) large-capacity capacitor (built-in) becomes a full charge in the current time of 30 minutes, and holds the current value of 10 days. When the voltage of the large-capacity capacitor is reduced there is that the state of the capacitor keep the device can not be properly maintained. Or when used for the first time after purchasing the FX1N Series PLC, when you want to use after the state that does not put a long time power supply, please initialize the capacitor keep the device. Also, before you resume operation, please do the setting of the device and the current time necessary for the operation.","Allowable momentary power failure time":"10ms will continue to operate for the momentary power failure follows.","100ms Integration Type (Capacitor Keep)":"T250 ~ T255 6 points (0.1 to 3,276.7 seconds) * Notes on the keep area is keep the area and non-keep-area is fixed. (Parameter change is not allowed) large-capacity capacitor (built-in) becomes a full charge in the current time of 30 minutes, and holds the current value of 10 days. When the voltage of the large-capacity capacitor is reduced there is that the state of the capacitor keep the device can not be properly maintained. Or when used for the first time after purchasing the FX1N Series PLC, when you want to use after the state that does not put a long time power supply, please initialize the capacitor keep the device. Also, before you resume operation, please do the setting of the device and the current time necessary for the operation.","Data register (32-bit in the pair used)":"16-bit general purpose : D0 ~ D127 128 points"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$136.00","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/e12845187b11551815459c77b967a941.pdf","sourceUrl":null},"ai":{"faq":[{"question":"What is the program memory capacity of FX1N-60MT-001?","answer":"Maximum program memory is 8000 steps, including file registers. Comment capacity is also 8000 steps."},{"question":"Does FX1N-60MT-001 have a real-time clock?","answer":"Yes, it includes a built-in real-time clock covering years 1980–2079 with leap-year correction and typical monthly deviation of ±45 seconds at 25°C. The clock is backed by a large capacitor that holds time for 10 days after a 30-minute charge; an optional battery can extend backup."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/mitsubishi/FX1N-60MT-001","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/mitsubishi/FX1N-60MT-001 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}